REMKO HTS 130 Instructions Manual Download Page 5

1.6  Safety notes for the operator

The operational safety of the units and compo-

nents is only assured providing they are used as

intended and in a fully assembled state.

n

The units and components may only be set up,

installed and maintained by qualified per-

sonnel.

n

Protective covers (grille) over moving parts

must not be removed from units that are in

operation.

n

Do not operate units or components with

obvious defects or signs of damage.

n

Contact with certain unit parts or components

may lead to burns or injury.

n

The units and components must not be

exposed to any mechanical load, extreme

levels of humidity or extreme temperature.

n

Spaces in which refrigerant can leak sufficient

to load and vent. Otherwise there is danger of

suffocation.

n

All housing parts and device openings, e.g. air

inlets and outlets, must be free from foreign

objects, fluids or gases.

n

The units must be inspected by a service tech-

nician at least once annually. Visual inspec-

tions and cleaning may be performed by the

operator when the units are disconnected from

the mains.

1.7  Safety notes for installation,

maintenance and inspection

n

Appropriate hazard prevention measures must

be taken to prevent risks to people when per-

forming installation, repair, maintenance or

cleaning work on the units.

n

The setup, connection and operation of the

units and its components must be undertaken

in accordance with the usage and operating

conditions stipulated in this manual and comply

with all applicable regional regulations.

n

Local regulations and laws such as Water

Ecology Act must be observed.

n

The power supply should be adapted to the

requirements of the units.

n

Units may only be mounted at the points pro-

vided for this purpose at the factory. The units

may only be secured or mounted on stable

structures, walls or floors.

n

Mobile units must be set up securely on suit-

able surfaces and in an upright position. Sta-

tionary units must be permanently installed for

operation.

n

The units and components should not be oper-

ated in areas where there is a heightened risk

of damage. Observe the minimum clearances.

n

The units and components must be kept at an

adequate distance from flammable, explosive,

combustible, abrasive and dirty areas or

atmospheres.

n

Safety devices must not be altered or

bypassed.

1.8  Unauthorised modification

and changes

Modifications or changes to units and components

are not permitted and may cause malfunctions.

Safety devices may not be modified or bypassed.

Original replacement parts and accessories

authorised by the manufactured ensure safety. The

use of other parts may invalidate liability for

resulting consequences.

1.9  Intended use

Depending on the model, the equipment and the

additional fittings with which it is equipped is only

intended to be used as an air-conditioner for the

purpose of cooling or heating the air in an

enclosed room.

Any different or additional use shall be classed as

non-intended use. The manufacturer/supplier

assumes no liability for damages arising from such

use. The user bears the sole risk in such cases.

Intended use also includes working in accordance

with the operating and installation instructions and

complying with the maintenance requirements.

Under no circumstances should the threshold

values specified in the technical data be exceeded.

1.10  Warranty

For warranty claims to be considered, it is essential

that the ordering party or its representative com-

plete and return the "certificate of warranty" to

REMKO GmbH & Co. KG at the time when the

units are purchased and commissioned.

The warranty conditions are detailed in the "Gen-

eral business and delivery conditions". Further-

more, only the parties to a contract can conclude

special agreements beyond these conditions. In

this case, contact your contractual partner in the

first instance.

 

 

 

 

 

5

Summary of Contents for HTS 130

Page 1: ...Electrical wiring Read the instructions prior to performing any task REMKO HTS 90 130 200 260 Air water heat pump with inverter technology Instructions for the Technician 0092 2015 03 Version 1 en_GB...

Page 2: ...rating instructions carefully before commis sioning using this device These instructions are an integral part of the system and must always be kept near or on the device Subject to modifications No li...

Page 3: ...ral 7 2 1 System layout 7 2 2 General notes 9 2 3 Electrical connection indoor module 10 2 4 Electrical connection outdoor module 10 2 5 Electrical configuration I O module 13 2 6 Terminal block key 1...

Page 4: ...ay be fatal or cause serious injury WARNING This combination of symbol and signal word warns of a potentially hazardous situation which if not avoided may be fatal or cause serious injury CAUTION This...

Page 5: ...s or floors n Mobile units must be set up securely on suit able surfaces and in an upright position Sta tionary units must be permanently installed for operation n The units and components should not...

Page 6: ...ion and recycling Disposal of packaging All products are packed for transport in environ mentally friendly materials Make a valuable contri bution to reducing waste and sustaining raw mate rials Only...

Page 7: ...tween indoor and outdoor modules condensate heating control wire 0 10V e g 5 x 1 mm2 power inlet 3 x 1 5 mm2 sensor cable sheathed 2 x 1 0 mm2 4 Refrigerant lines 3 8 and 5 8 5 Inlet 6 Return flow 7 P...

Page 8: ...cable sheathed 2 x 1 0 mm2 4 Refrigerant lines 3 8 and 5 8 5 Inlet 6 Return flow 7 Mains supply line indoor module 400V 3 50Hz 16A e g 5 x 2 5 mm2 Control power controller 230V 1 50Hz 16A e g 3 x 1 5...

Page 9: ...for this purpose con tact closed signifies release while contact open signifies an off period n Special rates for heat pumps may be offered by the power company utility n Ask your local power company...

Page 10: ...connec tion schematic and or the circuit diagram in the control box NOTICE Ensure correct polarity when connecting the electrical leads especially the control cable The number of lines and the sensor...

Page 11: ...sensor provided for use as a domestic hot water sensor S08 n When connecting up a solar system use a PT 1000 sensor S01 as a collector sensor and a PT 1000 sensor S02 as the lower storage tank sensor...

Page 12: ...und It may not be subjected to direct sunlight and is to be protected against excessive wind Installation above windows or air ducts is to be avoided n In order to carry out the installation remove th...

Page 13: ...n e S s t u p n I r o s n e S D N G 9 0 S D N G 0 1 S 1 S D N G 1 D N G 2 1 S D N G 3 1 S D N G 4 1 S D N G 5 1 S D N G 6 1 S s t u p t u O e e r F l a i t n e t o P 0 3 A 0 3 A 1 3 A 2 3 A 3 3 A 4 3...

Page 14: ...xed heating circuit INL S13 X Heat pump inlet S14 X 2nd mixed heating circuit RF S15 X Heat pump RF S16 X EVU contact NC dewpoint monitoring external open locked closed release S20 X Not connected S21...

Page 15: ...nnected A32 X Enable 2nd WE booster heating or boiler A33 X Not connected A34 X General fault external A40 X Speed setting solar pump PWM A41 X Speed specification 1st mixed heating circ 0 10V A42 X S...

Page 16: ...5 x 1 5 mm2 4 Control cable outdoor module 0 10V sheathed sensor cable sheathed e g 5 x 1 0 mm2 5 Sensor cable on outdoor sensor e g 2 x 1 0 mm2 6 Mains supply line to control unit I O module 230V 1...

Page 17: ...Hz 16A e g 5 x 2 5 mm2 3 Terminals in indoor module 4 Terminals on electrical heating coil 5 Mains supply line to control unit I 0 module 230V 1 50Hz e g 3 x 1 5 mm2 Electrical connections between ind...

Page 18: ...g 5 x 1 5 mm2 4 Control cable outdoor module 0 10V sheathed Sensor cable sheathed e g 5 x 1 0 mm2 5 Sensor cable on outdoor sensor e g 2 x 1 0 mm2 6 Mains supply line to control unit I O module 230V 1...

Page 19: ...Hz 16A e g 5 x 2 5 mm2 3 Terminals in indoor module 4 Terminals on electrical heating coil 5 Mains supply line to control unit I 0 module 230V 1 50Hz e g 3 x 1 5 mm2 Electrical connections between ind...

Page 20: ...ing 230V 1 50Hz 10A e g 5 x 1 5 mm2 5 Control line outdoor module 1 sheathed sensor cable sheathed e g 5 x 1 0 mm2 6 Control line outdoor module 2 sheathed e g 3 x 1 0 mm2 7 Sensor cable on outdoor se...

Page 21: ...stomer provided sub distribution D Outdoor sensor E Electrical heating coil 1 Mains supply line indoor module 400V 3 50Hz 16A e g 5 x 2 5 mm2 2 Mains supply line booster heating 400V 3 50Hz 16A e g 5...

Page 22: ...5 6 Signal cable 0 10V 6 7 GND 7 8 Response signal 8 9 Temperature sensor 9 10 GND 10 Electrical connections between indoor module and outdoor module 2 Indoor module Outdoor module 2 Terminal Descrip...

Page 23: ...heating 230V 1 50Hz 10A e g 5 x 1 5 mm2 5 Control line outdoor module 1 sheathed sensor cable sheathed e g 5 x 1 0 mm2 6 Control line outdoor module 2 sheathed e g 3 x 1 0 mm2 7 Sensor cable on outdo...

Page 24: ...r provided sub distribution D Outdoor sensor E Electrical heating coil 1 Mains supply line indoor module 400V 3 50Hz 20A e g 5 x 2 5 mm2 2 Mains supply line booster heating 400V 3 50Hz 16A e g 5 x 2 5...

Page 25: ...ional 5 6 Signal cable 0 10V 6 7 GND 7 8 Response signal 8 9 Temperature sensor 9 10 GND 10 Electrical connections between indoor module and outdoor module 2 Indoor module Outdoor module 2 Terminal De...

Page 26: ...mweiss SMT I O HTS Project 1 12 14 2015 1 15 Electricity meter S0 Heat pump Electricity meter S0 Household Medium flow rate Electricity meter S0 PV yield Electricity meter S0 PV feed in Pump PWM Solar...

Page 27: ...I3 DI4 DI5 DI6 DI7 DIC7 GND Y1 Y2 Y3 Y4 B8 B9 B10 B11 B12 GND DI8 DI9 DI10 DIC2 2 2 3 6 4 4 1 5 3 1 pLAN 5 4 1 6 2 3 RCCB1 Refrigerant circuit control board mweiss 6 17 2014 mweiss HTS RCCB 2 15 Proje...

Page 28: ...3 2014 mweiss INV ODU HTS 3 12 14 2015 3 15 Cooling cycle feedback control Outdoor unit Cooling cycle feedback control Outdoor unit Cooling cycle feedback control Only on HTS 200 and HTS 260 Connectio...

Page 29: ...indoor module 14 4 380V supply Power supply Supply Provided by the customer Power supply 230V supply 380V output Compressor 380V scroll Power supply RCCB Power supply Inv Power supply IT Power supply...

Page 30: ...8 9 10 11 6 25 2014 mweiss Supply 5 12 14 2015 5 15 230V supply 230V input Digital output Terminal block indoor module 14 4 380V supply Power supply 230V supply 380V output Compressor Power supply RC...

Page 31: ...ge Standard mweiss 0 1 2 3 4 5 6 7 8 9 10 11 0 1 2 3 4 5 6 7 8 9 10 11 6 25 2014 mweiss Communication 6 12 14 2015 6 15 Communication Communication Communication Com RCCB Com Inverter Com Control ele...

Page 32: ...MT I O sheet 1 7 12 14 2015 7 15 Sensor PT1000 Collector probe Sensor PT1000 Storage tank bottom solar Sensor PT1000 Solar inlet Sensor PT1000 Solar return flow Sensor PT1000 impulse sensor Circulatio...

Page 33: ...10 11 0 1 2 3 4 5 6 7 8 9 10 11 6 25 2014 mweiss SMT I O sheet 2 8 12 14 2015 8 15 Sensor PT1000 Outside temperature Sensor PT1000 Sensor PT1000 Sensor PT1000 Inlet sensor Sensor PT1000 Medium flow r...

Page 34: ...andard mweiss 0 1 2 3 4 5 6 7 8 9 10 11 0 1 2 3 4 5 6 7 8 9 10 11 6 25 2014 mweiss SMT I O sheet 3 9 12 14 2015 9 15 Medium flow rate Medium flow rate Impulse Heat pump current Electricity meter S0 Do...

Page 35: ...mp 230V unmix heating cycle Pump uncontrolled Pump 230V Circulation Pump uncontrolled Changeover valve 230V Hot water Changeover valve Changeover valve 230V 2nd heat generator Changeover valve Solar p...

Page 36: ...s SMT I O sheet 5 11 12 14 2015 11 15 Pump 230V 2nd mix heating cycle Pump uncontrolled Changeover valve pump 230V Cooling cycle Changeover valve Cooling cycle Pump uncontrolled Mixer 230V 1st mix hea...

Page 37: ...014 mweiss SMT I O sheet 6 12 12 14 2015 12 15 Solar cycle Pump PWM Pump 0 10V 1st mix heating cycle Pump 0 10V Pump 0 10V unmix heating cycle Pump 0 10V 230V supply Pump PWM Internal Pump PWM Pump 0...

Page 38: ...10 11 0 1 2 3 4 5 6 7 8 9 10 11 2 10 2015 mweiss RCCB sheet 1 HTS Projekt 14 12 14 2015 13 15 Supply Return flow temp Analogue Input Inlet flow temp Terminal block indoor module Digital Input High pr...

Page 39: ...s Standard mweiss 0 1 2 3 4 5 6 7 8 9 10 11 0 1 2 3 4 5 6 7 8 9 10 11 6 25 2014 mweiss RCCB sheet 1 15 12 14 2015 14 15 Supply Return flow temp Inlet flow temp Analogue Input Terminal block indoor mod...

Page 40: ...0 1 2 3 4 5 6 7 8 9 10 11 6 26 2014 mweiss RCCB sheet 2 16 12 14 2015 15 15 Electronic expansion valve Activation Eev Digital output 4 way valve 230V input Changed Replaced by Date of creation Origin...

Page 41: ...95 C 30 C 78 C 21 24 11 14 K2 5 11 14 9 21 24 9 11 14 10 Changed Replaced by Standard Date of creation Origin Drafted by Checked Date of issue Sheet title Project title mweiss Status 0 1 2 3 4 5 6 7...

Page 42: ...78 C 21 24 11 14 K2 5 11 14 9 21 24 9 11 14 10 Changed Replaced by Standard Date of creation Origin Drafted by Checked Date of issue Sheet title Project title mweiss Status 0 1 2 3 4 5 6 7 8 9 10 11 0...

Page 43: ...vi violet vio violet yel yellow Miscellaneous Circ Circulation Com Communication Eev Electronic expansion valve EVU Electrical power company HC Heating cycle HW Hot water INL Inlet mix Mixed PV Photov...

Page 44: ...ty Dangers of failure to observe the safety notes 4 General 4 Identification of notes 4 Notes for inspection 5 Notes for installation 5 Notes for maintenance 5 Personnel qualifications 4 Safety notes...

Page 45: ...45...

Page 46: ...REMKO HTS 46...

Page 47: ......

Page 48: ...t as advisers to our customers in air conditioning and heating technology SFlbCustomer Service Our equipment operates precisely and reliably However in the event of a fault REMKO customer service is q...

Reviews: