REMKO AMT 115-E Manual Download Page 4

It is evident that the corrosion rate 
below 50% relative humidity 
(RH) is low, and below 40% is 
negligible. 
 
The corrosion rate increases 
significantly above 60% RH. 
This threshold for damage 
as the result of humidity also 
applies to other materials, such 
as powdery substances, packaging, 
wood and electronic units.

Buildings may be dried in a variety 
of ways:

1.  

By heating and
air exchange:

   The air in the room is heated 

in order for moisture to be 
removed and then this air is fed 
outside. All of the energy that is 
involved is lost together with 
the moist air that is released.

2.  

By air dehumidification:

   The moist air that is 

present within an enclosed 
space is continuously 
dehumidified according 
to the condensation principle.

The correlations occurring when 
air is dehumidified are based 
on physical laws.  
These are depicted here 
in graphical form in order 
to provide you with a brief 
overview of the principles of air 
dehumidification.

The use of 
REMKO air dehumidifiers

–   Even if windows and doors 

are well insulated, water and 
moisture are still capable of 
penetrating thick concrete walls.

–   The water required for setting 

in the production of concrete, 
mortar and plaster etc. may only 
be diffused after 1-2 months.

–   Even moisture trapped 

in the masonry after high-
water or a flood is released very 
slowly.

–   The same is also true of 

moisture contained in stored 
materials for example.

The moisture (water vapour) 
released from parts of a building 
or materials is absorbed by 
the surrounding air. As a result, 
the moisture content increases, 
which ultimately gives rise 
to corrosion, mould, rot, peeling 
of paint and other unwanted 
damage.

By way of example, the diagram 
shows the corrosion rate of metal 
in different levels of humidity.

Air dehumidification

With regard to energy 
consumption, air 
dehumidification has one distinct 
advantage: 

Energy expenditure is limited 
exclusively to the air volumes 
present. The mechanical 
heat that is released by 
the dehumidification process is fed 
back into the room. 

Under normal use, the air 
dehumidifier uses approximately 
25% of the energy that is 
required for the "heating and 
ventilating" principle.

Relative air humidity

Our ambient air is a gaseous 
mixture which always contains 
a certain volume of water 
in the form of water vapour. 
This volume of water is specified 
in g per kg of dry air (absolute 
moisture content).

1m

3

 of air weighs approx. 1.2 kg 

at 20°C

Depending on the temperature, 
each kg of air is only capable 
of absorbing a certain volume 
of water vapour. Once this 
capacity has been reached, the air 
is referred to as "saturated" 
and has a relative humidity (RH) 
of 100%. 

Relative humidity is understood 
to mean the ratio between 
the current quantity of water 
vapour in the air and the maximum 
possible quantity of water vapour 
at the same temperature. 

The ability of the air to absorb 
water vapour increases 
as the temperature rises.  
I.e. the maximum possible 
(absolute) water content becomes 
greater as the temperature rises.

4

REMKO AMT

Summary of Contents for AMT 115-E

Page 1: ...Edition GB D09 REMKO AMT Air dehumidifiers Operation Technology Spare parts REMKO AMT 45 E to 115 E...

Page 2: ......

Page 3: ...ts Air dehumidification 4 Safety notes 6 Intended use 7 Customer service and guarantee 7 Environmental protection and recycling 7 Unit description 8 Set up 9 Commissioning 10 Shutdown 12 Transportatio...

Page 4: ...isture water vapour released from parts of a building or materials is absorbed by the surrounding air As a result the moisture content increases which ultimately gives rise to corrosion mould rot peel...

Page 5: ...the dew point making it easier for the temperature to fall below it Building materials and structures are capable of absorbing considerable volumes of water such as brick 90 190 l m heavy concrete 140...

Page 6: ...quality inspections prior to delivery However dangers can result from the units if they are used improperly or not as intended by untrained personnel The following notes must be observed in full The...

Page 7: ...on a wooden pallet The packaging materials are environmentally friendly and can be recycled By recycling packaging materials you make a valuable contribution to the reduction of waste and conservation...

Page 8: ...d enough for rime formation to occur rendering defrosting unnecessary Therefore the air dehumidifiers work economically The cooled and dehumidified air is re heated by the condenser heat exchanger and...

Page 9: ...osed to the neighbouring atmosphere Air circulation is improved if the unit is set up approx 1 m above the ground Avoid having opened windows and doors etc and avoid frequent entry to or exit from the...

Page 10: ...mmissioning Control panel 1 2 3 4 1 Operating hours counter 2 Operating switch with Indicator light 3 YELLOW indicator light Container full 4 RED indicator light Malfunction overheating Operation with...

Page 11: ...tainer either continuously or only during the defrosting phases The condensate is fed into the condensate container below via a connection nozzle not AMT 45 E and AMT 115 E A float is located inside t...

Page 12: ...is fed into a lower drain via a hose pipe This variant enables unattended permanent operating mode AMT 115 E condensate drain Due to their high dehumidification capacity the AMT 115 E units are not eq...

Page 13: ...tion and protective clamp This can also be dismantled easily if required When transporting the units observe the following 1 Before each change of location switch off the unit and remove the power plu...

Page 14: ...ry Check the evaporator for ice or rime formation If ice has formed check the functionality of the automatic defrost and the temperature sensor If the unit fails to function correctly after the checks...

Page 15: ...riebs stunden F 3 15 A 1 0 A 2 1 4 3 2 1 4 3 Kondensatpumpe optional SCHWARZ WEISS VIOLETT VIOLETT Steckdose am Ger t Stecker F hler C Verdampfer Kondensator F hler Wasser Stop Lampe St rung Lampe Was...

Page 16: ...ions and design as part of the ongoing technical development process Exploded view of the AMT 45 E unit 4 5 6 8 10 11 12 13 14 15 2 1 16 17 20 21 26 27 22 25 25 30 29 32 33 35 34 38 37 36 39 40 45 46...

Page 17: ...909 18 Operating condenser 1105910 20 Inspection housing part cpl 1105618 21 Completion panel 1105619 22 Base plate 1105956 23 Axle 1105621 24 Base plate rubber stop set 1105622 25 Wheel 1102155 26 Hu...

Page 18: ...design as part of the ongoing technical development process Exploded view of the AMT 65 E and 85 E units 3 6 7 8 2 1 5 10 11 12 13 14 15 16 17 20 21 22 25 25 23 18 29 30 31 40 35 39 37 36 50 51 48 52...

Page 19: ...t cpl 1105671 1105671 21 Completion panel 1105647 1105647 22 Base plate 1105957 1105957 23 Axle 1105673 1105673 24 Base plate rubber stop set 1105622 1105622 25 Wheel 1102155 1102155 26 Hubcap 1101623...

Page 20: ...ensions and design as part of the ongoing technical development process Exploded view of the AMT 115 E unit 3 2 1 16 17 18 19 10 5 4 6 7 8 9 11 15 24 25 22 20 26 29 27 31 35 29 30 47 46 44 43 42 37 41...

Page 21: ...enoid valve 1105715 20 Coil for solenoid valve 1105714 22 Compressor cpl 1105746 24 Inspection housing part cpl 1105689 25 Completion panel 1105690 26 Base plate 1105951 27 Axle 1105692 28 Base plate...

Page 22: ...te Signature 19 Date Signature 20 Date Signature Comments Unit type Unit number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Unit cleaned outside Unit cleaned inside Fan blade cleaned Fan housin...

Page 23: ...Refrigerant quantity g 480 580 750 1270 Power supply V Hz 230 1 50 Max rated current consumption A 3 2 4 0 4 8 6 7 Max power consumption kW 0 730 0 890 1 020 1 385 at 20 C 70 RH kW 0 510 0 640 0 740...

Page 24: ...ust be advisers to our customers in air conditioning and heating technology Customer service Our units operate precisely and reliably However in the event of a malfunction REMKO customer service is qu...

Reviews: