background image

The exhaust connection may only be used with ap-
proved chimneys. The chimneys can be made of bricks 
or metal. If the chimney is made of brick, make sure 
that the exhaust pipe does not protrude into the chim-
ney, thereby having an adverse effect on the cross-
section. 

G

 

The chimney must have an adequate chimney 
draught.

 

Chimneys 

 
The unit must be attached to chimneys. 

Chimneys are structural systems either in or on build-
ings  whose only function is to expel exhaust from fur-
naces above the roof.

 

If the roof is also the ceiling of the room where the unit 
has been installed, the chimney can be made of sheet 
steel. Each furnace must have its own chimney. Merg-
ing sheet steel chimneys is prohibited. 

The chimney must be placed in a tube jointing sleeve 
when passing through wall or roof penetrations so that it 
can expand freely when heated.

 

The following are important when planning and con-
structing: 

The applicable furnace system ordinance. 

The applicable regional building code. 

Installation 

 
The unit may only be installed in accordance with the 
applicable legal regulations and the ordinance on heat-
ing systems. 

The unit must be securely placed on a non-combustible 
surface outside of traffic zones.   

A safety zone of 1 m must  be maintained around the 
unit. 

The unit may not be placed too close to the wall or in a 
corner so that any cleaning and maintenance work can 
be performed in an unrestricted manner. 

We recommend installing the unit on a sufficiently large 
plate made of non-combustible material. 

The unit must be set up and operated in such a way that 
people are not exposed to exhaust or radiant heat  and 
fires are prevented from occurring. 

The unit may not be set up and operated in rooms and 
areas susceptible to fire or explosions.

 

The unit may not be operated in rooms that have above 
or below average pressure or rooms where this can oc-
cur. 

Heating units for solid fuels that remove combustion air 
from the room where the unit is installed may not be set 
up in rooms where ventilation systems or fans exhaust 
or suck in air. 

The unit may only be set up and operated in rooms if 
there is an adequate supply of air for combustion and 
the exhaust is expelled via exhaust flues. 

A natural air supply sufficient for combustion exists 
when, for example, the room content in m³ is equivalent 
to at least 10 times the rated heat output in kW of all 
heating units in operation in the room and natural air 
ventilation is supplied through windows and doors or the 
ratio of room content to overall heat output does not fall 
below 4 m³ per kW. 

If necessary, a separate combustion air supply must be 
installed from outside. 

Good natural ventilation exists when, for example, 

the room content in m³ equals 30 times the rated 
heat output of all units in operation in the room and 
natural ventilation is supplied through doors and 
windows or  

there are non-closable openings for air output and 
intake close to the ceiling and floor whose size in m² 
equals at least 0.003 times the rated heat output in 
kW of all heating units in operation in the room. 

Expulsion of combustion gases 

The unit is designed in such a way that it can only func-
tion correctly if gases are properly expelled. The ex-
haust connection must be installed correctly and comply 
with the relevant standards. 

If a chimney draught stabiliser is not in use, the effective 
height of the chimney must be at least 4 m. By using a 
chimney draught stabiliser (accessory, ref. no. 
1034250), the chimney can usually be constructed using 
the most ideal design. The chimney draught stabiliser 
generates the necessary  upwards propulsion (chimney 
draught ). 

The chimney’s diameter may not be smaller than  150 
mm Ø. 

The unit connection must be tightly sealed and secured 
against inadvertent loosening.     

Rivets or bolts.

 

G

 

Exhaust lines which bend in several places must 
be extended accordingly.

 

G

 

The construction of chimneys always requires a per-
mit.

 

Summary of Contents for Allmat

Page 1: ...REMKO powerful like a bear REMKO Allmat Automatic Slow Combustion Heater Edition GB M04 Operation Technology Spare Parts...

Page 2: ......

Page 3: ...ntee 12 Heating Adjacent Rooms 13 Arrangement of Refractory Lining 14 Stationery slow combustion heater REMKO Allmat Make sure to read these instructions carefully before starting using the unit Our g...

Page 4: ...flames that blow back The ashpan must be emptied regularly It may only be filled up to the upper edge The fire grate must be kept free of combustion resi due with pokers The flue gas flap may never b...

Page 5: ...erials when burned release ag gressive and toxic steam that damages the environ ment and destroys the unit and the exhaust system Burning the materials above or similar materials is not only strictly...

Page 6: ...this can oc cur Heating units for solid fuels that remove combustion air from the room where the unit is installed may not be set up in rooms where ventilation systems or fans exhaust or suck in air T...

Page 7: ...himneys made of steel or brick Technical data for the chimney draught stabiliser Electrical connection 1 230 V 50Hz Power consumption 60 W Draft range bis 0 3 mbar 3 mm WS Connection 150 mm EDV NO 103...

Page 8: ...on 5 Open the waste gas flap in the waste gas connection 6 Set the BIMATIK heat output regulator to the max position with the regulating knob 7 Clean the furnace and empty the ashpan Not necessary for...

Page 9: ...unit Never place the unit under a direct stream of water Do not use aggressive cleaning agents or those which contain solvents Use only suitable cleaners even when the unit is ex tremely dirty Regular...

Page 10: ...IMATIK temperature sensor 1 2 3 4 5 6 7 8 9 10 13 12 11 1 2 A 14 B 15 7 16 17 18 22 21 20 12 11 13 19 Side view sectional drawing 1 20 14 23 15 24 25 26 16 17 18 3 5 4 35 34 33 32 31 30 6 8 29 28 9 27...

Page 11: ...aft 1108000 21 Gasket cleaning opening 1104076 22 Cover cleaning opening 1104075 23 Plate rear 1104020 24 Refractory brick rear 1108303 25 Refractory brick side lower 1108304 26 Fire grate 1104050 27...

Page 12: ...al mm 600 1 In accordance with ordinance on small furnace systems 2 Noise measuring DIN 45635 01 KL3 Feeder chute dimensions W D H mm 360 200 590 Distance from ground to middle of exhaust connections...

Page 13: ...acent room is required G G Replace the existing cover with a cover with connections Make sure that the air follows a straight path without curves Replace the existing adjustable blow out grille with a...

Page 14: ...14 Arrangement of Refractory Lining F i g N r 3 4 E D V N r 1 1 0 8 3 0 1 Fig Nr 32 EDV Nr 1108302 Fig Nr 33 EDV Nr 1108300 Fig Nr 25 EDV Nr 1108304 Fig Nr 29 EDV Nr 1108406 Fig Nr 24 EDV Nr 1108303...

Page 15: ......

Page 16: ...REMKO GmbH Co KG Klima und W rmetechnik D 32791 Lage Im Seelenkamp 12 D 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606260...

Reviews: