Pinnacle Products International, Inc. Kerosene User’s Manual
Page 11
Maintenance (Continued)
PUMP PRESSURE ADJUSTMENT:
While heater is operating, turn relief valve clockwise to increase,
counterclockwise to decrease (see
Figure 20
). Use flat blade
screwdriver to turn valve. Correct pump pressure is as follows:
For best measurement of pressure, test with full tank of
fuel.
Optimum pressure occurs when the nose cone is
cherry red and there are no extending flames from the
heater.
Figure 20.
Pump Pressure Adjustment
Adjusting
Screw
Model #
Pump Pressure
HH-45-KFA
3.0 PSI
HH-70T-KFA
4.0 PSI
HH-125T-KFA
5.0 PSI
HH-175T-KFA
7.5 PSI
HH-215T-KFA
9.0 PSI
Tolerance ± 10%
NEVER LEAVE HEATER
UNATTENDED WHILE BURN-
ING OR WHILE CONNECTED
TO A POWER SOURCE
Kerosene
Forced Air Heaters