Remeha Gas 360 S

20/07/05 - 300005180-001-A

Description

1 Introduction

Gas 360 S boilers are made of cast iron:
- with atmospheric gas burners
- with electronic ignition via the ignition burner for hot water central

heating

- with a useful output of between 54 and 117 kW

They are designed to be connected to a chimney.

The figure given after Gas 360 S indicates the number of sections
which make up the boiler.
Gas 360 S boilers are delivered with a K control panel. They can be
fitted with an optional RC4 and RC5 control unit (master-slave control
unit options).

2 Certifications

2.1

Introduction

It is CE approved under the following number : 0085AU0115
The boilers are in compliance with the EC directives:
- Royal Decree dated 8th January 2004
- 90/396/EEC Gas Appliance Directive:

Reference Standard :  EN 297 ; EN 656

- 73/23/EEC Low Voltage Directive:

Reference Standard : EN 60.335.1

- 89/336/EEC Electromagnetic Compatibility Directive

Reference Standard : EN 50.081.1 ; EN 50.082.1 ; EN 55.014

- 92/42/EEC Efficiency Directive ** 

1

,

Gas fired condensing boiler

- Type B11

BS

 (8 sections): This model is factory-fitted with a flue gas

anti-overflow thermostat.

- Type B11 (10 to 14 sections): These models can be fitted with the

optional flue gas anti-overflow thermostat.

2.2

User country

The boilers leave the factory operating with H natural gas.

User country

ES

HU

GB

Category

II

2H3P

II

2H3P

II

2H3P

Gas type

G20

G31

G20

G31

G20

G31

Distribution pressure (mbar)

20

37

25

50

20

37

Summary of Contents for GAS 360 S

Page 1: ...Supplied By www heating spares co Tel 0161 620 6677 Remeha Gas 360 S Gas fired boilers Technical instructions English 20 07 05...

Page 2: ...n 10 1 Furnace operation equipped with safety box S4565 BF 1161 10 Adapting to another gas 14 1 Changing the burner nozzles 14 2 Changing the ignition burner injector 14 3 Setting the nozzle pressure...

Page 3: ...3 3 of the directive 97 23 EC it is certified by compliance with the directives 90 396 EC 92 42 EC 73 23 EC and 89 336 EC 1 Regulations It is in any case imperative to conform to the local regulations...

Page 4: ...is CE approved under the following number 0085AU0115 The boilers are in compliance with the EC directives Royal Decree dated 8th January 2004 90 396 EEC Gas Appliance Directive Reference Standard EN 2...

Page 5: ...ete ignition burner a Ignition electrode This ensures ignition burner ignition using a high voltage spark b Ionisation probe It detects flame presence on the ignition burner by flame ionisation 6 Safe...

Page 6: ...d the heating pump don t operate If the boiler is fitted with a control unit both buttons must be left on the Winter position 3 Main ON OFF switch 4 Location for hour run meter for the first and secon...

Page 7: ...45 54 54 2nd stage kW 63 81 99 117 Power input 1st stage kW 39 4 49 1 58 8 58 8 2nd stage kW 68 9 88 4 107 8 127 2 Number of sections Part 8 10 12 14 Mass flue gas flow rate 1 2 1st stage Kg h 140 16...

Page 8: ...20 6677 8 Remeha Gas 360 S 20 07 05 300005180 001 A 5 Identification plate The rating plate affixed to the front panel during assembly provides the exact identification of the boiler and indicates its...

Page 9: ...A 6 Main dimensions Connection for safety valves Rp 1 Heating outlet R 1 1 2 Heating return R 1 1 2 Draining Rp 3 4 Gas inlet R 1 Boiler Gas 360 S 8 10 12 14 A mm 946 1113 1280 1447 B mm 952 1007 1007...

Page 10: ...e valve VP2 opens Behaviour in abnormal conditions If the flame is not detected before the end of the safety time ts the safety control box goes into safety lockout and the safety lockout warning ligh...

Page 11: ...sformer TCH1 Boiler thermostat 1 Speed TCH2 Boiler thermostat 2 Speed VA Safety lockout warning light VBa Ignition burner valve VP1 Main burner valve 1 Speed VP2 Main burner valve 2 Speed t3n Flame st...

Page 12: ...ntrol valve 2 Safety solenoid valve 3 Gas inlet 4 Safety valve quality level B 5 Gas filter 6 Valve 7 Pressure adjustment screw 8 Pressure socket 9 Membrane 10 Main valve quality level D 11 Outlet to...

Page 13: ...socket 3 Output pressure socket 4 Safety solenoid valve 5 Lower regulation chamber 6 Controlled regulation flap 7 Distribution channel 8 Solenoid control valve 9 Threshold ignition system 10 Lower mem...

Page 14: ...m spanner and fit the new nozzles with their new seals First tighten the nozzles by hand and carefully lock them using a spanner Carry out a leak tightness check 2 Changing the ignition burner injecto...

Page 15: ...essure outlet on the manifold Turn the boiler on Set the boiler thermostats to maximum Unscrew the protection cap on each valve Set the pressure on the left and right valves as shown in the table in t...

Page 16: ...rewdriver In the factory it is set to maximum To modify this setting it necessary first to remove the protection using a screwdriver 1 4 turn The progressivity of the left valve 2nd stage is always se...

Page 17: ...677 17 Remeha Gas 360 S 20 07 05 300005180 001 A 4 1 Operation of the progressivity screw setting A Downstream pressure mbar B Time s 5 Attaching the label Affix the label which indicates for which ty...

Page 18: ...bar Boiler type Gas 360 S 8 10 12 14 Nozzle pressure Natural gas H mbar 14 14 14 14 Propane mbar 36 36 36 36 Start up pressure Natural gas H mbar 11 11 11 11 Propane mbar 10 10 10 10 Nozzle Number of...

Page 19: ...e socket located on the manifold Check that the nozzle pressure and the start up pressure match the pressures given in the relevant chapter Pressure settings and calibrated nozzle markings If necessar...

Page 20: ...dy must be checked once a year If it is necessary to sweep the boiler remove the burner drawer to prevent deposits and soot blocking the orifices in the gas trains With the burner out Take the column...

Page 21: ...lectrode gap 9 and the position of the flame diffuser 17 in terms of the sizes indicated on the drawing required in the event of heater malfunction After reassembly check for leak tightness 1 3 Painte...

Page 22: ...into standby burner cut and the alarm indicator flashes Anti blowback thermostat cut Check for adequate draw on the chimney connection Press the reset button on the safety control box Check that the d...

Page 23: ...Heater too hot or too cold for requirements 3 position switch on position Check the position of the 3 position switch Wrong setting for the heater thermostat Set the heater thermostat if the heater ha...

Page 24: ...heating spares co Tel 0161 620 6677 Spare parts Gas 360 S The code number on the list next to the required piece must be stated when ordering replacement parts 20 07 05 300005180 002 A Boiler body Dr...

Page 25: ...Supplied By www heating spares co Tel 0161 620 6677 25 Remeha Gas 360 S 20 07 05 300005180 001 A Gas line 8 10 12 sections...

Page 26: ...Supplied By www heating spares co Tel 0161 620 6677 26 Remeha Gas 360 S 20 07 05 300005180 001 A Gas line 14 sections...

Page 27: ...Supplied By www heating spares co Tel 0161 620 6677 27 20 07 05 300005180 001 A Remeha Gas 360 S Control panel K Control panel K Components...

Page 28: ...Supplied By www heating spares co Tel 0161 620 6677 28 Remeha Gas 360 S 20 07 05 300005180 001 A Metal casing for control panel K...

Page 29: ...Supplied By www heating spares co Tel 0161 620 6677 29 20 07 05 300005180 001 A Remeha Gas 360 S Boiler body insulation...

Page 30: ...Supplied By www heating spares co Tel 0161 620 6677 30 Remeha Gas 360 S 20 07 05 300005180 001 A Cladding...

Page 31: ...pipe 12 sections 17 9754 9672 Return pipe 14 sections 18 9755 0189 Flange gasket 19 8377 4091 Insulation outlet pipe 20 9696 0228 Brush 22 x 11 L500 21 8800 8966 Box of mastic 1 kg 22 9430 5027 Putty...

Page 32: ...8502 8108 Flame non return plate 8 sections 74 8377 8188 Flame non return plate 10 sections 74 8377 8190 Flame non return plate 12 sections 74 8377 8192 Flame non return plate 14 sections 75 8800 8961...

Page 33: ...177 200003526 Complete upper front panel 8 sections 177 200003527 Complete upper front panel 10 sections 177 200003528 Complete upper front panel 12 sections 177 200003529 Complete upper front panel 1...

Page 34: ...Supplied By www heating spares co Tel 0161 620 6677 Remeha Gas 360 S 20 07 05 300005180 001 A...

Page 35: ...Supplied By www heating spares co Tel 0161 620 6677 Remeha Gas 360 S 20 07 05 300005180 001 A...

Page 36: ...ra 55 59 08005 BARCELONA Tel 34 3 3000204 Fax 34 3 3009558 E Cuatrocesa S A c Sor Angela de La Cruz 10 1 Oficina C 28020 MADRID Tel 34 91 658 18 88 Fax 34 91 658 30 77 E D A C S A Tom s A Edison 29 Po...

Reviews: