Code
Display text
Description
Range
Gas 120
ACE - 65
Gas 120
ACE - 90
Gas 120
ACE - 115
AP108
OutsideSensorEn
abled
Enable the function Outside
Sensor
0 = Auto
1 = Wired sensor
2 = Wireless sensor
3 = Internet measured
4 = None
0
0
0
CP000
MaxZoneTFlowS
etpoint
Maximum Flow Temperature
setpoint zone
0 °C - 90 °C
80
80
80
GP017
Max power
Maximum power percentage in
kilo Watt
0 kW - 80 kW
103,6
124,5
140,9
GP050
Power Min
Minimum power in kilo Watt for
RT2012 calculation
0 kW - 80 kW
6,7
10,8
11,4
PP015
CH Pump postrun
time
Central heating pump post run
time
0 Min - 99 Min
1
1
1
Tab.34 Navigation for ADVANCED INSTALLER level
Level
Menu cascade
Advanced installer
> Installation Setup > CU-GH08 > Submenu
> Parameters, counters, signals > Parameters > Adv.
Parameters
(1) See the column "Submenu" in the following table for the correct navigation. The parameters are grouped in specific functionalities.
Tab.35 Factory settings at ADVANCED INSTALLER level
Code
Display text
Description
Range
Gas 120
ACE - 65
Gas 120
ACE - 90
Gas 120
ACE - 115
AP002
Manual Heat
Demand
Enable manual heat demand
function
0 = Off
1 = With setpoint
2 = TOutdoor Control
0
0
0
AP026
Setpoint manual
HD
Flow temperature setpoint for
manual heat demand
10 °C - 90 °C
40
40
40
AP056
Outdoor sensor
Enable outdoor sensor
0 = No outside sensor
1 = AF60
2 = QAC34
1
1
1
AP077
Max. display level Maximum Level of parameters
and signals to display on MK
1 = End user
2 = Installer
3 = Installer advanced
4 = Lab
5 = Controls
Development
3
3
3
AP102
Boiler Pump
function
Configuration of the boiler
pump as zone pump or system
pump (feed lowloss header)
0 = No
1 = Yes
0
0
0
AP111
Can line length
Can line length
0 = < 3m
1 = < 80m
2 = < 500m
0
0
0
CP130
T.OutdoorToZone Assigning the outdoor sensor
to zone …
0 - 4
0
0
0
GP007
Fan RPM Max
CH
Maximum fan speed during
Central Heating mode
1400 Rpm - 7000 Rpm
5600
6300
6800
GP008
Fan RPM Min
Minimum fan speed during
Central H Domestic
Hot Water mode
1400 Rpm - 4000 Rpm
1600
1600
1750
GP009
Fan RPM Start
Fan speed at appliance start
1000 Rpm - 4000 Rpm
2500
2500
2500
GP010
GPS Check
Gas Pressure Switch check
on/off
0 = No
1 = Yes
0
0
0
GP021
Temp diff
Modulating
Modulate back when delta
temperature is large then this
treshold
10 °C - 40 °C
25
25
20
9 Settings
7717201 - v03 - 25062019
MID _HMI T-control - Gas 120 ACE