24
90914
YES
NO
2.D FROZEN EVAPORATOR
IS
AMBIENT ABOVE
60
°
F?
IS
VOLTAGE WITHIN
±
10%?
CHECK VOLTAGE ITEMS IN 1.
DISCONNECT PROBE WIRE FROM
CONDUCTIVITY CONTROL.
DOES
TIMER
START?
HOT
GAS OPERATION
O.K.?
WATER
DUMP
O.K.?
DOES
ICE HARVEST
NORMALLY?
YES
NO
NO
YES
YES
YES
YES
NO
NO
NO
1. SHUTOFF ICE MAKER AND THAW EVAPORATOR.
2. START ICE MAKER.
1. ARRANGE TO MAINTAIN MINIMUM
60
°
F AMBIENT.
2. CONDUCT FACTORY REGARDING
SPECIAL APPLICATION.
1. CHECK TIMER MOTOR.
2. CHECK CONDUCTIVITY CONTROL.
1. CHECK ADJUSTMENT OF TIMER
CAM #2. (HOT GAS)
2. CHECK TIMER SWITCH #2.
3. CHECK HOT GAS SOLENOID.
1. CHECK ADJUSTMENT OF TIMER
CAM #4. (WATER DUMP)
2. CHECK TIMER SWITCH #4.
3. CHECK DUMP SOLENOID.