Summary of Contents for AeroMaster FP 2.7

Page 1: ...INSTALLATION AND SERVICE INSTRUCTIONS Air handling units 07 2013 ...

Page 2: ...tions 5 Connection of exchangers 6 Connection of exchangers 6 Water exchangers 6 Connection dimensions of water exchangers 6 Direct evaporators 6 Connection dimensions of direct evaporators 6 Other connections 7 Condensate outlet 7 Connection of air handling duct 7 Connection of electric devices 7 Connection of motors 7 Schemes of electric wiring 8 Preparation for start up start of operation 10 Ch...

Page 3: ...andling unit Unit construction is sectional modular Casing is com posed of panels and connecting bars between them Panels are attached to connecting bars and by thread ed joints between each other For cases of regular maintenance or inside checks change of filtration inserts cleaning etc the sections are equipped with service panels which have the same construction as stationary panels but they ar...

Page 4: ...foil and protected by polystyrene protections They must be stored at places where maximal relative air humidity doesn t exceed 85 and without humidity condensation surrounding temperature ranges from 20 C up to 40 C no dust gasses and corrosive fumes or other che mical matters causing corrosion of constructional parts and device equipment may get into the device Placing FP units are standardly ins...

Page 5: ...onent of the air hand ling unit in the documentation is marked with a position number This bond enables fast and exact orientation when put ting unit together and easy check of correctness and entireness of installation Connection of unit sections Connection of separate sections of a unit is done by bolt fastening Bolts are part of delivery Before faste ning of separate section together there must...

Page 6: ...tion left type of cooler air flow direction right type of cooler Picture 7 energy supply Table 1 connection dimensions of water exchangers Direct evaporators Picture 9 connection of evaporators air flow direction left type of eva porator air flow direction right type of eva porator Connection dimensions of direct evaporators Table 2 external connection dimensions of direct evaporators in mm Single...

Page 7: ...e draining kits are available as extra ordered optional accessories A se parate condensate draining kit must be used for each section The siphon height depends on the total pressu re of the fan and its proper height is essential for good functioning The type of condensate draining kit must be designed in the course of the air handling unit calcula tion Before the first start up and after longer sh...

Page 8: ...ase frequency inverter power supply 1ph 230 50Hz 29 50 frequency inverter terminals for the motor s thermo contact TK connection 61 68 69 Modbus bus terminals Frequency converter data settings have been set by the manufacturer Modbus Modbus Frequency inverter power supply Frequency inverter power supply U1 V1 W1 PE1 power supply clamps of the triple phase single speed motor 3ph 400V 50Hz TK TK cla...

Page 9: ...e unit with two motors Connection of motors Motors are equipped with protecting thermocontacts which protect the motor from overheating Thermocon tacts must be connected according to specified conne ction Single speed motors are designed for 230V D 400V Y power supply voltages and connections for electro mo tors with output up to 3kW Motors are in production wired to wiring box on casing of fan se...

Page 10: ...ation check the tightening of the Taper Lock collets check the tightening of the screw joints of the fan assembly Filter section state of filters attachment of filters setting of pressure difference sensors Water heater section state of heat transmission surface state of inlet and outlet duct connection state and connection of mixing set state wiring and installation of elements of anti freeze pro...

Page 11: ...nctions principles of health protection and rules of safety operation and attendance of air handling device requirements for eligibility and training of attendant personnel list of workers who are authorized to operate the device detailed instructions for attendance attendance ac tions during emergency and failure states list of operation specialities in different climatic areas summer and winter ...

Page 12: ...imit the unit belongs to a waste group according to the Waste Act No 185 2001 Sb This product belongs to the Q14 waste group Waste Classification in accordance with Directive No 381 2001 Sb Materials used to pack the product 15 01 01 cardboard box paper and cardboard packa ging products 15 01 02 polyester packaging pads plastic packaging products 15 01 03 pallet wooden packaging products Disabled ...

Page 13: ...13 Air handling units Spare parts service ...

Page 14: ...Air handling units 14 Notes ...

Page 15: ...or copying of Installation and service instructions either a part or a whole must be obtained in written form from company REMAK a s Zuberská 2601 Rožnov p R This Installation and service instructions is exclusive property of company REMAK a s Right for changes reserved Date of issue 10 7 2013 ...