4Ć2
Processor in the rack is a M/N 57C430A or M/N 57C431, the
operating system(s) will be loaded at 9600 baud. At 9600 baud, it will
require approximately two minutes to load each operating system to
Processors in the rack. Although they are similar, the operating
systems for the 6010/6011 and 7010 Processor are different. If there
are6010/6011 and 7010 Processors mixed in thesamerack, loading
the operating systems will take approximately twice as long as it
would if therewereonly onetypeof Processor in therack.
Follow the directions below to load the operating system(s) for all
Processor modules in the local rack at one time. You can then load
the operating system(s) to all racks on all networks in the system.
Note: If you load an operating system into a Processor(s) that
already contains one, the new operating system will write over
the existing operating system, and any tasks in the Processor(s)
will be deleted.
1. If you havenot already doneso, turn on thepersonal computer
and run theAutoMax Executiveby typing
AUTOMAX2
or
AUTOMAX3
2. Turn on power to therack. You will notethat theleftmost
Processor modulein therack displays theletters L" and O"
(reading top to bottom). This code prompts you to Load the
Operating system. Because Processor modules have onĆboard
battery backup, you will need to reĆload the operating system
only when enhancements become available, when you change
thepassword for therack using thePWOS.EXE utility or when a
Processor module in the rack is replaced.
3. If you have not already done so, connect the personal computer
to theleftmost processor in therack, following thedirections
in 4.4.
4. Enter a <CR> at the initial screen. If you are using AutoMax
Version 2, select F10 for Load Operating System". If you are
using AutoMax Version 3, select Load Operating System" from
theCommands menu. Notethat you will seethemessageLocal
OS invalid Ć Direct connection only" before you load the
operating system for the first time. The AutoMax Executive
software will load the operating system onto all Processor
modules in thelocal rack at thenormal baud rate. TheAutoMax
Executive will display on the screen the portion (%) of the
operating system that has been loaded.
5. When installation begins, the code L" O" will disappear from the
two sevenĆsegment LEDs on the leftmost Processor module. The
LEDs should be blank. If any error codes appear on the LEDs of
the leftmost Processor, the loading was not successful. Repeat
step 4 above.
6. You can now load the operating system to other racks in the
system connected to the local rack (the rack to which your
personal computer is connected) through 57C404A Network
Communication modules. For any network containing 57C404
Network Communication modules, you must connect directly to
each rack on the network to load the operating system (see steps
1Ć5 above).
Summary of Contents for AutoMax 57C430A
Page 1: ...Instruction Manual JĆ3650Ć6 AutoMax Processor Module M N 57C430A M N 57C431 M N 57C435 ...
Page 6: ...afadfdfdasfdsfdsdsdfdsfdsfdsfsdfdsa fdfdsfdsfdfdsfdsfsadfda sfdfaddfdd ...
Page 10: ...afadfdfdasfdsfdsdsdfdsfdsfdsfsdfdsa fdfdsfdsfdfdsfdsfsadfda sfdfaddfdd ...
Page 14: ...afadfdfdasfdsfdsdsdfdsfdsfdsfsdfdsa fdfdsfdsfdfdsfdsfsadfda sfdfaddfdd ...
Page 20: ...afadfdfdasfdsfdsdsdfdsfdsfdsfsdfdsa fdfdsfdsfdfdsfdsfsadfda sfdfaddfdd ...
Page 26: ...afadfdfdasfdsfdsdsdfdsfdsfdsfsdfdsa fdfdsfdsfdfdsfdsfsadfda sfdfaddfdd ...
Page 38: ...afadfdfdasfdsfdsdsdfdsfdsfdsfsdfdsa fdfdsfdsfdfdsfdsfsadfda sfdfaddfdd ...
Page 42: ...afadfdfdasfdsfdsdsdfdsfdsfdsfsdfdsa fdfdsfdsfdfdsfdsfsadfda sfdfaddfdd ...
Page 54: ...afadfdfdasfdsfdsdsdfdsfdsfdsfsdfdsa fdfdsfdsfdfdsfdsfsadfda sfdfaddfdd ...
Page 57: ...afadfdfdasfdsfdsdsdfdsfdsfdsfsdfdsa fdfdsfdsfdfdsfdsfsadfda sfdfaddfdd ...
Page 58: ...afadfdfdasfdsfdsdsdfdsfdsfdsfsdfdsa fdfdsfdsfdfdsfdsfsadfda sfdfaddfdd ...
Page 59: ...afadfdfdasfdsfdsdsdfdsfdsfdsfsdfdsa fdfdsfdsfdfdsfdsfsadfda sfdfaddfdd ...