Reliable Automatic Sprinkler Co., Inc.
Manufacturer & Global Distributor of Fire Protection Products
www.reliablesprinkler.com
RASCOFLEX Technical & Installation Instruction
R0029B
Rfxxxb series (braided hose):
Town Mains
Pumps
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Pre-calculated
Assembly Length
(mm)
700
1000
1200
1500
1800
Fully Hydraulically
Calculated
Yes
Yes
Yes
Yes
Yes
•
All pipe work supplied with RASCOFLEX as connection assemblies in pre-calculated systems shall be
sized as distribution mains.
•
In suspended ceilings RASCOFLEX flexible sprinkler connection must be installed in accordance with
this data sheet.
•
In suspended ceilings, RASCOFLEX flexible sprinkler connection must be connected to the ceiling
support system with brackets supplied.
LPCB Equivalent Length of RASCOFLEX as follows:
Assembly Length (mm)
Number of 90
o
Bends
Equivalent Length of
DN25 Sch. 40 Pipe at
C=120 in Meters
700
1
5.0
1000
1
7.2
1200
2
7.1
1500
2
7.6
1800
3
9.4
Rfxxxb series (braided hose):
APPROVED FOR USE IN THE FOLLOWING LOCATIONS:
Page 7 of 11