background image

3.

Sprinkler

Model

Type

Temperature

Rating

Maximum

Ambient

Ceiling Temp.

Nominal

K-Factor

Orifice

Size

Thread

Size

Sprinkler Ht.

Inch (mm)

Sprinkler

Identification

Number (SIN)

°

F

°

C

°F

°

C

N252 EC

Pendent/
Recessed
Pendent

165

74

100

38

25.2

1 inch

1

²

NPT

(R1)

3.6 (91,5)

RA0852

212

100

150

66

Technical Data

Design Criteria for UL and C-UL

The Models N252 EC Pendent and Recessed

Pendent Sprinklers are cULus Listed control-mode,
extended coverage density/area sprinklers for
installation in accordance with the extended
coverage pendent spray sprinkler criteria of NFPA 13,
or other applicable NFPA standards, when used in
combination with the following guidelines:

• Protection for extra hazard and high-piled

storage occupancies using NFPA 13
density/area criteria.

• Suitable for use in wet pipe systems, and in

dry-pipe and preaction systems as specifically
allowed for pendent sprinklers in NFPA 13.

• cULus

Listed

for

“unobstructed”

or

non-combustible “obstructed” construction.
Given that the Model N252 EC sprinklers are
specifically listed for noncombustible obstructed
construction, they may be installed within trusses
or bar joists having noncombustible web
members greater than 1 inch (25.4 mm) when
applying the “Four Times Rule” as defined in
NFPA 13 under “Obstructions to Sprinkler
Discharge Pattern Development.”

• Maximum area of coverage per sprinklers is 196

ft

2

(18.2 m

2

); minimum area of coverage is 100 ft

2

(9.3 m

2

). Maximum spacing between sprinklers

is 14 ft (4.3 m); minimum spacing between
sprinklers is 8 ft (2.44 m).

• Minimum flow requirement is based on the

design density applied over the actual area of
coverage per sprinkler. Example 1, a design
density of 0.43 gpm/ft

2

(17.5 mm/min) applied

over 14 ft x 14 ft (4.3 m x 4.3 m) spacing, or 196 ft

2

(18.2 m

2

), would require a minimum sprinkler

design flow rate and pressure of 84.3 gpm (319.2
L/min) at 11.2 psi (0.77 bar). Example 2, a design
density of 0.43 gpm/ft

2

(17.5 mm/min) applied

over 14 ft x 12 ft (4.3 m x 3.7 m) spacing, or 168 ft

2

(15.6 m

2

), would require a minimum sprinkler

design flow rate and pressure of 72.2 gpm (273.3
L/min) at 8.2 psi (0.57 bar).

• Maximum working pressure - 175 psi (12.1 bar).

• Minimum end head pressure - 7 psi (0.5 bar).

• The minimum clearance between the deflector

and the top of storage is 3 ft. (0,92m). For
clearances of 3 ft. (0,92m) up to 4 ft. (1,21m), the
minimum design pressure is 22 psi (1,52 bar). For
clearances of 4 ft. (1,21m) and greater, the
minimum design pressure is established by the
minimum flow requirement (however, the
pressure can never be less than 7 psi (0,48 bar)).

• Available temperature ratings are Ordinary, 165

°

F (74

°

C) and Intermediate, 212

°

F (100

°

C).

Selection of temperature rating is based on the
expected maximum ambient temperature
exposure, or in accordance with the high-piled
storage density/area curve requirements
specified in Chapter 12 of the 2002 edition of
NFPA 13. In accordance with the listing of the
sprinkler, the density curves normally associated
with high temperature rated sprinklers [286

°

F

(141

°

C)] may be used with either the ordinary or

intermediate temperature rating of the N252 EC
sprinklers.

• The obstruction criteria in NFPA 13 for Extended

Coverage Pendent Sprinklers shall be used for
the locating and positioning Model N252 EC
sprinklers relative to obstructions.

Design Criteria for FM

The Model N252 EC Pendent Sprinklers are FM

approved to be utilized in accordance with the
following guidelines:

• Sprinklers may be used to protect any

occupancy for which there is an area/density
design criterion up to 11.2 k-factor standard
spray control mode area/density sprinklers
specified in FM Global Data Sheets. Model N252
EC sprinklers are not approved for use in control
mode specific application or suppression mode
protection.

• Suitable for use in wet pipe systems, and in

dry-pipe and preaction systems as specifically
allowed for pendent sprinklers in NFPA 13.

• Follow

obstruction

requirements

for

control-mode area/density sprinklers in FM Data
Sheet 2-8N section 4-6.5.