P/N 9999970310
Bulletin 172
May 2019
Page 7 of 7
www.reliablesprinkler.com
Installation
Glass bulb sprinklers have orange bulb protectors to minimize
bulb damage during shipping, handling, and installation. Re-
liable sprinkler installation wrenches are designed to install
sprinklers with bulb protectors in place. Remove the bulb pro-
tector at the time when the sprinkler system is placed in service
for fire protection. Removal of the bulb protector before this time
may leave the bulb vulnerable to damage. Remove bulb protec-
tors by undoing the clasp by hand. Do not use tools to remove
bulb protectors.
Models J112 and JL112 series sprinklers must be installed
with the Reliable sprinkler installation wrench identified in this
bulletin. Any other wrench may damage the sprinkler. Recom-
mended installation torque is 14 to 20 lb.ft (19 to 27 N.m). Do
not tighten sprinklers over the maximum recommended installa-
tion torque. Exceeding the maximum recommended installation
torque may cause leakage or impairment of the sprinkler.
Recessed pendent sprinklers are to be installed as shown in
Fig. 6 or Fig 7., as applicable to the specific model being in-
stalled. Models J112 and JL112 series recessed pendent sprin-
klers may only be installed with the Reliable Model F1, Model
F2, or Model FP recessed escutcheon. The use of any other
recessed escutcheon will void all approvals and negate all war-
ranties. The Reliable Model FP escutcheon may not be used
in ceilings having positive pressure with respect to the space
below. Ensure that the openings in the Model FP escutcheon/
can assembly are unobstructed following installation.
Maintenance
Models J112 and JL112 series sprinklers should be inspect-
ed and the sprinkler system maintained in accordance with
NFPA 25. Do not clean sprinklers with soap and water, ammo-
nia or any other cleaning fluids. Remove dust by gentle vacu-
uming. Replace any sprinkler which has been painted (other
than factory applied) or damaged in any way. A stock of spare
sprinklers should be maintained to allow quick replacement of
damaged or operated sprinklers. Prior to installation, sprinklers
should be maintained in the original cartons and packaging un-
til used to minimize the potential for damage to sprinklers that
would cause improper operation or non-operation.
J1 Wrench
RJ Wrench
Table G
Sprinkler Finishes
Special Application Sprinkler Finishes
Sprinkler
F1, F2, & FP
(3)
Escutcheons
Sprinkler
F1, F2, & FP
(3)
Escutcheons
Bronze
Chrome Plated
White Polyester
(2)
Brass
Chrome Plated
White Polyester
Bright Brass
Dull Chrome
Black Polyester
(2)
Custom Color Polyester
Electroless Nickel PTFE
(2) (4)
Bright Brass
Dull Chrome
Black Polyester
Custom Color Polyester
Type 316 Stainless Steel
Sprinkler & Escutcheon Finishes
(1)
Notes
:
(1)
Paint or any other coating applied over the factory finish will void all approvals and warranties.
(2)
cULus Listed Corrosion Resistant when ordered with Model J112 Pendent (RA7216) or Model J112 Upright (RA7326).
(3)
The Model FP escutcheon assembly consists of an unfinished galvanized cup with a finished escutcheon ring.
(4)
Available with Model J112 Pendent (RA7216) and Model J112 Upright (RA7326) only.
Listings and Approvals
Listed by Underwriters Laboratories, Inc. and certified by
Underwriters Laboratories of Canada (cULus)
UL Listing Category
Sprinklers, Automatic and Open Extended Coverage Sprinklers
UL Guide Number – VNIV.
Ordering Information
Specify:
1. Sprinkler Model: [J112 Pendent] [JL112 Pendent]
[J112 Upright] [JL112 Upright]
2. Temperature Rating: J112: [155°F (68°C)] [200°F (93°C)]
[286°F (141°C)]
JL112: [165°F (74°C)] [212°F (100°C)]
3. Finish: (See Table G)
4. Escutcheon (Pendent Only; for 3/4” threads)
Model F1 (Ordinary Hazard Only)
Model F2
Model FP