Installation

Glass bulb sprinklers have orange bulb protectors to minimize 
bulb damage during shipping, handling, and installation. Re-
liable sprinkler installation wrenches are designed to install 
sprinklers with bulb protectors in place. Remove the bulb pro-
tector at the time when the sprinkler system is placed in service 
for fire protection. Removal of the bulb protector before this time 
may leave the bulb vulnerable to damage. Remove bulb protec-
tors by undoing the clasp by hand. Do not use tools to remove 
bulb protectors. 

Models J112 and JL112 series sprinklers must be installed 
with the Reliable sprinkler installation wrench identified in this 
bulletin. Any other wrench may damage the sprinkler. Recom-
mended installation torque is 14 to 20 lb.ft (19 to 27 N.m). Do 
not tighten sprinklers over the maximum recommended installa-
tion torque. Exceeding the maximum recommended installation 
torque may cause leakage or impairment of the sprinkler. 

Recessed pendent sprinklers are to be installed as shown in 
Fig. 6 or Fig 7., as applicable to the specific model being in-
stalled. Models J112 and JL112 series recessed pendent sprin-
klers may only be installed with the Reliable Model F1, Model 
F2, or Model FP recessed escutcheon. The use of any other 
recessed escutcheon will void all approvals and negate all war-
ranties. The Reliable Model FP escutcheon may not be used 
in ceilings having positive pressure with respect to the space 
below. Ensure that the openings in the Model FP escutcheon/
can assembly are unobstructed following installation. 

Maintenance

Models J112 and JL112 series sprinklers should be inspect-
ed and the sprinkler system maintained in accordance with 
NFPA 25. Do not clean sprinklers with soap and water, ammo-
nia or any other cleaning fluids. Remove dust by gentle vacu-
uming. Replace any sprinkler which has been painted (other 
than factory applied) or damaged in any way. A stock of spare 
sprinklers should be maintained to allow quick replacement of 
damaged or operated sprinklers. Prior to installation, sprinklers 
should be maintained in the original cartons and packaging un-
til used to minimize the potential for damage to sprinklers that 
would cause improper operation or non-operation.

J1 Wrench

RJ Wrench

Table G

Sprinkler Finishes

Special Application Sprinkler Finishes

Sprinkler

F1, F2, & FP

(3)

 Escutcheons

Sprinkler

F1, F2, & FP

(3)

 Escutcheons

Bronze

Chrome Plated

White Polyester 

(2)

Brass

Chrome Plated

White Polyester

Bright Brass
Dull Chrome

Black Polyester 

(2)

Custom Color Polyester

Electroless Nickel PTFE 

(2) (4)

Bright Brass
Dull Chrome

Black Polyester

Custom Color Polyester

Type 316 Stainless Steel

Sprinkler & Escutcheon Finishes 

(1)

Notes

(1)

 Paint or any other coating applied over the factory finish will void all approvals and warranties. 

 

 

                     (2)

 cULus Listed Corrosion Resistant  when ordered with Model J112 Pendent (RA7216) or Model J112 Upright (RA7326).

                     (3)

 The Model FP escutcheon assembly consists of an unfinished galvanized cup with a finished escutcheon ring.

           

  (4)

 Available with Model J112 Pendent (RA7216) and Model J112 Upright (RA7326) only.

Listings and Approvals

Listed by Underwriters Laboratories, Inc. and certified by
Underwriters Laboratories of Canada (cULus)

UL Listing Category

Sprinklers, Automatic and Open Extended Coverage Sprinklers
UL Guide Number – VNIV.

Ordering Information

Specify:

1.  Sprinkler Model: [J112 Pendent] [JL112 Pendent] 
                                [J112 Upright] [JL112 Upright]
2.    Temperature  Rating:  J112:  [155°F  (68°C)]  [200°F  (93°C)]          
                                                [286°F (141°C)]          
                                      JL112: [165°F (74°C)] [212°F (100°C)]
3.  Finish: (See Table G)
4.  Escutcheon (Pendent Only; for 3/4” threads)
                  Model F1 (Ordinary Hazard Only)
                  Model F2
                  Model FP

Summary of Contents for J112 Pendent

Page 1: ...112 Upright sprinklers use a fusible link operating element Model J112 Pendent and Model JL112 Pendent sprinklers are cULus Listed for use with the Model F2 and Model FP recessed escutch eons which pr...

Page 2: ...adjustment FP 1 2 13mm adjustment Listings and Approvals cULus Listed cULus Listed as Corrosion Resistant with White Polyester Black Polyester and ENT finish only Max Spacing ft x ft m x m Light Hazar...

Page 3: ...2 13mm adjustment FP 1 2 13mm adjustment Listings and Approvals cULus Listed Chrome and white polyester finish is supplied with white link regardless of temperature rating Max Spacing ft x ft m x m Li...

Page 4: ...sted cULus Listed as Corrosion Resistant with White Polyester Black Polyester and ENT finish only Max Spacing ft x ft m x m Light Hazard Ordinary Hazard Group 1 Ordinary Hazard Group 2 Flow gpm l m Pr...

Page 5: ...ULus Listed Chrome and white polyester finish is supplied with white link regardless of temperature rating Max Spacing ft x ft m x m Light Hazard Ordinary Hazard Group 1 Ordinary Hazard Group 2 Flow g...

Page 6: ...em Spacing 7 6 2 3m Min Tee Stem Spacing 3 0 0 9m Max Tee Length 32 0 9 8m or baffles not less than the depth of the tees must be installed so that the longitudinal space between baffles does not exce...

Page 7: ...in accordance with NFPA 25 Do not clean sprinklers with soap and water ammo nia or any other cleaning fluids Remove dust by gentle vacu uming Replace any sprinkler which has been painted other than fa...