background image

www.reliablesprinkler.com

Product Description

Model J112 and JL112 series sprinklers are cULus Listed 
extended coverage spray sprinklers intended for installation 
in accordance with NFPA 13. The sprinklers also have cU-
Lus Listed Specific Application Criteria for installation under 
concrete tee construction in accordance with the require-
ments documented in this bulletin. Coverage areas up to 
400 ft

2

 (37 m

2

) per sprinkler with a maximum spacing of up 

to 20 ft by 20 ft (6.1 m by 6.1 m) are permitted for both Light 
Hazard and Ordinary Hazard occupancies. Listed flows and 
pressures for each hazard classification and sprinkler spac-
ing are provided in this bulletin. Model J112 and JL112 se-
ries sprinkler are cULus Listed as quick-response sprinklers 
for Light Hazard occupancies. When used in the Ordinary 
Hazard occupancies, Model J112 and JL112 series sprin-
klers are cULus Listed as quick-response for spacings up 
to 14 ft by 14 ft (4.3 m by 4.3 m) and standard-response for 
other listed spacings up to 20 ft by 20 ft (6.1 m by 6.1 m). 

Model J112 Pendent and J112 Upright sprinklers use a 
glass bulb operating element and are cULus Listed as 
Corrosion Resistant Sprinklers when ordered with White 
Polyester, Black Polyester, or Electroless Nickel PTFE (ENT) 
finish. Model JL112 Pendent and JL112 Upright sprinklers 
use a fusible link operating element.  Model J112 Pendent 
and Model JL112 Pendent sprinklers are cULus Listed for 
use with the Model F2 and Model FP recessed escutch-
eons, which provide up to ½ inch (13 mm) of adjustment. In 
addition, for Ordinary Hazard occupancies, the Model J112 
Pendent and Model JL112 Pendent sprinklers are cULus 
Listed for use with the Model F1 recessed escutcheon that 
provides up to ¾ inch (19 mm) of adjustment.

Application

Model J112 and JL112 series sprinklers are intended for 
installation in Light Hazard and Ordinary Hazard occupan-
cies in accordance with NFPA 13. The sprinklers must be 
installed in accordance with the requirements of NFPA 13 
for extended coverage spray sprinklers and the require-
ments identified in this bulletin. In addition to the installation 
requirements of NFPA 13, cULus Listed Specific Application 
Criteria for installation under concrete tee construction is 
provided in this bulletin.

cULus Listed

K11.2 (160 metric)

Model J112 and JL112 Sprinklers

Extended Coverage Sprinklers for 

Light Hazard and Ordinary Hazard

Bulletin 172 May 2019

Model J112 Upright

Model JL112 Upright

Model J112 Pendent

Model JL112 Pendent

Model J112 and JL112 Series Sprinkler Summary

Model

Orientation

Operating Element

Sprinkler Identification Number 

(SIN)

J112

Pendent

Glass Bulb

RA7216

JL112

Pendent

Fusible Link

R7216

J112

Upright

Glass Bulb

RA7326

JL112

Upright

Fusible Link

R7326

Table A

FP Recessed Escutcheon

F1/F2 Recessed Escutcheon

Summary of Contents for J112 Pendent

Page 1: ...112 Upright sprinklers use a fusible link operating element Model J112 Pendent and Model JL112 Pendent sprinklers are cULus Listed for use with the Model F2 and Model FP recessed escutch eons which pr...

Page 2: ...adjustment FP 1 2 13mm adjustment Listings and Approvals cULus Listed cULus Listed as Corrosion Resistant with White Polyester Black Polyester and ENT finish only Max Spacing ft x ft m x m Light Hazar...

Page 3: ...2 13mm adjustment FP 1 2 13mm adjustment Listings and Approvals cULus Listed Chrome and white polyester finish is supplied with white link regardless of temperature rating Max Spacing ft x ft m x m Li...

Page 4: ...sted cULus Listed as Corrosion Resistant with White Polyester Black Polyester and ENT finish only Max Spacing ft x ft m x m Light Hazard Ordinary Hazard Group 1 Ordinary Hazard Group 2 Flow gpm l m Pr...

Page 5: ...ULus Listed Chrome and white polyester finish is supplied with white link regardless of temperature rating Max Spacing ft x ft m x m Light Hazard Ordinary Hazard Group 1 Ordinary Hazard Group 2 Flow g...

Page 6: ...em Spacing 7 6 2 3m Min Tee Stem Spacing 3 0 0 9m Max Tee Length 32 0 9 8m or baffles not less than the depth of the tees must be installed so that the longitudinal space between baffles does not exce...

Page 7: ...in accordance with NFPA 25 Do not clean sprinklers with soap and water ammo nia or any other cleaning fluids Remove dust by gentle vacu uming Replace any sprinkler which has been painted other than fa...

Reviews: