3.

Maintenance

Model G6-80 Concealed Sprinklers should be inspected 

and maintained in accordance with NFPA 25.  Do not clean 
sprinklers with soap and water, ammonia or any other clean-
ing fluids.  Remove dust by using a soft brush or gentle vac-
uuming.  Remove any sprinkler cover plate assembly, which 
has been painted (other than factory applied) or damaged 
in any way.  A stock of spare sprinklers should be maintained 
to allow quick replacement of damaged or operated sprin-
klers.  Prior to installation, sprinklers should be maintained in 
their original cartons and packaging until used to minimize 
the potential for damage to sprinklers that would cause im-
proper operation or non-operation.

Model G6-80 Concealed Quick Response
Extended Coverage Light Hazard Horizontal 
Sidewall Sprinkler Speci

fi

 cation

Sprinklers shall be a [quick response – cULus Listed] ex-

tended coverage concealed horizontal sprinkler with G6-80 
deflector and adjustable cover plate for light hazard, inte-
rior, non-corrosive applications.  Sprinklers to be of bronze 
frame construction with brass cover plate and copper alloy 
retainer flange assembly. Water seal assembly shall consist 
of a Teflon* coated Belleville spring washer and machined 
brass cup containing no plastic parts. Method of attach-
ing the cover plate to the sprinkler cup shall be a push-on 
and Pull-off design allowing a ¼” cover plate adjustment.  
Sprinklers shall have a nominal K-factor of 8.0 (115.3), and 
¾” NPT thread.  Sprinkler temperature rating shall be 165°F 
(74°C) with a cover plate temperature rating of 135°F (57°C).  
Sprinklers shall be capable of a maximum coverage area of 
16 ft. x 24 ft. (4.9 m x 7.4 m) or 18 ft. x 22 ft (5.5 m x 6.7 m), 
with a minimum lateral spacing of 8 ft. (2.4 m).  Rated work-
ing pressure shall be 175 psi (12,0 bar).  A plastic protec-
tive cap shall be provided and factory installed inside the 
sprinkler cup to protect the sprinkler from damage, which 
could occur during construction before the cover plate is 
installed.  Standard cover plate finish: [Chrome] [White] 
[Custom Color– specify]. Extended Coverage Concealed 
horizontal sidewall sprinklers shall be Reliable Model G6-80. 
SIN RA4762 (Bulletin 047).

UL Listing Category

Sprinklers, Automatic and Open
Quick Response Extended coverage Sprinklers

Ordering Information

Specify:

1. Model G6-80 Sidewall Concealer

® 

2.  Cover Plate Type: Solid or Perforated
3.  Cover Plate Finish

Installation Wrench

Model G6 Sprinkler Wrench

Installation Aid

A protective plastic cap is included for use during instal-
lation. 

Cover Plate Finishes

(1)

Standard Finishes

Chrome

White Paint

Special Application Finishes

Bronze
Black Paint
Flat White Paint

(1)

 Other colors and finishes are available.  Consult factory for details.

Note:

 Paint or any other coatings applied over the factory 

finish will void all approvals and warranties.

*DuPont Registered Trademark