3.
Maintenance
Model G6-80 Concealed Sprinklers should be inspected
and maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other clean-
ing fluids. Remove dust by using a soft brush or gentle vac-
uuming. Remove any sprinkler cover plate assembly, which
has been painted (other than factory applied) or damaged
in any way. A stock of spare sprinklers should be maintained
to allow quick replacement of damaged or operated sprin-
klers. Prior to installation, sprinklers should be maintained in
their original cartons and packaging until used to minimize
the potential for damage to sprinklers that would cause im-
proper operation or non-operation.
Model G6-80 Concealed Quick Response
Extended Coverage Light Hazard Horizontal
Sidewall Sprinkler Speci
fi
cation
Sprinklers shall be a [quick response – cULus Listed] ex-
tended coverage concealed horizontal sprinkler with G6-80
deflector and adjustable cover plate for light hazard, inte-
rior, non-corrosive applications. Sprinklers to be of bronze
frame construction with brass cover plate and copper alloy
retainer flange assembly. Water seal assembly shall consist
of a Teflon* coated Belleville spring washer and machined
brass cup containing no plastic parts. Method of attach-
ing the cover plate to the sprinkler cup shall be a push-on
and Pull-off design allowing a ¼” cover plate adjustment.
Sprinklers shall have a nominal K-factor of 8.0 (115.3), and
¾” NPT thread. Sprinkler temperature rating shall be 165°F
(74°C) with a cover plate temperature rating of 135°F (57°C).
Sprinklers shall be capable of a maximum coverage area of
16 ft. x 24 ft. (4.9 m x 7.4 m) or 18 ft. x 22 ft (5.5 m x 6.7 m),
with a minimum lateral spacing of 8 ft. (2.4 m). Rated work-
ing pressure shall be 175 psi (12,0 bar). A plastic protec-
tive cap shall be provided and factory installed inside the
sprinkler cup to protect the sprinkler from damage, which
could occur during construction before the cover plate is
installed. Standard cover plate finish: [Chrome] [White]
[Custom Color– specify]. Extended Coverage Concealed
horizontal sidewall sprinklers shall be Reliable Model G6-80.
SIN RA4762 (Bulletin 047).
UL Listing Category
Sprinklers, Automatic and Open
Quick Response Extended coverage Sprinklers
Ordering Information
Specify:
1. Model G6-80 Sidewall Concealer
®
2. Cover Plate Type: Solid or Perforated
3. Cover Plate Finish
Installation Wrench
Model G6 Sprinkler Wrench
Installation Aid
A protective plastic cap is included for use during instal-
lation.
Cover Plate Finishes
(1)
Standard Finishes
Chrome
White Paint
Special Application Finishes
Bronze
Black Paint
Flat White Paint
(1)
Other colors and finishes are available. Consult factory for details.
Note:
Paint or any other coatings applied over the factory
finish will void all approvals and warranties.
*DuPont Registered Trademark