background image

The Reliable Automatic Sprinkler Co., Inc.,

 103 Fairview Park Drive, Elmsford, New York 10523

Model G6-80 
Concealed Quick Response
Extended Coverage Light Hazard
Horizontal Sidewall Sprinkler
(SIN RA4762)

Bulletin 047

Bulletin 047

The Sidewall Concealer

®

Coverage to 18 ft. x  22 ft. (5.5m x 6.7m), 
16 ft. x 24 ft. (4.9m x 7.3m). 
175 psi (12,0 bar) Rated.
Features:

1.  Flat cover plate (Solid or Perforated) for optimized 

finish mounting purposes.

2.  8.0 K Factor.
3.  Sprinkler is approved for 175 psi (12,0 bar)  

applications.

4.  Quick response, extended coverage light hazard 

Horizontal Sidewall.

5.  Push-on/pull-off, sturdy convenient flat cover plate.
6.  Sprinkler, shipped complete with factory installed  

protective cap.

7.  Sprinkler assembly and cover plate packaged 

separately.

8.  ¼” (6.3mm) adjustment.
9.  Cover plate available in chrome, standard white 

paint, special bronze, black paint or flat white 
finishes.

Approval Organizations

1. Listed by Underwriters Laboratories Inc. and 

UL certified for Canada (cULus).

Patents:

U.S. Patent No. 6,374,919, other Patents pending

Product Description

The Reliable Model G6-80 Concealed Quick Response 

Extended Coverage Horizontal Sidewall Sprinkler is an at-
tractive, concealed sprinkler assembly that utilizes a push-
on/pull-off cover plate assembly. The sprinkler assembly is 
shipped with a protective cap.  

 The flat cover plate is attached to the skirt using 135°F 

(57°C) ordinary temperature classification solder.  The sprin-
kler is easily installed into the sprinkler fitting using the Model 
G6 Sprinkler Wrench.  

When the ambient temperature rises, the solder holding 

the cover plate melts, allowing the release of this part and 
thus exposing the sprinkler inside to the rising ambient tem-
perature.

The Model G6-80 utilizes a Quick Response soldered link.  

This quick response enables the sprinkler to apply water to a 
fire sooner than standard sprinklers of the same temperature 
rating.

 This sprinkler is listed for a maximum service pressure of 

175 psi (12,0 bar).

Application and Installation

The Model G6-80 sprinkler is intended for installation in 

light hazard occupancies in accordance with NFPA 13.  This 
sprinkler is especially well-suited for use in student dormito-
ries, hotels, hospitals and care facilities.

Model G6-80 Concealed Horizontal Sidewall sprinklers 

utilize a sprinkler assembly with spring loaded deployable 
deflector feature.  The assembly is  completed by the instal-
lation of the attractive, 135°F (57°C) push-on/pull-off cover 
plate assembly, which provides ¼” (6.3mm) of adjustment.

Apply a Teflon* - based thread sealant to the sprinkler 

threads.  After a 2 

5

/

8

” (66.7mm) diameter hole is cut in the 

wall, the sprinkler is easily installed and properly oriented 
with the Model G6 Wrench, as follows:

Do not remove factory installed plastic protective cap since 

it is sized to fit inside the G6 wrench. Note that the sprinkler 
can only mate  when the sprinkler’s deflector orientation tab 
(Fig. 1) is aligned with wrench’s key-way. G6 wrench is pro-
vided with bubble level pad and TOP marking, features that 
assure proper orientation of the internally retained horizontal 
sidewall deflector. Final leveling can be done after leak proof 
joint is obtained with a minimum to maximum torque of 10 to 
20 ft-lbs (13,4 to 26,8 N.m). Do not attempt to compensate 
for improper rough in dimensions of fitting by over tighten-
ing the sprinkler assembly, but readjust the sprinkler fitting 
instead. Leave the protective cap on to assure sprinkler pro-
tection while the wall is plastered, wallpapered or painted.

Concealed cover plate/cup assemblies are listed only for 

use with specific sprinklers.  The use of any other concealed 
cover plate/cup assembly with the Model G6-80 Horizontal 
Sidewall Sprinkler or the use of this dedicated concealed 
cover plate assembly on any sprinkler with which it is not 
specifically listed will void all guarantees, warranties, listings 
and approvals.
* DuPont Registered Trademark