Reliable G5-56 300 Quick Start Manual Download Page 2

Installation 

Do not install the G5-56 300 in ceilings which have pos-

itive pressure in the space above. 
•  Cut a 2

5

/

8

” inch (67mm) diameter hole in the ceiling, 

the sprinkler is easily installed with the Model FC 
Wrench.  The wrench has a socket drive which is in-
serted into the body of the sprinkler.  When installing 
a sprinkler the wrench is first positioned into the sprin-
kler/cup assembly until the wrench socket engages 
the body of the sprinkler.  The sprinkler is then tight-
ened into the pipe fitting.  When inserting or remov-
ing the wrench from the sprinkler/cup assembly, care 
should be taken to prevent damage to the sprinkler.  
DO NOT WRENCH ON ANY OTHER PART OF THE 
SPRINKLER/CUP ASSEMBLY.  Install the cover plate 
by hand turning the cover in the clockwise direction 
until it is tight against the ceiling. 

A protective cap is provided to protect the drop-down 
sprinkler deflector from damage which could occur dur-
ing construction before the cover plate is installed.  The 
cap is factory installed inside the sprinkler cup. Remove 
cap to install sprinkler, then re-install cap until the cover 
plate is installed.

Maintenance

The Model G5-56 300 Concealer

®

 should be inspected 

and the sprinkler system maintained in accordance with 
NFPA 25.   Do not clean sprinklers with soap and water, 
ammonia or any other cleaning  fluids.  Remove dust by 
using a soft brush or gentle vacuuming.  Remove any 
sprinkler that has been painted (other than factory ap-
plied) or damaged in any way.  A stock of spare sprin-
klers should be maintained to allow quick replacement 
of damaged or operated sprinklers.  Prior to installation, 
sprinklers should be maintained in the original cartons 
and packaging until used to minimize the potential for 
damage to sprinklers that would cause improper opera-
tion or non-operation.

Ordering Information

Specify:

1. Sprinkler 

Model

2. Nominal 

Orifice

3. 

Flat Cover Plate Assembly Finish

UL Listing Category

Sprinklers, Automatic and Open 
Quick Response Sprinkler

UL Guide Number

VNIV

Cover Plate Finishes

(1)

Standard Finishes

Chrome
White Paint

Special Application
Finishes

(2)(3)

Bright Brass
Finished Bronze
Black Plating
Black Paint
Off White
Satin Chrome

(1)

 Other finishes and colors are available on special order. Consult 

factory for details. Coverplate custom paint is semi-gloss, unless 
specified otherwise.

(2)

 For the perforated style coverplate, consult factory for availability on 

these and other custom finishes.

(3)

 Available upon request.

Standard Temperature Ratings

Classi

fi

 cation Sprinkler

Link 

Color

Cover

Plate

Max. Ambient

Temp.

Ordinary

165°F/74°C Black 135°F/57°C

100°F/38°C

Intermediate

212°F/100°C White 165°F/74°C

150°F/66°C

Model FC Sprinkler 