background image

Reliable Automatic Sprinkler Co., Inc.,

 

103 Fairview Park Drive, Elmsford, New York 10523

Bulletin  040 Rev

. A

Bulletin 040 Rev. A

Model G5-56 300
Quick Response
Concealed Automatic
300 psi (20,7 bar) Rated 
Sprinkler

The G5-56 300 Concealer

®

A Quick Response Concealed Sprinkler 
with ¾” (19mm) Adjustment

For adjustable K5.6 sprinklers refer to Bulletin 
162 for Technical Specifications and Approvals

Features

1.  Cover plate attachment (Plain or Perforated) 

with ¾” (19mm) total adjustment. Does not 
require clips or springs.

2.  Smooth aesthetic ceiling profile.
3.  Factory installed protective cap.
4.  Available in chrome and white painted finishes.
5.  Ordinary and intermediate temperature rating.
6.  300 psi (20,7 bar) maximum pressure rating.

Listings & Approvals

1.  Listed by Underwriters Laboratories, Inc. and Certified 

by UL for Canada (cULus) - Quick Response

Note:

 Approvals are for light and ordinary hazard.  The 

cup and skirt are fabricated from plated steel and are 
recommended for interior, non-corrosive applications.

Note:

 Paint or any other coatings applied over the factory 

finish will void all approvals and warranties.

US. Patent Number 6,554,077

The Model G5-56 300 Concealer

®

 is a cULus Listed Quick 

Response Concealed Sprinkler intended for use in accor-
dance with NFPA 13.

Product Description

The Reliable Model G5-56 300 Concealer

®

 uses a proven 

quick response fusible element in a standard style sprin-
kler frame with a drop-down deflector.  This assembly is re-
cessed into the ceiling and concealed by a flat cover plate 
assembly.  This threaded engagement provides ¾” (19mm) 
of cover adjustment.  The flat cover plate is attached to the 
skirt using 135°F (57°C) ordinary temperature classification 
solder or 165°F (74°C) intermediate temperature classifica-
tion solder. When the ceiling temperature rises, the solder 
holding the flat cover plate melts, the flat cover plate re-
leased thus exposing the sprinkler inside to the rising ambi-
ent temperature.

The subsequent fusing of the solder element in the sprin-

kler opens the waterway and causes the deflector to drop 
into position to distribute the discharging water.  Any secure 
engagement between the cover plate and cup will assure 
that the drop-down deflector is properly located below the 
ceiling.

Application

The Reliable Model G5-56 300  

Concealer

®

 is a versatile quick 

response concealed sprin-
kler.  It provides the best form 
of fire protection while offering 
an attractive appearance and 
¾” (19mm) cover plate adjust-
ment for ease of installation. The 
small diameter cover plate as-
sembly is easily attached and 

Plain Cover Plate

Perforated Cover Plate

blends into the ceiling, concealing the most dependable 
fire protection, an automatic sprinkler system.

The Model G5-56 300 Concealer

®

 is designed for use 

where aesthetic appearance is important.  It can be used 
at working pressures up to 300 psi (20,7 bar).