background image

Installation

Refer to Figures 1, 2, and 3

Do not install the G4-300 Concealer

®

 in ceilings which have 

positive pressure in the space above.

After a 2

5

/

8

”  (67mm) diameter hole is cut in the ceiling, the 

sprinkler is easily installed with the Model G4 Wrench.  The 
wrench has drive tangs which insert into the cup slots.  When 
installing a sprinkler the wrench is first positioned into the 
sprinkler/cup assembly until the wrench tangs engage the 
drive slots in the top of the cup (there are two sets of drive 
slots in the cup).  The sprinkler is then tightened into the pipe 
fitting.  When inserting or removing the wrench from the sprin-
kler/cup assembly care should be taken to prevent damage 
to the sprinkler.  DO NOT WRENCH ON ANY OTHER PART 
OF THE SPRINKLER/CUP ASSEMBLY.   Final adjustment of 
the cover is made by hand turning the cover in the clockwise 
direction until it is tight against the ceiling. 

A protective cap is provided to protect the drop-down 

sprinkler deflector from damage which could occur during 
construction before the cover plate is installed.  The cap is 
factory installed inside the sprinkler cup.  Remove cap to 
install sprinkler, then re-install cap until the cover plate is in-
stalled.

Maintenance

The Model G4-300 Concealed Sprinklers should be in-

spected and the sprinkler system maintained in accordance 
with NFPA 25.  Do not clean sprinklers with soap and water, 
ammonia or any other cleaning fluids.  Remove any sprinkler 
that has been painted (other than factory applied) or dam-
aged in any way.  A stock of spare sprinklers should be main-
tained to allow quick replacement of damaged or operated 
sprinklers.  Prior to installation, sprinklers should be main-
tained in the original cartons and packaging to minimize the 
potential for damage to sprinklers that would cause improper 
operation or non-operation.

Note:

 Paint or any other coat-

ings applied over the factory 
finish will void all approvals 
and warranties.

Ordering Information 

Specify:
1. Sprinkler 

Model 

2. Nominal 

Orifice

3.  Cover Plate Finish
4. Inlet 

Type

Model G4 Sprinkler 

Wrench

Cover Plate Finishes

(1)

Standard Finishes

Chrome
White Paint

Special Application
Finishes

(2)

Bright Brass
Finished Bronze
Black Plating
Black Paint
Off White
Satin Chrome

(1)

 Other finishes and colors are 

available on special order. Con-
sult factory for details. Cover-
plate custom paint is semi-gloss, 
unless specified otherwise.

(2)

 For the perforated style cover-

plate, consult factory for avail-
ability on these and other custom 
finishes.

2.

Standard Temperature Ratings

Classi

fi

 cation

Sprinkler

Cover Plate

Max. Ambient Temp.

Ordinary
Ordinary
Ordinary

Intermediate

135°F/57°C
165°F/74°C

165°F/ 74°C

212°F/100°C

135°F/57°C
135°F/57°C
165°F/74°C
165°F/74°C

100°F/38°C
100°F/38°C
100°F/38°C
150°F/66°C

Technical Data

Sprinkler Inlet

Total

Adjustment

Nominal 

Ori

fi

 ce

Nominal K Factor

Thread

Approvals

Sprinkler

Identi

fi

 cation 

Number (SIN)

US

Metric

Non Adjustable

½” (13mm)

½” (15mm)

5.6

80

½” NPT (R½)

1, 2, 3

R6115

Adjustable

1½” (38mm)

½” (15mm)

5.6

80

1” NPT  Male or Female

1, 2, 3

R6118

Reviews: