Model G Conventional

Model G Series Conventional Sprinklers

Sprinkler 

Model

K-Factor gpm/psi

1/2

 

(lpm/bar

1/2

)

Orientation

Response

Listings & 

Approvals

Max. Working 

Pressure psi (bar)

Sprinkler 

Identification 

Number (SIN)

G

4.10 (59.1)

Conventional

SR

Planiere Assemblee

175 psi (12 bar)

R1074

5.62 (81.0)

LPCB, CE, Planiere 

Assemblee

R1075

8.2 (118.2)

LPCB, CE, Planiere 

Assemblee

 R1077

Table A

Note: 

 Not all versions of the sprinkler are shown.

Features

• 

Standard response

• 

Conventional deflector

• 

Robust solder capsule thermal element

• 

Available in a wide variety of finishes

Product Description

Conventional (or “old-style” sprinklers) direct approximately 40% 
of their water discharge up against the ceiling and the remainder 
downward to the floor, and may be used in either the upright or 
pendent position.

Reliable Model G Conventional Sprinklers are standard-response 

fire sprinklers utilizing a solder capsule/strut and lever thermal 

element.

These sprinklers are available in 4.10 (59.1 metric), 5.62 (81.0 
metric), and 8.2 (118.2 metric) K factor.

When used in the pendent position, sprinklers may be installed 
exposed or surface mounted using escutcheons such as the 
Reliable Models B, C, or HB (reference Technical Bulletin 204).

Table A provides a summary of the approvals and availability of 

specific Model G Series Conventional sprinkler configurations. 

Additional technical information for each sprinkler model is 
provided on the following pages.

www.reliablesprinkler.com

K Factor 4.10 (59.1), 5.62 (81.0), and 8.2 (118.2)

Model G

Conventional Sprinklers

Bulletin 079 May 2021

Summary of Contents for G Series

Page 1: ...t the ceiling and the remainder downward to the floor and may be used in either the upright or pendent position Reliable Model G Conventional Sprinklers are standard response fire sprinklers utilizing a solder capsule strut and lever thermal element These sprinklers are available in 4 10 59 1 metric 5 62 81 0 metric and 8 2 118 2 metric K factor When used in the pendent position sprinklers may be ...

Page 2: ...nkler Frame Leaded Red Brass Alloy Cap Brass Alloy with PTFE Load Screw Brass CDA Alloy Deflector Brass CDA Alloy Sprinkler Finishes See Table B Sensitivity Standard Response Temperature Ratings 135 F 57 C 165 F 74 C 212 F 100 C 286 F 141 C Sprinkler Wrench Model W2 Listings and Approvals Pleniere Assemblee Model G 3 8 Conventional Sprinkler Components and Dimensions Figure 1 Bulletin 079 May 2021...

Page 3: ... Leaded Red Brass Alloy Cap Brass Alloy with PTFE Load Screw Brass CDA Alloy Deflector Brass CDA Alloy Sprinkler Finishes See Table B Sensitivity Quick Response Temperature Ratings 135 F 57 C 165 F 74 C 212 F 100 C 286 F 141 C Sprinkler Wrenches Model W2 Listings and Approvals LPCB Pleniere Assemblee CE 1438 CPR 0052 Model G 1 2 Conventional Sprinkler Components and Dimensions Figure 2 Bulletin 07...

Page 4: ...Leaded Red Brass Alloy Cap Brass Alloy with PTFE Load Screw Brass CDA Alloy Deflector Brass CDA Alloy Sprinkler Finishes See Table B Sensitivity Standard Response Temperature Ratings 135 F 57 C 165 F 74 C 212 F 100 C 286 F 141 C Sprinkler Wrenches Model W2 Listings and Approvals LPCB Pleniere Assemblee CE 1438 CPR 0052 Model G 3 4 Conventional Sprinkler Components and Dimensions Figure 3 Bulletin ...

Page 5: ...ce any sprinkler which has been painted other than factory applied A stock of spare sprinklers should be maintained to allow quick replacement of damaged or operated sprinklers Failure to properly maintain sprinklers may result in inadvertent operation or non operation during a fire event Standard Finishes Special Application Finishes Bronze Bright Brass 3 Chrome Plated Black Plated White Polyeste...

Reviews: