Reliable Automatic Sprinkler Co., Inc.,

 103 Fairview Park Drive, Elmsford, New York 10523

Model F3QR56 Dry

K5.6 (80 metric)

Quick-Response,

Standard Spray Sprinklers

Bulletin 157 

Rev
.

 M

Bulletin 157 

Rev. 

M

Features

1.  Available in the following configurations:

•  Pendent with standard escutcheon
•  Pendent with Model HB extended escutcheon
•  Pendent with Model FP recessed escutcheon
•  Pendent with Model F1 recessed escutcheon
•  Concealed Pendent with Model CCP cover plate
•  Horizontal Sidewall with Standard escutcheon
•  Horizontal Sidewall with Model HB extended es-

cutcheon

•  Horizontal Sidewall with Model FP recessed es-

cutcheon (FM Standard Response)

•  Horizontal Sidewall with Model F1 recessed es-

cutcheon (FM Standard Response)

2.  Available with 1” NPT, ISO7-1R1, 3/4” NPT, or ISO7-

1R3/4 inlet fitting.

3.  3/4” NPT inlet fittings permit replacement of older 3/4” 

inlet dry sprinklers without changing to a larger sprin-
kler fitting.

4.  Sprinklers, escutcheons, and cover plates are avail-

able in a wide variety of standard and special appli-
cation finishes.

5.  White polyester, black polyester, and Electroless 

Nickel PTFE (ENT) finish sprinklers are cULus Listed 
as Corrosion Resistant. 

6.  Available with cULus Listed 250 psi (17.2 bar) pres-

sure rating for Dry Pendent and select HSW configu-
rations. FM Approved for 175 psi (12 bar).

Product Description

Model F3QR56 Dry sprinklers are quick-response, stan-

dard coverage sprinklers with a nominal K-Factor of 5.6 (80 
metric). Available in Dry Pendent or Dry Horizontal Sidewall 
configurations, Model F3QR56 Dry sprinklers all use a 3 mm 
glass bulb operating element. See the Temperature Rat-
ings table in this Bulletin for available temperature ratings. 
Model F3QR56 Dry sprinklers are intended for installation 
on wet-pipe, dry-pipe, or preaction sprinkler systems in ac-
cordance with NFPA 13, FM Property Loss Prevention Data 
Sheets, and other applicable installation standards.

Model F3QR56 Dry sprinklers are available with a vari-

ety of escutcheon options as illustrated in Figs. 1 through 
3 and Figs. 5 through 9. In addition, Model F3QR56 Dry 
Pendent sprinklers are also available with the Model CCP 
conical concealed cover plate as illustrated in Fig. 4. Avail-
able sprinkler, escutcheon, and cover plate finishes are 
identified in the Finishes table in this Bulletin. The Model F1 
escutcheon, Model FP escutcheon, and Model CCP cover 
plate are the only recessed escutcheons and cover plate 
listed for use with Model F3QR56 Dry sprinklers; the use of 
any other recessed escutcheon or cover plate with Model 
F3QR56 Dry sprinklers will void all guarantees, warranties, 
listings and approvals.

Concealed

(See Fig. 4)

Recessed FP Pendent

(See Fig. 3)

 Recessed F1

Horizontal Sidewall

(See Fig. 9)

 Horizontal Sidewall

(See Fig. 6)

Pendent

(See Fig. 1)

Recessed F1 Pendent

(See Fig. 5)

 Recessed FP 

Horizontal Sidewall

(See Fig. 8)

Pendent / HB

(See Fig. 2)

Horizontal Sidewall / HB

(See Fig. 7)

Summary of Contents for F3QR56 Dry

Page 1: ...ry sprinklers are quick response stan dard coverage sprinklers with a nominal K Factor of 5 6 80 metric Available in Dry Pendent or Dry Horizontal Sidewall configurations Model F3QR56 Dry sprinklers a...

Page 2: ...eon CCP Cover Plate Standard Escutcheon 2 to 48 50 to 1200 mm cULus FM NYC 1 NPT or ISO7 1R1 HB Extended Escutcheon 3 1 2 to 48 90 to 1200 mm F1 Recessed Escutcheon FP Recessed Escutcheon CCP Cover Pl...

Page 3: ...F 68 C Intermediate Yellow 175 F 79 C 165 F 74 C 150 F 66 C cULus NYC Intermediate Green 200 F 93 C 165 F 74 C 150 F 66 C cULus FM NYC High Blue 286 F 141 C None 225 F 107 C cULus FM 2 NYC 165 F 74 C...

Page 4: ...ent provides 6mm to 1 32mm A dimension adjustment range Fig 1 Model F3QR56 Dry Pendent Sprinkler with Standard Escutcheon SIN R5714 A Dim 2 to 48 51mm to 1219mm in 1 4 6mm increments for 1 connections...

Page 5: ...o 1219mm in 1 4 6mm increments for 1 connections or 3 to 36 89mm to 914mm in 1 4 6mm increments for 3 4 connections Note The sprinkler can protrudes 1 when escutcheon is in nominal position Escutcheon...

Page 6: ...in ceilings which have positive pressure in the space above Fig 3 6 Model F3QR56 Dry Pendent Sprinkler with Model FP Recessed Escutcheon SIN R5714 A Dim 31 2 to 48 89mm to 1219mm in 1 4 6mm increment...

Page 7: ...o 48 89mm to 1219mm in 1 4 6mm increments for 1 connections or 3 to 36 89mm to 914mm in 1 4 6mm increments for 3 4 connections Note Do not install the Model F3QR56 Dry Pendent sprinkler with the Model...

Page 8: ...Dry Pendent Sprinkler with Model F1 Recessed Escutcheon SIN R5714 A Dim 31 2 to 48 89mm to 1219mm in 1 4 6mm increments for 1 connections or 3 to 36 89mm to 914mm in 1 4 6mm increments for 3 4 connect...

Page 9: ...ustment provides 6mm to 1 32mm A dimension adjustment range Fig 6 9 Model F3QR56 Dry Horizontal Sidewall Sprinkler with Standard Escutcheon SIN R5734 A Dim 2 to 48 51mm to 1219mm in 1 4 6mm increments...

Page 10: ...31 2 to 48 89mm to 1219mm in 1 4 6mm increments for 1 connections or 3 to 36 89mm to 914mm in 1 4 6mm increments for 3 4 connections Note The sprinkler can protrudes 1 when escutcheon is in nominal p...

Page 11: ...48 89mm to 1219mm in 1 4 6mm increments for 1 connections or 3 to 36 89mm to 914mm in 1 4 6mm increments for 3 4 connections Note Do not install the Model F3QR56 Dry Horizontal Sidewall sprinkler with...

Page 12: ...Horizontal Sidewall Sprinkler with Model F1 Recessed Escutcheon SIN R5734 A Dim 31 2 to 48 89mm to 1219mm in 1 4 6mm increments for 1 connections or 3 to 36 89mm to 914mm in 1 4 6mm increments for 3...

Page 13: ...13 Fig 10...

Page 14: ...Fig 11 14...

Page 15: ...Fig 13 Model XLO2 Wrench Fig 12 Model F3 or Model F3R Wrench 15...

Page 16: ...C31400 6 GLASS BULB GLASS W GLYCERIN SOLUTION 7 ORIFICE ADAPTOR BRASS ALLOY PER UNS C36000 8 OUTER TUBE GALVANIZED STEEL 9 INNER TUBE BRASS ALLOY PER UNS C23000 10 YOKE BRASS ALLOY PER UNS C38000 11 I...

Page 17: ...f the sprinkler s inlet fitting 3 Install the sprinkler in the fitting using the installation wrench specified in the Installation Data table The Model F3 and F3R wrenches are designed to be in serted...

Page 18: ...or Cover Plate Suggested Hole Diameter in Wall or Ceiling Required Centerline of Sprinkler Tube Inlet to Finished Ceiling Vertical Dimension Installation Wrench F3QR56 Dry Pendent Standard Escutcheon...

Reviews: