Reliable F3 Manual Download Page 4

4.

Model F3QR Dry Recessed FP Horizontal Sidewall Sprinkler

•  Listed by cULus for Quick Response. Approved by FM for 

Standard Response.

•  Recessed Horizontal sidewall sprinklers are listed with cULus 

for installation of min. 4” (100mm) - to - max. 6” (150mm) below 
ceiling and  approved by FM for installation of min. 4” (100mm) 
- to - max. 12” (300mm) below ceiling.

“A” Dim.

3

1

/

2

” to 48” (89mm to 1219mm) in ¼” (6mm) increments

Finishes 

(1)

Sprinkler

Escutcheon

Electroless Nickel PTFE(Teflon

®

)*

(3)

Bronze

Chrome 

White Polyester 

(2)

Electroless Nickel PTFE  (Teflon

®

)*

(4) 

 Brass

Chrome 

White

(1)

 Other finishes and colors are available on special order.

    Consult factory for details. Cup remainds unfinished. “See page 2”

(2)

 cULus Listed as a Corrosion Resistant sprinkler in standard Black or 

White.

(3)

 cULus Listed Corrosion Resistant Sprinkler.

(4)

 Sprinkler’s can and FP Escutcheon Electroless Nickel PTFE (Teflon

®

)*  

    Plated recommended for exterior applications.

Standard Temperature Ratings

Classi

fi

 cation

Sprinkler Tem-

perature Rating

Max.

Ambient Temp.

Bulb Color

Ordinary
Ordinary
Intermediate 

(1)

Intermediate
High 

(1)

135°F   (57°C)
155°F   (68°C)
175°F   (79°C)
200°F   (93°C)
286°F (141°C)

100°F   (38°C) 
100°F   (38°C)
150°F   (66°C)
150°F   (66°C)
225°F (107°C)

Orange
Red
Yellow
Green
Blue

(1)

 Listed and Certi

fi

 ed only by cULus.

Notes:

 Do not install the Model F3QR Dry Recessed FP Horizontal 

Sidewall Sprinkler in walls which have positive pressure in their 
side space.

Fig. 8

Model F3QR Dry Horizontal Sidewall Sprinkler

“A” Dim.

2” to 48” (51mm to 1219mm) in ¼” (6mm) increments

Finishes

(1)

Sprinkler

Escutcheon

Electroless Nickel PTFE(Teflon

®

)*

(4)

Bronze

Chrome 

White Polyester 

(2)

Electroless Nickel PTFE (Teflon

®

)*  

 Brass 

(3)

 

Chrome 

White

(1)

 Other finishes and colors are available on special order.

    Consult factory for details. 

(2)

 cULus Listed as a Corrosion Resistant sprinkler in standard Black or 

White.

(3)

 Not available for HB escutcheons.

(4)

 cULus listed Corrosion Resistant 

Note:

  The sprinkler can protrudes ¼” when escutcheon is in nominal 

position.  Escutcheon  adjustment provides -¼” (-6mm) to  +1¼”  
(+32mm) “A” dimension adjustment range.

Fig. 6

Note:

  The sprinkler can protrudes 1¼” when escutcheon is in nomi-

nal position.  Escutcheon adjustment provides -½” (-12.7mm) to 
+½” (+12.7mm) “A” dimension adjustment range.

Fig. 7

Model F3QR Dry HSW w/HB Escutcheon

“A” Dim.

3

1

/

2

” to 48” (89mm to 1219mm) in ¼” (6mm) increments

Standard Temperature Ratings

Classi

fi

 cation

Sprinkler 

Temperature 

Rating

Max.

Ambient 

Temp.

Bulb Color

Ordinary
Ordinary
Intermediate 

(1)

Intermediate
High

135°F   (57°C)
155°F   (68°C)
175°F   (79°C)
200°F   (93°C)
286°F (141°C)

100°F   (38°C) 
100°F   (38°C)
150°F   (66°C)
150°F   (66°C) 
225°F (107°C)

Orange
Red
Yellow
Green
Blue

 

(1)

 Listed and Certi

fi

 ed only by cULus.

Sprinkler Installation Wrench: 

Model F3 Sprinkler Wrench

Sprinkler Identi

fi

 cation Number (SIN): R5734

*DuPont Registered Trademark

Sprinkler Installation Wrench:

Model XLO2 Sprinkler Wrench

Sprinkler Identi

fi

 cation Number (SIN): R5734

Summary of Contents for F3

Page 1: ... specific styles for correct A dimension range 9 Available in a variety of plated and painted finishes 10 Polyester Coated or Electroless Nickel PTFE Teflon Plated Corrosion Resistant Sprinklers Concealed Sprinkler is not corrosion resistance US Patent Numbers 5 775 431 and 5 967 240 Other US Patents pending Approvals 1 Listed by Underwriters Laboratories Inc and UL Certified for Canada cULus Styl...

Page 2: ...286 F 141 C 100 F 38 C 100 F 38 C 150 F 66 C 150 F 66 C 225 F 107 C Orange Red Yellow Green Blue Sprinkler cup and FP Escutcheon fabricated of steel and recommended for interior applications Note The sprinkler can protrudes when escutcheon is in nominal position Escutcheon adjustment provides 6mm to 1 32mm A dimension adjustment range Fig 1 Note Do not install the Model F3QR Dry Recessed FP Penden...

Page 3: ...er Wrench Sprinkler Identification Number SIN R5714 Note Do not install the Model F3QR Dry Concealed Pendent Sprinkler in ceilings which have positive pressure in the space above Fig 4 Model F3QR Dry Recessed F1 Pendent Sprinkler A Dim 31 2 to 48 89mm to 1219mm in 6mm increments Finishes 1 Sprinkler Escutcheon Collar Electroless Nickel PTFE Teflon 3 Chrome White Polyester 2 Electroless Nickel PTFE...

Page 4: ...prinkler in walls which have positive pressure in their side space Fig 8 Model F3QR Dry Horizontal Sidewall Sprinkler A Dim 2 to 48 51mm to 1219mm in 6mm increments Finishes 1 Sprinkler Escutcheon Electroless Nickel PTFE Teflon 4 Bronze Chrome White Polyester 2 Electroless Nickel PTFE Teflon Brass 3 Chrome White 1 Other finishes and colors are available on special order Consult factory for details...

Page 5: ...nsystemsandinareassubjectedtofreezingtemperatures such asfreezersandunheatedportionsinsideandoutsidebuildings Environments wherein dry sprinklers are employed can be cor rosive Forthisreason ModelF3Sprinklershaveaspecialwaxfillet placedinthegapbetweenthecupthatsupportsthebulbandthe wrenching boss This wax will not interfere with the operation of the sprinkler and it prevents contaminents from ente...

Page 6: ...th its jaws above the sprinkler de flector is moved laterally until centered with the cup Then raise the wrench inside of the cup until its jaws engage the sprinkler s square wrenching pads Fig 14 To remove the wrench follow this procedure in reverse order Care should be taken to avoid striking the deflector with the wrench Model F3 Wrench Fig 15 is used for installation of Pendent and Horizontal ...

Page 7: ...Fig 10 7 ...

Page 8: ...8 Fig 11 ...

Page 9: ...Fig 13 XLO2 Wrench Fig 15 F3 Wrench Fig 14 XLO2 Wrench Fig 12 XLO2 Wrench 9 ...

Page 10: ...throughout the United States Canada and foreign countries Automatic sprinklers Flush automatic sprinklers Recessed automatic sprinklers Concealed automatic sprinklers Adjustable automatic sprinklers Dry automatic sprinklers Intermediate level sprinklers Open sprinklers Spray nozzles Alarm valves Retarding chambers Dry pipe valves Accelerators for dry pipe valves Mechanical sprinkler alarms Electri...

Reviews: