Sprinkler 

Model

K-Factor gpm/psi

1/2

 

(lpm/bar

1/2

)

Orientation

Response

Listings & 

Approvals

Max. Working 

Pressure psi (bar)

Sprinkler 

Identification 

Number (SIN)

F1XLH 

4.2 (60)

Upright

SR

cULus

175 psi (12 bar)

RA1323

Pendent

RA1313

F1FRXLH 

4.2 (60)

Upright

QR

cULus

175 psi (12 bar)

 RA1423

Pendent

RA1413

Table A

Features

• 

Standard Response or Quick Response

• 

Standard Spray Deflectors

• 

Low profile, compact design

• 

Available in a wide variety of finishes

Product Description

Reliable Model F1XLH Standard Spray Sprinklers are standard 

response fire sprinklers utilizing a 5.0 mm glass bulb thermal 
element.

Reliable Model F1FRXLH Standard Spray Sprinklers are quick 

response fire sprinklers utilizing a sensitive 3.0 mm thermal glass 
bulb element.

These sprinklers are characterized by a 4.2 (60 metric) K-factor 

with a pintle on the deflector.

Table A provides a summary of the approvals and availability 
of specific Model F1XLH and F1FRXLH Series Standard Spray 
Sprinkler configurations. Additional technical information for each 
sprinkler model is provided on the following pages.

Pendent sprinklers may be installed exposed or surface mounted 
using escutcheons such as the Reliable Models B, C, or HB 
(reference Technical Bulletin 204). When installed recessed, the 
Models F1XLH and F1FRXLH series sprinklers are specifically 
listed and may only be installed with listed recessed escutcheons. 
Refer to the technical information on the following pages for 
specific listings for recessed sprinklers, and refer to Figure 5 for 
dimensional information.

www.reliablesprinkler.com

K-factor 4.2 (60 metric)

F1XLH and F1FRXLH Series 

Standard Spray Sprinklers

Bulletin 184 January 2022

Summary of Contents for F1XLH Series

Page 1: ...ire sprinklers utilizing a sensitive 3 0 mm thermal glass bulb element These sprinklers are characterized by a 4 2 60 metric K factor with a pintle on the deflector Table A provides a summary of the a...

Page 2: ...g Washer Nickel with PTFE Load Screw Copper Alloy Deflector Brass Alloy Sprinkler Finishes See Table B Sensitivity Standard Response Temperature Ratings 135 F 57 C 155 F 68 C 175 F 79 C 200 F 93 C 286...

Page 3: ...itivity Standard Response Temperature Ratings 135 F 57 C 155 F 68 C 175 F 79 C 200 F 93 C 286 F 141 C 360 F 182 C Guards and Shields F7 Guard F8 Guard with Shield Recessed Escutcheons F1 cULus F2 cULu...

Page 4: ...Sealing Washer Nickel with PTFE Load Screw Copper Alloy Deflector Brass Alloy Sprinkler Finishes See Table B Sensitivity Quick Response Temperature Ratings 135 F 57 C 155 F 68 C 175 F 79 C 200 F 93 C...

Page 5: ...See Table B Sensitivity Quick Response Temperature Ratings 135 F 57 C 155 F 68 C 175 F 79 C 200 F 93 C 286 F 141 C Guards and Shields F7 Guard F8 Guard with Shield Recessed Escutcheons F1 cULus F2 cUL...

Page 6: ...available on special order Consult your Reliable sales representative for details 2 Paint or any other coating applied over the factory finish will void all approvals and warranties 3 The Model FP an...

Page 7: ...er Finish See Table B Sprinkler Wrench Model W2 Model W4 Recessed Model J with guard installed Guards and Shields See individual sprinkler pages Installation Model F1XLH and F1FRXLH Series sprinklers...