background image

Installation

Model F1FR Series sprinklers must be installed in accordance with 
NFPA13 and the requirements of all applicable authorities having 
jurisdiction.  Model F1FR Series sprinklers must be installed with 
the Reliable sprinkler installation wrench identified in this Bulletin. 
Any other wrench may damage the sprinkler.  The Models W2 and 
W4 wrenches have two sets of jaws.  Use the smallest set of jaws 
that fit on the wrench flats of the sprinkler.  A leak tight sprinkler 

joint can be obtained with a torque of 8 to 18 lb-ft (11 to 24 

N-m). Do not tighten sprinklers over the maximum recommended 
installation torque. Exceeding the maximum recommended 
installation torque may cause leakage or impairment of the 

sprinkler.

Glass bulb sprinklers have orange bulb protectors or protective 
caps to minimize bulb damage during shipping, handling and 

installation. Reliable sprinkler installation wrenches are designed 

to install sprinklers with bulb protectors in place. Remove the bulb 
protector at the time when the sprinkler system is placed in service 
for fire protection. Removal of the bulb protector before this time 
may leave the bulb vulnerable to damage. Remove bulb protectors 
by undoing the clasp by hand. Do not use tools to remove bulb 

protectors.

Standard Finishes

Special Application Finishes

Sprinkler

F1, F2 and FP

(3)

Escutcheons

Sprinkler

F1, F2 and FP

(3)

Escutcheons

Bronze

Brass

Electroless Nickel PTFE

(4)(5)

Bright Brass

Chrome Plated

Chrome Plated

Bright Brass

(6)

Black Plated

White Polyester

(4)

White Polyester

Black Plated

Black Paint

Black Paint

(7)

Off White

Off White

(7)

Chrome Dull

Chrome Dull

Notes:

1. 

Other finishes and colors are available on special order. Consult your Reliable sales representative for details.

2. 

Paint or any other coating applied over the factory finish will void all approvals and warranties.

3. 

The Model FP and CCP assemblies consist of a sprinkler mounted in a galvanized steel cup with a finished trim ring or cover plate.

4. 

cULus Listed as corrosion resistant.

5. 

FM Approved as corrosion resistant.

6. 

For 200°F (93°C) maximum temperature rated sprinklers only.

7. 

cULus Only.

Finishes

(1)(2)

Table B

Maintenance

Reliable Model F1FR series sprinklers should be inspected and 

the sprinkler system maintained in accordance with NFPA 25, as 
well as the requirements of any Authorities Having Jurisdiction.

Prior to installation, sprinklers should remain in the original 
cartons and packaging until used. This will minimize the potential 
for damage to sprinklers that could cause improper operation or 

non-operation.

Do not clean sprinklers with soap and water, ammonia liquid or 
any other cleaning fluids. Remove dust by gentle vacuuming 

without touching the sprinkler.

Replace any sprinkler which has been painted (other than factory 

applied). A stock of spare sprinklers should be maintained to 
allow quick replacement of damaged or operated sprinklers.  
Failure to properly maintain sprinklers may result in inadvertent 
operation or non-operation during a fire event.

 Wrenches

Model W2 (upright, pendent)

Model J (with guard installed)

Model W4
(recessed pendent)

Bulletin 063
August 2021

Page 5 of 6

www.reliablesprinkler.com

Summary of Contents for F1FR80 Series

Page 1: ...alled exposed or surface mounted using escutcheons such as the Reliable Models B C or HB reference Technical Bulletin 204 When installed recessed the Model F1FR80 series sprinklers are specifically listed with and may only be installed with listed Reliable recessed escutcheons Refer to the technical information on the following pages for specific listings for recessed installations and refer to Fi...

Page 2: ...sher Nickel with PTFE Load Screw Copper Alloy Deflector Brass Alloy Sprinkler Finishes See Table B Sensitivity Quick response Temperature Ratings 135 F 57 C 155 F 68 C 175 F 79 C 200 F 93 C 286 F 141 C Guards Shields F 1 Guard cULus FM F 2 Guard FM F 3 Guard with Shield cULus FM Sprinkler Wrenches Model W2 Model J with guard installed Listings and Approvals cULus FM LPCB VdS CE Model F1FR80 Uprigh...

Page 3: ...cheons Model F1 cULus Model F2 cULus FM Model FP cULus Guards Shields 2 F 2 Guard FM F 6 Guard Shield Kit FM F 7 Guard cULus F 8 Guard Shield Kit cULus S 2 Shield cUlus FM Sprinkler Wrenches Model W2 pendent Model W4 recessed Model J with guard installed Listings and Approvals 3 cULus Listed FM Approved LPCB VdS CE Notes 1 286 F 141 C temperature rated sprinkler not listed for recessed use 2 Not s...

Page 4: ...Recessed and Concealed Installation Pendent Sprinklers Figure 3 FP Escutcheon F1 Escutcheon F2 Similar Bulletin 063 August 2021 Page 4 of 6 www reliablesprinkler com ...

Page 5: ...s 6 Black Plated White Polyester 4 White Polyester Black Plated Black Paint Black Paint 7 Off White Off White 7 Chrome Dull Chrome Dull Notes 1 Other finishes and colors are available on special order Consult your Reliable sales representative for details 2 Paint or any other coating applied over the factory finish will void all approvals and warranties 3 The Model FP and CCP assemblies consist of...

Page 6: ...ering Information Specify the following when ordering Model F1FR80 Deflector Orientation Upright Upright Intermediate Pendent Temperature Rating See sprinkler technical specifications Sprinkler Finish See Table B Recessed Escutcheon F1 F2 FP Escutcheon Finish See Table B Sprinkler Wrench Model W2 upright and pendent Model W4 recessed Model J with guard installed ...

Reviews: