Installation
Model F1FR Series sprinklers must be installed in accordance with
NFPA13 and the requirements of all applicable authorities having
jurisdiction. Model F1FR Series sprinklers must be installed with
the Reliable sprinkler installation wrench identified in this Bulletin.
Any other wrench may damage the sprinkler. The Models W2 and
W4 wrenches have two sets of jaws. Use the smallest set of jaws
that fit on the wrench flats of the sprinkler. A leak tight sprinkler
joint can be obtained with a torque of 8 to 18 lb-ft (11 to 24
N-m). Do not tighten sprinklers over the maximum recommended
installation torque. Exceeding the maximum recommended
installation torque may cause leakage or impairment of the
sprinkler.
Glass bulb sprinklers have orange bulb protectors or protective
caps to minimize bulb damage during shipping, handling and
installation. Reliable sprinkler installation wrenches are designed
to install sprinklers with bulb protectors in place. Remove the bulb
protector at the time when the sprinkler system is placed in service
for fire protection. Removal of the bulb protector before this time
may leave the bulb vulnerable to damage. Remove bulb protectors
by undoing the clasp by hand. Do not use tools to remove bulb
protectors.
Standard Finishes
Special Application Finishes
Sprinkler
F1, F2 and FP
(3)
Escutcheons
Sprinkler
F1, F2 and FP
(3)
Escutcheons
Bronze
Brass
Electroless Nickel PTFE
(4)(5)
Bright Brass
Chrome Plated
Chrome Plated
Bright Brass
(6)
Black Plated
White Polyester
(4)
White Polyester
Black Plated
Black Paint
Black Paint
(7)
Off White
Off White
(7)
Chrome Dull
Chrome Dull
Notes:
1.
Other finishes and colors are available on special order. Consult your Reliable sales representative for details.
2.
Paint or any other coating applied over the factory finish will void all approvals and warranties.
3.
The Model FP and CCP assemblies consist of a sprinkler mounted in a galvanized steel cup with a finished trim ring or cover plate.
4.
cULus Listed as corrosion resistant.
5.
FM Approved as corrosion resistant.
6.
For 200°F (93°C) maximum temperature rated sprinklers only.
7.
cULus Only.
Finishes
(1)(2)
Table B
Maintenance
Reliable Model F1FR series sprinklers should be inspected and
the sprinkler system maintained in accordance with NFPA 25, as
well as the requirements of any Authorities Having Jurisdiction.
Prior to installation, sprinklers should remain in the original
cartons and packaging until used. This will minimize the potential
for damage to sprinklers that could cause improper operation or
non-operation.
Do not clean sprinklers with soap and water, ammonia liquid or
any other cleaning fluids. Remove dust by gentle vacuuming
without touching the sprinkler.
Replace any sprinkler which has been painted (other than factory
applied). A stock of spare sprinklers should be maintained to
allow quick replacement of damaged or operated sprinklers.
Failure to properly maintain sprinklers may result in inadvertent
operation or non-operation during a fire event.
Wrenches
Model W2 (upright, pendent)
Model J (with guard installed)
Model W4
(recessed pendent)
Bulletin 063