The Reliable Automatic Sprinkler Co., Inc.,
103 Fairview Park Drive, Elmsford, New York 10523
Model F1FR
Model F1FR Recessed
Quick Response Extended
Coverage Sprinklers
Bulletin 148
Rev
.
F
Bulletin 148
Rev.
F
A complete line of UL Listed and FM Approved
quick response extended coverage sprinklers
for light hazard applications.
Horizontal Sidewall Sprinklers are approved
for installation 4” - 12” (102mm - 305mm)
below the ceiling.
Model F1FR QREC Sprinkler Types
Extended Coverage Pendent
Extended Coverage Horizontal Sidewall
• EC-9 Deflector
Model F1FR QREC Recessed Sprinkler Types
Recessed Extended Coverage Pendent
Recessed Extended Coverage Horizontal
Sidewall:
• EC-9 Deflector
For Model F1FR QREC ½” K 5.6 (80) Sprinkler Types
refer to Bulletin 028 for technical specifications and
approvals.
Approval Organizations
1. Underwriters’ Laboratories, Inc. (UL)
2. Underwriters Laboratories of Canada (ULC)
3. Factory Mutual Approvals (FM)
4. NYC MEA 258-93-E
UL Listing Category
Sprinklers, Automatic & Open
Quick Response Extended Coverage Sprinkler
UL Guide Number
VNIV
Note:
Consult appropriate FM Installation Standards
regarding limitations of room size, ceiling height and
minimum wall fire resistance rating.
Product Description
Reliable Models F1FR QREC and F1FR QREC Recessed
Sprinklers are quick response sprinklers which combine the
durability for a standard sprinkler with the attractive low pro-
file of a decorative sprinkler.
The Models F1FR QREC and F1FR QREC Recessed Auto-
matic Sprinklers utilize a 3.0mm frangible glass bulb. These
sprinklers have demonstrated response times in laboratory
tests which are five times faster than standard response
Recessed Extended
Coverage Pendent
Extended Coverage
Pendent
sprinklers. This quick response enables these sprinklers to
apply water to a fire much faster than standard sprinklers of
the same temperature rating.
The glass bulb consists of an accurately controlled amount
of special fluid hermetically sealed inside a precisely manu-
factured glass capsule. This glass bulb is specially con-
structed to provide fast thermal response. The balance of
parts are made of brass, copper and beryllium nickel.
The temperature rating of the sprinkler is identified by the
color of the glass bulb.
Application
Quick response sprinklers are used in fixed fire protec-
tion systems: Wet, Dry, Deluge or Preaction. Care must be
exercised that the orifice size, temperature rating, deflector
style and sprinkler type are in accordance with the latest
published standards of the National Fire Protection Asso-
ciation or the approving authority having jurisdiction. Quick
response sprinklers are intended for installation as specified
in NFPA 13.
Extended Coverage
Horizontal Sidewall EC-9
Recessed Extended
Coverage Horizontal Sidewall
EC-9