background image

The Reliable Automatic Sprinkler Co., Inc.,

 103 Fairview Park Drive, Elmsford, New York 10523

Model F1FR

Model F1FR Recessed

Quick Response Extended

Coverage Sprinklers

Bulletin 148 

Rev
.

 F

Bulletin 148 

Rev. 

F

A complete line of UL Listed and FM Approved 

quick response extended coverage sprinklers 

for light hazard applications.
Horizontal Sidewall Sprinklers are approved 

for installation 4” - 12” (102mm - 305mm) 

below the ceiling.
Model F1FR QREC Sprinkler Types

Extended Coverage Pendent
Extended Coverage Horizontal Sidewall 
•  EC-9 Deflector

Model F1FR QREC Recessed Sprinkler Types

Recessed Extended Coverage Pendent
Recessed Extended Coverage Horizontal
Sidewall:
•  EC-9 Deflector

For Model F1FR QREC ½” K 5.6 (80) Sprinkler Types
refer to Bulletin 028 for technical specifications and
approvals.

Approval Organizations

1.  Underwriters’ Laboratories, Inc. (UL)
2.  Underwriters Laboratories of Canada (ULC)
3.  Factory Mutual Approvals (FM)
4.  NYC MEA 258-93-E

UL Listing Category

Sprinklers, Automatic & Open
Quick Response Extended Coverage Sprinkler

UL Guide Number

 VNIV

Note:

 Consult appropriate FM Installation Standards

regarding limitations of room size, ceiling height and
minimum wall fire resistance rating.

Product Description 

Reliable Models F1FR QREC and F1FR QREC Recessed 

Sprinklers are quick response sprinklers which combine the 
durability for a standard sprinkler with the attractive low pro-
file of a decorative sprinkler.

The Models F1FR QREC and F1FR QREC Recessed Auto-

matic Sprinklers utilize a 3.0mm frangible glass bulb.  These 
sprinklers have demonstrated response times in laboratory 
tests which are five times faster than standard response 

Recessed Extended 

Coverage Pendent

Extended Coverage 

Pendent

sprinklers.  This quick response enables these sprinklers to 
apply water to a fire much faster than standard sprinklers of 
the same temperature rating.

The glass bulb consists of an accurately controlled amount 

of special fluid hermetically sealed inside a precisely manu-
factured glass capsule.  This glass bulb is specially con-
structed to provide fast thermal response.  The balance of 
parts are made of brass, copper and beryllium nickel.

The temperature rating of the sprinkler is identified by the 

color of the glass bulb. 

Application 

Quick response sprinklers are used in fixed fire protec-

tion systems:  Wet, Dry, Deluge or Preaction.  Care must be 
exercised that the orifice size, temperature rating, deflector 
style and sprinkler type are in accordance with the latest 
published standards of the National Fire Protection Asso-
ciation or the approving authority having jurisdiction.  Quick 
response sprinklers are intended for installation as specified 
in NFPA 13.

Extended Coverage 

Horizontal Sidewall EC-9

Recessed Extended 

Coverage Horizontal Sidewall 

EC-9

Reviews: