After installation, inspect all sprinklers to ensure that
there is a gap between the cover plate and ceiling and
that the four cup slots are open and free from any air flow
impediment to the space above.
Concealed cover plate/cup assemblies are listed only
for use with specific sprinklers. The use of any other con-
cealed cover plate/cup assembly with the Model F1FR
56 Pendent Sprinkler or the use of the Model CCP Con-
cealed cover plate assembly on any sprinkler with which
it is not specifically listed my prevent good fire protection
and will void all guarantees, warranties, listings and ap-
provals.
Glass bulb sprinklers have orange bulb protectors to
minimize bulb damage during shipping, handling and
installation. REMOVE THIS PROTECTION AT THE TIME
THE SPRINKLER SYSTEM IS PLACED IN SERVICE FOR
FIRE PROTECTION. Removal of the protectors before this
time may leave the bulb vulnerable to damage. RASCO
wrenches are designed to install sprinklers when covers
are in place. REMOVE PROTECTORS BY UNDOING THE
CLASP BY HAND. DO NOT USE TOOLS TO REMOVE
THE PROTECTORS.
Temperature Ratings
Classi
fi
cation
Sprinkler
Temperature
Max. Ambient
Temp.
Bulb Color
°C
°F
Ordinary
Ordinary
Intermediate
Intermediate
High
(1)
57
68
79
93
141
135
155
175
200
286
100°F (38°C)
100°F (38°C)
150°F (66°C)
150°F (66°C)
225°F (107°C)
Orange
Red
Yellow
Green
Blue
(1)
Not available for recessed sprinklers.
Escutcheon Data
(1)
Escutcheon
Model
Approvals
Adjustment
“A”
Dimension
Face of Fitting to
Ceiling or Wall
Dimension
F1
1, 3, 4
Max Recess
Min Recess
1½” (38.1mm)
3
/
4
” (19.1mm)
3
/
16
” -
15
/
16
”
(5mm - 24mm)
F2
1, 2, 3, 4
Max Recess
Min Recess
1 ½” (38.1mm)
1” (25mm)
3
/
16
” -
11
/
16
”
(5mm - 17mm)
FP Push-on/
Thread-off
1, 4
Max Recessed
Min Recessed
7
/
16
” (11mm)
15
/
16
(24mm)
1
1
/
2
” (38.1mm)
1” (25.4mm)
(1)
SIN: RA1435 - cULus and FM permits use with F1 or F2 escutcheons for light
hazard only.
Maintenance
The Models F1FR 56 and F1FR 56 Recessed Sprinklers
should be inspected quarterly and the sprinkler system
maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by using a soft brush or
gentle vacuuming. Remove any sprinkler which has
been painted (other than factory applied) or damaged
in any way. A stock of spare sprinklers should be main-
tained to allow quick replacement of damaged or oper-
ated sprinklers. Prior to installation, sprinklers should be
maintained in the original cartons and packaging to mini-
mize the potential for damage to sprinklers that would
cause improper operation or non-operation.
Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Recessed Pendent
Vertical Sidewall
Horizontal Sidewall
Recessed Horizontal sidewall
Concealed pendent
Finishes
(1)
Standard Finishes
Sprinkler
Escutcheon
Cover plate
Bronze
Chrome Plated
White Polyester
Coated
(4)(5)
Brass
Chrome
Plated
White Painted
Chrome
White
Special Application Finishes
Sprinkler
Escutcheon
Cover plate
Bright Brass
(3)
Black Plated
Black Paint
(2)
Off White
(2)
Satin Chrome
Bright Brass
Black Plated
Black Paint
Off White
Satin Chrome
Bright Brass
Satin
Off White
Black Paint
Black Plated
(1)
Other finishes and colors are available on special order.
Consult the factory for details.
(2)
cULus Listed only.
(3)
200°F (93°C) maximum.
(4)
cULus listed “corrosion resistance” applies to SIN Numbers
RA1425 (Upright) and RA1414 (Pendent) in standard black or white.
(5)
FM Approvals finish as “Polyester coated” applies to SIN Number
RA1414 (Pendent) in standard black or white.
Ordering Information
Specify:
Sprinkler Model
Sprinkler Type
Orifice Size
Deflector Type
Temperature Rating
Sprinkler Finish
Escutcheon Type
Escutcheon Finish (where applicable)
Cover plate Model
Cover plate Thread size
Cover plate Temperature
Cover plate Adjustment
Cover plate Finish
Note:
When Model F1FR 56 Recessed sprinklers are ordered, the
sprinklers and escutcheons are packaged separately.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.