background image

The Reliable Automatic Sprinkler Co., Inc.,

 

103 Fairview Park Drive, Elmsford, New York 10523

Bulletin 151 

Mar
ch 2019

Bulletin 151 

March 2019

Model F1FR QREC CCP
Concealed Quick Response  
Extended Coverage 
Sprinkler

Concealed Quick Response 
Sprinkler Coverage 
to 20’ x 20’ (6.0 m x 6.0 m)

Features

1.  Quick response performance.

2.  Push on, thread off, sturdy convenient 

cover plate.

3.  Factory assembled sprinkler and 

cup, shipped complete with protec-

tive cap.

4.  Sprinkler assembly and cover plate 

separately packaged.

5.  Two Versions:

•  ½” (13mm) Adjustment
•   

5

/

16

” (8mm) Adjustment

6.  Rugged damage resistant assembly. 

No exposed thermal element.

7.  Utilizes the Model F1FR QREC 

Pendent Sprinkler.

8.  Aesthetic ceiling profile.

9.  Standard finishes in white painted or 

chrome plated. Other color-painted 

and specialty finishes available.

For Model F1FR QREC CCP ½” K 5.6 (80) Sprinkler Types 
refer to Bulletin 028 for technical specifications and 
approvals.

Product Description

Model F1FR QREC Quick Response Extended Coverage 

Concealed Sprinkler is an attractive, low profile concealed 
sprinkler assembly.  This sprinkler assembly utilizes a Model 
F1FR QREC pendent sprinkler in a Model CCP cup and push-
on thread-off cover plate assembly. The cup is securely factory 
threaded on the sprinkler’s inlet end. The assembly is shipped 
with a protective cap. The sprinkler and cup are easily installed 
into the sprinkler fitting using the Model GFR2 Sprinkler Wrench.  
The cover plate assembly is attached to the sprinkler cup us-
ing a flexible tooth threaded engagement.  The cover plate is 
attached to the skirt using 135°F (57°C) ordinary temperature 
classification solder.

When the ceiling temperature rises, the solder holding the 

cover plate melts, allowing the release of this part and thus 
exposing the Model F1FR QREC sprinkler inside to the rising 
ambient temperature.  The Temperature rating of the sprinkler 
identified by the color of the glass bulb.

Model F1FR QREC automatic sprinkler utilizes a 3.0 mm fran-

gible glass bulb. This sprinkler has demonstrated response 
times in laboratory tests which are five times faster than stan-
dard response sprinklers. This quick response enables the 
Model F1FR QREC sprinkler to apply water to a fire faster than 
standard sprinklers of the same temperature rating.

Approval Type: 

Quick Response Extended Coverage — Light Hazard

Technical Data:

Nominal 

Orifice

Thread 

Size

K Factor

Approval

Organizations

Sprinkler 

Ident.

Number 

(SIN)

US Metric

17

/

32

” (20mm) ¾” (R¾)  8.0  115.3

1,2,3

R4842

Thread 

Size

Model

Temp. Rating

Max. 

Ceiling 

Temp.

Bulb 

Color

Sprinkler

Cover

¾” NPT 

(R¾)

F1FR 

QREC

135°F 

57°C

135°F 

57°C

100°F 

38°C

Orange

¾” NPT 

(R¾)

F1FR 

QREC

155°F 

68°C

135°F 

57°C

100°F 

38°C

Red

Coverage Area

Flow Rate 

gpm (L/m)

Pressure

psi (bar)

Max. Enclosure Area 

Width x Length

ft. x ft. (m x m)

K=8.0 

(Metric 115.3)

26 (98.4)

33 (125.0)
40 (151.4) 

10.6 (0,7)
17.0 (1,2)
25.0 (1,7)

 16 x 16 (4.9 x 4.9)

18 x 18 (5.5 x 5.5)

20 x 20

(1)

 (6.0 x 6.0)

(1)

(1)

 135°F (57°C) Only

Note:

 1 bar = 100 kPa

Reviews: