Reliable Automatic Sprinkler Co., Inc.,

 103 Fairview Park Drive, Elmsford, New York 10523

Model F1FR – 300 
Quick Response Extended 
Coverage Sprinklers
300 psi (20,7 bar) Rated

Bulle

tin 159 A

ug

ust 2021

Bulletin 159 August 2021

Model F1FR – 300 QREC 
300 psi (20,7 bar) Rated

 

Sprinkler Types

•  Extended Coverage Pendent (QREC)
•  Extended Coverage Horizontal Sidewall 

(QREC-9)

•  Extended Coverage Recessed Pendent 

(QREC)

•  Extended Coverage Recessed Horizontal Side-

wall (QREC-9)

For Model F1FR-300 EC ½” K 5.6 (80) Sprinkler Types refer 

to Bulletin 028 for technical specifications and approvals. 

Approval Organizations

1.  Underwriters Laboratories Inc.
2. 

UL Certified for Canada

3.  NYC MEA 258-93-E

ULI Listing Category

Sprinklers, Automatic & Open
Quick Response Sprinklers

ULI Guide Number

VNIV

Product Description

Reliable Models F1FR-300 QREC and F1FR-300 QREC-9 

pendent and horizontal sidewall sprinklers are high pressure 
rated automatic sprinklers which can handle a maximum 
service pressure of 300 psi (20,7 bar).

These Models are quick response sprinklers which utilize 

a 3.0mm frangible glass bulb.  These sprinklers have dem-

onstrated response times in laboratory tests which are five 

times faster than standard response sprinklers.  This quick 
response enables Model F1FR-300 QREC and QREC-9 

sprinklers to apply water to a fire much faster than standard 

sprinklers of the same temperature rating.

The glass bulb contains an accurately controlled amount 

of special fluid hermetically sealed inside a precisely man-
ufactured glass capsule.  This glass bulb is specially con-
structed to provide fast thermal response.  Other sprinkler 
parts are made of brass, copper or beryllium nickel.

Recessed 

QREC Pendent

QREC-9 Horizontal 

Sidewall

Recessed QREC-9

Horizontal Sidewall

QREC Pendent

At normal temperatures, the glass bulb contains fluid in 

both the liquid and vapor phases.  The vapor phase can be 
seen as a small bubble.  As heat is applied, the liquid ex-
pands, forcing the bubble smaller and smaller as the liquid 
pressure increases.  Continued heating forces the liquid to 
push out against the bulb, causing the glass to shatter, op-
erating the waterway and allowing the deflector to distribute 
the discharging water.

The temperature rating of the sprinkler is identified by the 

color of the glass bulb. 

Application

The most common applications for Model F1FR-300 

QREC and QREC-9 Sprinklers will be in fire protection sys

-

tems for high rise buildings where a quick response rating is 
required and the pressure entering the sprinkler system is in 
excess of 175 psi (12 bar).  The use of these sprinklers will 
provide the opportunity to reduce or eliminate the need for 
pressure reducing valves.