background image

The Reliable Automatic Sprinkler Co., Inc.,

 103 Fairview Park Drive, Elmsford, New York 10523

Model F156 Series

Standard Response

Standard Spray

Bulletin 013 Rev

. G

Bulletin 013 Rev. G

Model F156 Sprinkler Types

Standard Upright
Standard Pendent
Conventional
Vertical Sidewall
Horizontal Sidewall

Model F156 Recessed Sprinkler Types

Pendent/F1/F2/FP
Horizontal Sidewall

Approval Organizations

1.  Underwriters Laboratories Inc. and certified for 

Canada (cULus)

2.  Factory Mutual Approvals (FM)
3.  Loss Prevention Council (LPCB, UK)
4.  VdS Schadenverhütung GmbH

UL Listing Category

Sprinklers, Automatic & Open (VNIV)

Product Description

The F156 Series Glass Bulb Sprinkler combines the 

durability of a standard sprinkler with the attractive low 
profile of a decorative sprinkler. Whether installed on ex-
posed piping or in an office ceiling, it is functional and 
attractive. 

Beautifully versatile is the description for the Reliable 

Model F156 Series Recessed glass bulb sprinkler. Re-
cessing the F156 Series enhances its already low profile 
decorative appearance, and facilitates a rapid and per-
fect installation.

Model F156 Series Recessed escutcheon is highly ad-

justable. The two piece construction makes field installa-
tion a very easy and rapid task. This also allows ceiling 
panels to later be removed without shutting down the fire 
protection system, thus facilitating maintenance of above 
ceiling services.

The F156 Series Automatic Sprinkler utilizes a 5.0 mm 

frangible glass bulb. The glass bulb consists of an ac-
curately controlled amount of special fluid hermetically 
sealed inside of a precisely manufactured glass capsule. 
This glass bulb is specially constructed to provide fast 
thermal response.

At normal temperatures, the glass bulb contains the 

fluid in both the liquid phase and in the vapor phase. The 
vapor phase can be seen as a small bubble. As heat is 
applied, the liquid expands forcing the bubble smaller 

Pendent

Conventional

Recessed

Pendent/F1/F2

Upright

and smaller as the liquid pressure increases. Continued 
heating forces the liquid to push out against the bulb, 
causing the glass to shatter, opening the waterway and 
allowing the deflector to distribute the discharging wa-
ter.

The F156 Series Sprinkler temperature rating is identi-

fied by the color of the glass bulb capsule as well as 
frame color where applicable

Vertical Sidewall

Horizontal Sidewall

Recessed

Horizontal Sidewall

Recessed

Pendent/FP

Summary of Contents for F156 Series

Page 1: ...Series Recessed escutcheon is highly ad justable The two piece construction makes field installa tion a very easy and rapid task This also allows ceiling panels to later be removed without shutting down the fire protection system thus facilitating maintenance of above ceiling services The F156 Series Automatic Sprinkler utilizes a 5 0 mm frangible glass bulb The glass bulb consists of an ac curate...

Page 2: ...2 25 57mm 1 2 3 4 RA1325 2 RA1314 2 3 Conventional Install in Upright or Pendent Position 15mm 1 NPT R 5 6 80 57mm 3 4 RA1375 1 Refer to Bulletin 024 for Special Response Sprinklers F1S5 56 2 cULus Listed corrosion resistant Polyester coated sprinkler 3 Polyester coated FM Approved sprinkler Model F156 Recessed Pendent Sprinkler 1 Installation Wrench Model GFR2 Sprinkler Wrench Installation Data N...

Page 3: ...5 6 8 0 2 25 57mm 1 2 3 RA1385 1 1 LPC Approval is pendent only 57 C through 141 C ratings 2 cULus Listed corrosion resistant Polyester coated sprinkler Model F156 Horizontal Sidewall Sprinkler Deflector HSW Installation Wrench Model D Sprinkler Wrench Installation Data Horizontal Sidewall Nominal Orifice Thread Size Nominal K Factor Sprinkler Height Approval Organizations Sprinkler Identification...

Page 4: ...inkler Type 3 Orifice Size 4 Deflector Type 5 Temperature Rating Specify when ordering Model F156 Pendent Sprinkler 6 Sprinkler Finish 7 Escutcheon Finish where applicable Note When Model F156 Recessed Sprinklers are ordered the sprin klers and escutcheons are packaged separately Escutcheon Data 1 Escutcheon Model Approvals Adjustment A Dimension Face of Fitting to Ceiling or Wall Dimension F1 1 3...