Bulletin 117 

Rev.

 Z

Model F1 LO
K 8.0 (115 metric)
Standard Response
Sprinklers

Model F1 LO Sprinkler

Standard Spray Upright
Standard Spray Pendent
Extended Coverage Pendent
Conventional

Model F1 LO Recessed Sprinkler

Recessed Standard Spray Pendent
Recessed Extended Coverage Pendent

For Model F1 ½” K 5.6 (80), 4.2 (60) & 2.8 (40) Sprinkler 
Types refer to Bulletin 013, 024 or 027 for technical speci-
fications and approvals.

Approval Organizations

1.  Underwriters Laboratories Inc. (UL)
2.  Underwriters’ Laboratories of Canada (ULC)
3.  Factory Mutual Approvals (FM)
4.  Loss Prevention Council (LPCB, UK)
5.  VdS Schadenverhütung Gmbh
6.  EC Certificate: 1438-CPD-0041 (R1712)

  

 

     1438-CPD-0040 (R1722)

UL Listing Category

Sprinklers, Automatic & Open (VNIV)

Product Description

Model F1 LO series sprinklers are K8.0 (115) standard-

response sprinklers with a glass bulb operating element. 
The  sprinklers  use  a  compact  frame  for  a  low-profile, 
decorative  appearance.  Model  F1  LO  series  sprinklers 
are  available  in  a  variety  of  finishes  as  indicated  in  the 
Finishes table in this Bulletin. 

Standard spray Model F1 LO sprinklers are available in 

pendent, recessed pendent, and upright configurations. 
Extended  coverage  pendent  and  recessed  pendent 
Model F1 LO sprinklers are available for modifications or 
additions to existing light hazard sprinkler systems with 
standard-response sprinklers as well as for replacement 
of  individual  standard-response  sprinklers  in  existing 
light hazard sprinkler systems. A conventional (old-style) 
Model F1 LO sprinkler is also available. Refer to the In-
stallation Data in this Bulletin for additional information on 
each specific Model F1 LO sprinkler.

Model F1 LO sprinklers are available in a range of tem-

perature ratings as indicated in the Temperature Ratings 
table in this Bulletin, which may be modified by the Instal-
lation Data for each specific model. 

Upright

Model F1 LO & F1 LO Recessed Sprinklers

Application

Model F1 LO and F1 LO Recessed sprinklers are used in 

fixed fire protection systems: Wet, Dry, Deluge or Preaction. 
Care must exercised that the orifice size, temperature rat-
ing, deflector style and sprinkler type are in accordance with 
the latest published standards of the National Fire Protection 
Association or the approving Authority Having Jurisdiction.

Pendent

Conventional

Recessed Pendent

Extended Coverage 

Pendent

Recessed Extended 

Coverage Pendent