background image

Reliable Automatic Sprinkler Co., Inc.,

 

103 Fairview Park Drive, Elmsford, New York 10523

Model DDX-LP PrePak System
2” (50mm), 2

1

/

2

” (65mm),

3” (80mm), 4” (100mm),
6” (150mm) & 8” (200mm)

Bulletin 748 July 2019

Bulletin 748 July 2019

Instructions for 
Installation, Operation,
Care and Maintenance

Low Pressure Dry-Pipe System
10 psi - 26 psi (0.7 bar - 1.8 bar)
Recommended System Pressure

General Description 

The Reliable Model DDX-LP PrePak (Sizes 2” (50mm), 

2½” (65 mm), 3” (80 mm), 4” (100 mm), 6” (150mm) and 
8” (200mm)) is a completely self-contained, supervised dry 
pipe system that can be readily installed within a floor space 
of less than 7 square feet (0.65 square meters). Refer to Fig. 
1 for cabinet dimensions. Installation of the DDX-LP PrePak 
requires just three piping connections: the water supply, the 
sprinkler system and the drain. Reference locations of these 
piping connections are shown in Fig. 1. One electrical sup-
ply connection is required.

 Note:

 The Model DDX-LP PrePak 

is available with an optional 115V VAC (60Hz) air compres-
sor.

Full assembly drawings for the units are available on the 

Reliable Automatic Sprinkler Company website (www.reli-
ablesprinkler.com).

The heart of the Reliable Model DDX-LP PrePak is the 

Model DDX-LP Dry Pipe Valve. The Reliable Model DDX-LP 
Dry Pipe Valve is a hydraulically operated, differential-type 
valve designed for use as a primary control valve in a low 
pressure dry pipe valve system. The trim set used with the 
Model DDX-LP Dry Pipe Valve contains the Reliable Model 
LP Dry Pilot Actuator releasing device. This Actuator allows 
the system air or nitrogen pressure to be considerably less 
than the water supply pressure (see Table A). The following 
benefits are a direct result of lower air pressure:
1.  In refrigerated area systems, lower air pressure de-

creases the possibility of ice plugs that could impede 
or prevent the flow of water to fire sprinkler heads in 
the event of fire.

2.  Lower air pressure allows for smaller capacity, lower 

cost dehydration equipment, where required.

3.  Lower air or nitrogen pressure can reduce water de-

livery time when the system actuates, and in some 
cases, may eliminate the need for an accelerator.

4.  For systems supplied with nitrogen, low supervisory 

pressure reduces the quantity of nitrogen required to 
maintain  the system pressure.

Note: Photograph is for illustrative purposes only.

Summary of Contents for DDX-LP PrePak

Page 1: ...le Automatic Sprinkler Company website www reli ablesprinkler com The heart of the Reliable Model DDX LP PrePak is the Model DDX LP Dry Pipe Valve The Reliable Model DDX LP Dry Pipe Valve is a hydraulically operated differential type valve designed for use as a primary control valve in a low pressure dry pipe valve system The trim set used with the Model DDX LP Dry Pipe Valve contains the Reliable...

Page 2: ...mm 32 8 ft 17 7 m 6 150 mm 54 7 ft 21 8 m 8 200 mm 79 3 ft 24 2 m The equivalent length in the table above includes the Model DDX LP PrePak valve supply manifold tee sup ply side control valve and the section of pipe above the Model DDX LP PrePak valve 3 Shipping Weight System Size Weight 2 50 mm 2 65 mm 3 80 mm 554 lb 252 kg 4 100 mm 710 lbs 322 kg 6 150 mm 800 lbs 363 kg 8 200mm 1350 lbs 531kg 4...

Page 3: ...3 Fig 1 ...

Page 4: ...rotected area The air supply sys tem must be carefully designed to prevent plugging by frost deposits Special requirements such as those in FME R s Installation Guidelines for Refrigerated Storage may need to be incorporated Nitrogen used in refrigerated area systems minimizes the possibility of ice build up and blockage inside the system piping that could inhibit proper system operation The dew p...

Page 5: ...nk to drain any condensate ac cumulation Reliable Technical Bulletins 338 and 519 pro vide additional information for maintaining the Model DDX LP PrePak Deluge Valve System Setup Refer to Figure 2 1 Close the main valve controlling water supply to the Model DDX LP PrePak deluge valve Also close the two valves supplying air or nitrogen to the system 2 Close the pushrod chamber supply valve 3 Open ...

Page 6: ...r and Model B Manual Emergency Sta tion for leakage Also verify that tubing drain lines from releasing devices are not pinched or crushed which could prevent proper releasing of the deluge valve 7 Testing alarms Open the alarm test valve permit ting water from the supply to flow to the alarm pressure switch and to the mechanical sprinkler alarm if pres ent After testing close this valve completely...

Page 7: ...Fig 2 7 Model DDX LP Low Pressure Dry Pipe System Valve Legend Note Some items omitted for clarity ...

Page 8: ...8 Fig 3 ...

Page 9: ...9 Fig 4 ...

Page 10: ...e P N are required to be 0 None 2 Not Used 3 Air Compressor sizing may differ if specified sprinkler system has an uncommon volume capacity DDX LP PrePak Valve Size System Side Control Valve U Trim Type 3 Solenoid Valve 0 Releasing Control Panel 0 Air Compressor 3 Y System Air Devices Z 2 2 0 None 0 None 0 None 0 None 0 2 1 2 1 1 2 HP 115 VAC systems up to 3 in size 1 Nitrogen Supply Kit 3 3 3 Pre...

Reviews: