![Reliable AH42 Bulletin Download Page 24](http://html1.mh-extra.com/html/reliable/ah42/ah42_bulletin_1435942024.webp)
Installation Orientation
Figure 29
Model DD Series
Install Model DD Series sprinklers with the
deflector parallel to the
floor
and arrows on deflector pointing down the roof slope in both
directions.
Model DS56
Install Model DS56 sprinklers with the
frame arms perpendicular
to the roof deck (parallel with lower eave)
and the arrow on the
deflector pointing down the roof slope.
I
nstall Model GP56 sprinklers with the
deflector parallel
to the roof deck
and the arrow on the deflector pointing
down the roof slope. Install Model AH Series sprinklers
with the deflector parallel to the roof, and
frame arms
parallel with the lower eave of the protected space.
Model GP56 and AH Series
Installation
Install Reliable Attic Sprinklers only in the orientation indicated in Figure 28. Figure 29 provides additional select installation
criteria for each sprinkler model.
Figure 30
Model DD Series
Model DS56
Model GP56
Model AH42/AH56
Installation Dimensions
Bulletin 056
February 2020
Page 24 of 27
www.reliablesprinkler.com