8.3 Diagnostic messages
Diagnostic reports can be output over sub-index 2 of Object 2005h
Diagnostic. The corresponding diagnostic bit is erased if the fault does no longer exist.
Message
Remedy
Bit 2
2
= 1,
internal hardware
communication error
- Check wiring
- Try to restart the device: Voltage OFF/ON.
If the message occurs repeatly, the measuring system must be replaced.
Bit 2
5
= 1,
internal Communication
error (CRC)
- Check wiring
- Try to restart the device: Voltage OFF/ON.
If the message occurs repeatly, the measuring system must be replaced.
Bit 2
6
= 1,
Wrong measuring range
detected
- Try to restart the device: Voltage OFF/ON.
If the message occurs repeatly, the measuring system must be replaced.
8.4 Miscellaneous faults
Fault
Cause
Solution
Position jumps
by the measuring
system
Strong vibrations
Vibrations, impacts and shocks, e.g. on presses, are
dampened with so-called "shock modules". If the error
occurs repeatedly despite these measures, the measuring
system must be replaced.
Electrical faults
EMC
Isolated flanges and couplings made of plastic may help
against electrical faults, as well as cables with twisted pair
wires for data and supply. The shielding and line routing
must be executed in accordance with the Equipment
Mounting Directives for the respective field bus system.
Table 8: Miscellaneous faults