Parameterization
TR-Electronic GmbH 2013, All Rights Reserved
Printed in the Federal Republic of Germany
Page 146 of 175
TR - ECE - BA - DGB - 0102 - 09
01/17/2019
7.4.3.30
Attribute 104, Preset Value Extended (≤ 64 bit)
Danger of physical injury and damage to property due to an actual value
jump during execution of the preset adjustment function!
The preset adjustment function should only be executed when the
measuring system is stationary, or the resulting actual value jump must be
permitted by both the program and the application!
Preset Value Extended
is used to set the measuring system value to any position
value within the range of 0 to measuring length in increments
–1.
The output position value is set to the
Preset value Extended
parameter, if the
Set_Attribute_Single
service is executed to this attribute.
ULINT
Preset value
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
2
7
- 2
0
2
15
- 2
8
2
23
- 2
16
2
31
- 2
24
2
39
- 2
32
2
47
- 2
40
2
55
- 2
48
2
63
- 2
56
Access
Set / Get
Lower limit
0
Upper limit
Value within the range from 0 to programmed
measuring length in steps
– 1
Default
0
Connection path,
Packed EPATH
with 8 bit class
0x20
0x23
0x24
0x01
0x30
0x68
Logical Type
= Class
Class #23
Logical Type
= Instance
Instance #1
Logical Type
=Attr.-ID
Attr.-ID #104
This attribute is immediately active and saved.
In order to ensure a safe acceptance of the instance attributes
●
12, Direction Counting Toggle
●
101, Total Measuring Range
●
102, Number of Revolutions - numerator and
●
103, Number of Revolutions - divisor
changes must be first taken over or saved by means of Attribute 112
Accept
Parameter
or the service code 0x16
Save
. In a further step the new
Preset
value
can be written.