16
REGULUS - TRS 5 Controller - www.regulus.eu
Operating mode
menu 4
F 4 - Operating mode
Menu
„4. Operating mode”
is used to specify the
operating modes for the heating circuit.
After an interruption of the mains voltage the
controller automatically returns to the last operating
mode selected!
The menu is closed by pressing
„esc”
or selecting
„Exit operating mode”
.
The controller works with the set operating
times and the corresponding different
reference
fl
ow temperature values only in
the automatic mode.
F 4.1 - Heating circuit
menu 4.1
Auto
= Automatic/Normal mode using the set times.
Continuous Day
= The set values for day mode are used.
Continuous Night
= The set values for night mode are used.
Reference value
= Fixed
fl
ow temperature regardless of the outdoor temperature. The desired
fl
ow
temperature has to be set in Menu 4.3.
14 day reference value
= Speci
fi
c
fi
xed
fl
ow temperatures can be set for the next 14 days in menu 4.4.
After 14 days, the reference temperature of the 14th day is used until the operating mode is changed.
Off.
= Heating circuit is switched off (except Frost protection)
Setting range:
Auto, Continuous day, Continuous night, Reference value, 14 day reference, Off
Default: Automatic
F 4.2 - Manual
menu 4.2
In Manual mode the individual relay outputs and the connected consumers can be checked for proper
functioning and correct assignment.
The operating mode
„Manual”
may only be used by specialists for brief function tests, e.g. during
commissioning.
Function in manual mode:
The relays and thus the connected consumer are switched on and off by pressing a key, with no regard to the
current temperatures and the parameters which have been set. At the same time, the current measurement
values of temperature sensors are also shown in the display for the purposes of function control.
F 4.3 - Heating circuit reference
menu 4.3
If operating mode
„Reference value”
is selected, (Menu 4.1), the reference
fl
ow temperature has to be set
here, regardless of the curve or outdoor temperature.
Setting range: 10
°C to 75
°C
Default: 30
°C
F 4.4 - 14 day reference
menu 4.4
If operating mode
„14 day reference value”
is selected (Menu 4.1), the reference
fl
ow temperature for each
of the 14 days can be set here.
In the
fi
rst menu 4.4.1 the starting time of the program is shown. To start the program, press restart.
Pressing
„restart”
again will reset the 14 day reference program and start it at day 1.
F 4.5 - Domestic hot water
menu 4.5
The domestic hot water heating can be activated here.
„Auto”
makes use of the times set in the
„times”
menu (see 3.4),
„On”
activates continuously, and
„Off”
switches the DHW heating off.
Setting range: Auto, On, Off
Default: Auto
Danger
Danger