Operating mode 

menu 4

F 4 - Operating mode

Menu 

„4. Operating mode”

 is used to specify the 

operating modes for the heating circuit.
After an interruption of the mains voltage the 
controller automatically returns to the last operating 
mode selected!

The menu is closed by pressing 

„esc”

 or selecting 

„Exit operating mode”

.

The controller works with the set operating 
times and the corresponding different 
reference 

fl

ow temperature values only in 

the automatic mode.

F 4.1 - Heating circuit 

 

 

 

menu 4.1

Auto

 = Automatic/Normal mode using the set times.

Continuous Day

 = The set values for day mode are used.

Continuous Night

 = The set values for night mode are used.

Reference value

 = Fixed 

fl

ow temperature regardless of the outdoor temperature. The desired 

fl

ow 

temperature has to be set in Menu 4.3.

14 day reference value

 = Speci

fi

fi

xed 

fl

ow temperatures can be set for the next 14 days in menu 4.4. 

After 14 days, the reference temperature of the 14th day is used until the operating mode is changed.

Off.

 = Heating circuit is switched off (except Frost protection)

Setting range:
Auto, Continuous day, Continuous night, Reference value, 14 day reference, Off
Default: Automatic

F 4.2 - Manual 

 

 

 

 

menu 4.2

In Manual mode the individual relay outputs and the connected consumers can be checked for proper 
functioning and correct assignment.

The operating mode 

„Manual”

 may only be used by specialists for brief function tests, e.g. during 

commissioning.

Function in manual mode:
The relays and thus the connected consumer are switched on and off by pressing a key, with no regard to the 
current temperatures and the parameters which have been set. At the same time, the current measurement 
values of temperature sensors are also shown in the display for the purposes of function control.

F 4.3 - Heating circuit reference   

 

menu 4.3

If operating mode 

„Reference value”

 is selected, (Menu 4.1), the reference 

fl

ow temperature has to be set 

here, regardless of the curve or outdoor temperature.

Setting range: 10

°C to 75

°C

Default: 30

°C

F 4.4 - 14 day reference   

 

 

menu 4.4

If operating mode 

„14 day reference value”

 is selected (Menu 4.1), the reference 

fl

ow temperature for each 

of the 14 days can be set here.
In the 

fi

rst menu 4.4.1 the starting time of the program is shown. To start the program, press restart.

Pressing 

„restart”

 again will reset the 14 day reference program and start it at day 1.

F 4.5 - Domestic hot water 

 

 

menu 4.5

The domestic hot water heating can be activated here. 

„Auto”

 makes use of the times set in the 

„times”

 

menu (see 3.4), 

„On”

 activates continuously, and 

„Off”

 switches the DHW heating off.

Setting range: Auto, On, Off
Default: Auto

Danger

Danger

Summary of Contents for TRS 5

Page 1: ...TRS 5 Controller EN v 1 1 Installation wiring and operating instructions...

Page 2: ...devices to be provided by the customer e g a safety valve air vent valve etc The installation shall be done by a qualified specialist who is trained accordingly For the user Make sure that the specia...

Page 3: ...s E Controller Use E 1 Display and input 10 E 2 Menu sequence and menu structure 11 E 3 Commissioning help setup wizard 12 E 4 Free commissioning 12 F Parameter Setting F 1 Measurements 13 F 2 Statist...

Page 4: ...ontroller operation max 85 rel humidity at 25 C for transport storage no moisture condensation permitted Other specifications and dimensions Housing design 2 part ABS plastic Installation method wall...

Page 5: ...by means of statistical graphics extensive menus with interactive explanations menu lock can be activated to prevent unintentional setting changes usual preset parameters in factory setting A 3 Scope...

Page 6: ...nts may be mandatory such as check valves non return valves safety temperature limiters scalding protectors etc and must therefore be provided 1 Mixed heating circuit with accumulation tank 2 Mixed he...

Page 7: ...hen doing so 4 Hold the lower part of the housing up to the selected position and mark the 3 mounting holes Make sure that the wall surface is as even as possible so that the housing does not become d...

Page 8: ...g with a screwdriver Fig C 2 1 and wire the cables following the diagrams in section D 5 Lock the housing lid onto the top margin of its bottom counterpart push the cables inside and close the housing...

Page 9: ...tional expansion Z2 optional expansion Use terminal block S for connecting the sensor earths of S1 S6 The polarity is freely selectable The sensors S3 S6 are optional depending on the hydraulic varian...

Page 10: ...ey 3 is used to cancel an entry or to exit a menu If applicable there will be a request for confirmation as to whether the changes which have been made should be saved The function of each of the othe...

Page 11: ...ol of the system with operating hours etc 3 Operating times for heating circuit and DHW setting the clock 4 Operating times for heating circuit and DHW manual mode 5 Set parameters for the heating cir...

Page 12: ...step to the selection mode thus cancelling the commissioning help Finally menu 4 2 under operating mode Manual should be used to test the switch outputs with the consumers connected and to check the...

Page 13: ...Overview or esc exits the Info mode If Error appears on the display instead of the measurement value then there may be a defective temperature sensor or its wiring If the cables are too long or the se...

Page 14: ...the unit of time and the two left buttons scroll through the diagram F 2 2 28 days Menu 2 2 flow temperature during the last 28 days In the graphical overview the characteristics of the outdoor and fl...

Page 15: ...which the heating circuit is supplied with an increased comfort temperature e g for quick heating in the morning Setting range One time range for each day of the week Default Mo Su off Note See 5 for...

Page 16: ...ual mode the individual relay outputs and the connected consumers can be checked for proper functioning and correct assignment The operating mode Manual may only be used by specialists for brief funct...

Page 17: ...l straight curve Setting simple or a split curve Setting split that is divided into 2 parts by a split point The straight curve can be set easily using one parameter The characteristic curve for the s...

Page 18: ...erature in nighttime operation that is by 7 C below that of daytime operation Setting range from 30 C to 30 C Default 2 C F 5 6 Comfort temperature boost menu 5 6 paraleln posun k ivky The comfort tem...

Page 19: ...C F 6 2 DHW Setpoint menu 6 2 Minimum domestic hot water temperature If the temperature at the DHW sensor S3 drops below the temperature set here and the DHW charging is enabled the DHW charging rela...

Page 20: ...ure of the heating circuit Should the heating circuit temperature exceed this value the heating circuit is switched off until the temperature drops below This feature is used e g to protect underfloor...

Page 21: ...d Pressing the esc more than once takes you back step by step to the selection mode thus cancelling the commissioning help see also E3 May only be started by a specialist during commissioning Observe...

Page 22: ...in the room temperature has on the reference flow temperature For every degree of deviation of the room temperature from the reference room temperature the percentage of the calculated reference flow...

Page 23: ...closed by pressing esc or selecting Exit menu lock The menus listed below remain completely accessible despite the menu lock being activated and can be used to make adjustments if necessary F 1 Measur...

Page 24: ...e following table The menu can be closed at any time by pressing esc Caution 10 1 10 31 10 2 10 32 10 3 10 33 10 4 10 34 10 5 10 35 10 6 10 36 10 7 10 37 10 8 10 38 10 9 10 39 10 10 10 40 10 11 10 41...

Page 25: ...egulus eu Language menu 11 F 11 Language Menu 11 Language can be used to select the language for the menu guidance This is queried automatically during initial commissioning Language selection is not...

Page 26: ...hes To obtain more detailed information on the error press the key under the warning or info symbol Do not try to deal with this yourself Consult a specialist in the event of an error Possible error m...

Page 27: ...d fuse and check it Exchange the defective fuse for a new one locate the external source of the error e g pump and exchange it Then first recommission the controller and check the function of the swit...

Page 28: ...rd any analyses and data that are particularly important to you at regular intervals see 7 IMPORTANT INFORMATION ON DISPOSAL IN COMPLIANCE WITH THE EUROPEAN DIRECTIVE 2002 96 EC European Directive 200...

Reviews: