Regulus RGMAT E G60 Installation And Operation Manual Download Page 2

1. Introduction

RegulusRGMAT E G60 Load Unit makes boiler installation quicker as it contains all important 

components needed for boiler circuit circulation and boiler protection against low-temperature corrosion. 

It is designed to be installed directly on a boiler return piping. The min. distance of the pipe axis from a 

wall is 100 mm to enable insulation removal if needed. 

This Load Unit is intended for hydronic fireplaces and solid-fuel boilers.

2. RGMAT E G60 Description

RGMAT E G60 keeps the temperature at the boiler inlet above the flue gas condensation temperatures, 

which prevents so called low-temperature corrosion of the boiler combustion chamber. This limits con-

densation and boiler tarring significantly, the efficiency of fuel combustion increases and service life of 

the boiler is extended.  

Main Features

Function

maintaining a minimum inlet temperature into a boiler (fireplace) through a load 

valve

Application

Load Unit for solid-fuel boilers and fireplaces; it prevents low-temperature 

corrosion and boiler (fire) fouling

Description

consists of a UPM3 FLEX AS pump, ball valves with union nuts, TSV3B valve 

(with automatic bypass balancing), thermometer, insulation 

Working fluid

water; water/glycol mixture (max. 1:1) or water/glycerine mix-ture (max. 2:1)

Installation

on boiler return piping, min. distance of the pipe axis from a wall is 100 mm

RGMAT E G60 Technical Data

Fluid working temperature

5 - 95 °C

Max. working pressure

6 bar

Min. working pressure

0.5 bar

Max. ambient temperature

5 - 40 °C

Max. relative humidity

80 %, non condensing

Load valve control range

t

valve,opening

 +5 °C

Valve Kvs (A→AB direction) 

6.2 m

3

/h

Valve Kvs (B→AB direction) 

4.4 m

3

/h

Power supply

230 V, 50 Hz

Insulation material

EPP RG 60 g/l

Overall dimensions

325 x 140 x 220 mm

Total weight

3.25 kg

Connections

3x G 1" F

Accessories

Bypass with float non-return valve

code 16126

Codes

max. boiler output

19083

 for opening temperature 45 °C

max. 46 kW 

19090

 for opening temperature 50 °C

max. 42 kW 

19086

 for opening temperature 55 °C

max. 36 kW 

19092

 for opening temperature 60 °C

max. 32 kW 

19089

 for opening temperature 65 °C

max. 26 kW 

19091

 for opening temperature 70 °C

max. 22 kW 

Summary of Contents for RGMAT E G60

Page 1: ...www regulus eu RGMAT E G60 RGMAT E G60 EN Installation and Operation Manual RegulusRGMAT E G60 LOAD UNIT with UPM 3 insulated for heating systems...

Page 2: ...es it prevents low temperature corrosion and boiler fire fouling Description consists of a UPM3 FLEX AS pump ball valves with union nuts TSV3B valve with automatic bypass balancing thermometer insulat...

Page 3: ...may hinder or even disable its operation Always respect valid rules and boiler manufacturer s data during installation Possible Connection Example I The diagram shows a typical connection of a solid...

Page 4: ...nlet limiting so the hot water flow coming from the bypass till its complete tight closure Thanks to this no balancing valve is needed The load valve is made of brass element and plug seals are in EPD...

Page 5: ...t needed Pump control The circulation pump can be controlled by an external PWM signal profile for use in heating systems or without a PWM signal by selecting a pump performance curve A maximum curve...

Page 6: ...n the pump runs at factory settings or the last setting The display shows the current pump performance Setting selection for UPM3 To select your desired setting press the button repeatedly until you f...

Page 7: ...Pump wiring socket for power supply A and signal transmission B power supply A and signal B connectors N brown L brown PE yellow green PWM GDN blue PWM out black PWM in brown Permissible positions...

Page 8: ...iping or horizontally to the left of a boiler When being installed horizontally to the left of a boiler the Load Unit needs to be turned by 180 and the TSV3B valve turned as shown in the pics below 20...

Reviews: