STORAGE WATER HEATERS

R2BC 200, R2BC 300, R2BC 400,

R2BC 500, R2BC 750, R2BC 1000,

R2BC 1500, R2BC 2000, R2BC 2500, R2BC 3000

EN

v. 1.6

Owners Manual

Summary of Contents for R2BC 1000

Page 1: ...STORAGE WATER HEATERS R2BC 200 R2BC 300 R2BC 400 R2BC 500 R2BC 750 R2BC 1000 R2BC 1500 R2BC 2000 R2BC 2500 R2BC 3000 EN v 1 6 Owners Manual ...

Page 2: ...4 Connection points on the tank 3 1 5 Packing 3 2 General Information 3 3 Technical Data and Dimensions of R2BC Models 4 4 Operation 5 5 Examples of Assigning Connection Points 5 6 Installation and Commissioning 7 7 Tank s Insulation 8 8 Maintenance Replacement of Magnesium Anode Bar 9 9 Disposal 9 10 Warranty 9 11 Recommended Accessories 9 ...

Page 3: ...thick with a white PVC surface Tanks of 750 and 1000 l volume are supplied with a hard polyurethane insulation 75 mm thick with a white leatherette surface Tanks of 1500 2000 2500 and 3000 l volume have the insulation 100 mm thick The insulation can be detached for easier handling 1 4 Connection points on the tank 4 lateral with G 5 4 inner thread to the heating coils 2 lateral with G 5 4 inner th...

Page 4: ... 4 5 4 8 5 2 Empty weight kg g 96 124 150 168 270 285 302 465 543 600 DHW heating t 35 C 80 60 10 45 upper coil l h kW h 680 27 7 760 31 1 760 31 1 760 31 1 2000 81 3 2090 84 7 1850 75 2170 88 2612 106 2744 112 DHW heating t 35 C 80 60 10 45 lower coil l h kW i 680 27 7 1280 51 9 1620 65 8 1620 65 8 2000 81 3 2090 84 7 3138 128 3362 137 3552 145 3885 158 Dimensions mm A 1265 1710 1690 1780 1870 21...

Page 5: ...ample III with a heat pump 1 magnesium anode magnesium anode magnesium anode 2 thermometer thermometer thermometer 3 plug electric heating rod electric heating rod 4 cold water inlet cold water inlet cold water inlet 5 outlet to a solar system outlet to a solar system return line to a heat pump 6 temperature probe thermostat temperature probe thermostat temperature probe thermostat 7 inlet from a ...

Page 6: ...iler solar system and accumulation tank Example III With a heat pump solar system and non regulated solid fuel source DHW cold water recirculation boiler PS R2BC E E T bb bbb B bbb DHW cold water recirculation R2BC HEAT PUMP EcoAir E E T bb bbb B bbb fireplace accumulation accumulation ...

Page 7: ...ar a reduc ing valve is necessary In order to prevent water loss an expansion tank should be installed at the cold water inlet as well 8 l volume for R2BC 200 12 l volume for R2BC 300 and 400 18 l volume for R2BC 500 24 l vol ume for R2BC 750 35 l volume for R2BC 1000 60 l volume for R2BC 1500 80 l volume for R2BC 2000 100 l volume for R2BC 2500 and 2 60 l volume for R2BC 3000 Should the water be ...

Page 8: ...nks that prevents heat losses Thermal insulation of hard polyurethane foam with zipped PVC layer is used Warning Insulation dismantling and installation shall be done in two or three persons depending on the tank size The hard foam insulation with zipper must not be dismantled installed at temperatures below 20 C If this can not be avoided the insulation shall be pre warmed in another room to at l...

Page 9: ...t be claimed 9 Disposal Packing shall be disposed of in compliance with the valid rules When the product reaches the end of its life it shall not be disposed of as household waste It shall be dropped off at a Local Waste Recycling Center Insu lation shall be recycled as plastic and the steel vessel as scrap iron 10 Warranty This product is covered by warranty according to the conditions described ...

Page 10: ...ounting flange for the inspection hole Electric heating rods can be used in storage water heaters and in accumulation tanks They can be power supplied either by 230V or 3 230V 400V Heating rods of output 2 12 kW can be installed into these tanks into the sleeves with G 6 4 inner thread the right type should be selected with respect to its length and the tank diameter Electric heating rods are curr...

Page 11: ...ous sediments This well balanced mixture of corrosion inhibitors and protective film creating compounds ensures a max protection of underfloor heating and solar panel circuits MR 501 R 1kg Concentrated alkaline anti corrosion liquid removing scale and calcareous sediments from heating systems It dissolves scale and rust and makes it possible to remove them by flushing the system 2 liters of MR 501...

Page 12: ...itions set by this Manual are maintained and installation is done by an authorized person confirmed in the Warranty Certificate 4 The claimed defect must not be caused by tampering improper installation and operation using the product for other purposes than intended placing the product in improper environment or by a natural disaster 5 Claims shall be settled by your dealer at the address shown b...