10.  Now insert the green terminal block into the module. Try to push the terminal block with slight 

 

 pressure.

11. 

Insert the remaining wires IR-L M1, N M1 and PE M1 into the upper terminal block. N M1 into 

 

 

the  terminal  under  the  N  label,  IR-L  M1  into  the  L2IR  terminal  and  PE  M1  into  the 

 

 

yellow-green PE terminal. In the picture, the corresponding holes are marked in white. After 

 

 

inserting the conductor into the terminal, make sure that the conductor is firmly connected to 

 

 

the terminal by pulling on the conductors (white holes in the picture, for inserting the conductors).

12.  Insert all wires into the cable duct and cover it.

13.  Visually inspect the entire installation and only after that you may start the RegulusBOX.