background image

INSTRUCTION

 

i

Read this instruction before installation 

and wiring of the product

RVAN10-24

Valve actuator for 3-point control

RVAN10-24 is a valve actuator designed for control of Regin valves. 
For more info, see the product sheet of each valve. The actuator can 
also be combined with other brands of valves using adapter kits. The 
actuator can be operated manually.

Technical data

Supply voltage 

 

24 V AC ±15 %, 50/60 Hz 

Control signal 

 

3-point 

Max. power consumption  6.2 W / 6.7 VA 
Stroke 

 

10...30 mm 

Stroke time 

 

3 s/mm 

Force 

 

1000 N 

Ambient temperature 

0...50°C 

Storage temperature 

-40...80°C 

Ambient humidity   

10...90 % RH 

Dimensions 

 

198 x 266 x 133 mm 

Protection class   

IP54

Installation

If the valve stem adaptor and valve throat adaptor are not already mount-
ed on the valve, mount them. Pull the valve stem out as far as possible. 
Remove the locking bolt (U-bolt) from the actuator yoke. Insert the valve 
stem into the yoke and make sure that the stem adaptor engages the hole 
in the angled iron of the actuator drive spindle.
The groove in the valve throat adaptor must be made to line up with the 
U-bolt mounting holes on the actuator. If the spindle needs moving in or 
out for this to happen, depress the central part of the manual button and 
turn it clockwise for the actuator spindle to extend, and anti-clockwise for 
it to retract (see Manual override). When the valve is in the correct posi-

tion, insert the U-bolt. Tighten the bolt nuts until the valve is firmly gripped. 

Disassembly in reverse order.

Mounting positions

90º

90º

Wiring

24 V AC

1

2

3

1

2

3

G2 G1

G1 closed = Actuator spindle extending

G2 closed = Actuator spindle retracting

 

Stroke and end position calibration

Stroke and end position calibration is not necessary due to a construction 
utilizing end position stops. When the valve reaches the end position, a 
force is generated.

 Once the force of the actuator reaches a predefined 

level, the limit switch automatically halts the drive motor.

Manual override

To manually set the valve position, first depress the central part of 
the button until it clicks and remains depressed (1 in the figure). This 

disengages the gears and also cuts the power to the motor. Then the 
valve position can be changed manually by turning the button (2 in 

the figure). Clockwise rotation will extend the drive rod and anti-clock

-

wise will retract it. 

To reconnect power, set the button so the flats are in line with the 

cutout in the edge of the cover, Auto position. Then press on the outer 

parts of the button (3 in the figure). The central depressed part will 

pop out re-engaging the gears and reconnecting the power.

This product carries the CE-mark. More information is available at 
www.regincontrols.com. 

Contact

AB Regin, Box 116, 428 22 Kållered, Sweden 
Tel: +46 31 720 02 00, Fax: +46 31 720 02 50 
www.regincontrols.com, [email protected]

RVAN10-24

10571D

 

MA

Y 18

EN

1