The Occupancy button

If you press the Occupancy button for less than 5 seconds 
when the controller is in the preset operating mode, the 
controller changes to operating mode Bypass. If you press 
the button for less than 5 seconds when the controller 
is in Bypass, it changes operating mode to the preset 
operating mode.
When the Occupancy button is held depressed for more 
than 5 seconds, the controller changes operating mode to 
Unoccupied, regardless of the current operating mode. If 
you press the Occupancy button for less than 5 seconds 
in Unoccupied, the controller returns to Bypass.

Forced ventilation

Regio has a built-in function for forced ventilation. 
A short press on the Occupancy button activates the 
output that has been configured for forced ventilation, for 
example for a damper.

Setpoint

In Occupied mode, the controller operates from a heating 
setpoint (FS=22°C) or a cooling setpoint (FS=24°C) that 
can be changed centrally or locally using the dipswitches 
on RU-FO. 
The setpoint can be adjusted up and down  
(FS=+/-3°C) with the knob on the front of the room unit. 
Switching between heating and cooling setpoints is done 
automatically in the controller depending on the heating 
and cooling requirement.

Indications

The room unit has an LED shaped like a thermometer on 
the front. A red indication is shown when heating control 
is functional and a blue indication when cooling control is 
active. No LED indication shows that neither heating nor 
cooling control is active.

Fan control

RU-FO has a fan switch with the following positions:
Auto 

Automatic control of the fan speed to maintain  

 

desired room temperature. 

Fan off. 

Manual position with low speed. 

II 

Manual position with medium speed. 

III 

Manual position with high speed.

In operating modes Off and Unoccupied, the fan is 
stopped, regardless of the position of the fan switch. 

Summary of Contents for RU-FO

Page 1: ...ely programmable controllers with communication Applications The Regio controllers are suitable in buildings where you want optimal comfort and low energy consumption for example offices schools shopping centres airports hotels and hospitals etc Design The room units have a modern design The design has been awarded the 2007 iF product design award Sensor The room unit has a built in sensor Easy to...

Page 2: ... Occupied mode the controller operates from a heating setpoint FS 22 C or a cooling setpoint FS 24 C that can be changed centrally or locally using the dipswitches on RU FO The setpoint can be adjusted up and down FS 3 C with the knob on the front of the room unit Switching between heating and cooling setpoints is done automatically in the controller depending on the heating and cooling requiremen...

Page 3: ...ength 10 m This product conforms with the requirements of European EMC standards CENELEC EN 61000 6 1 and EN 61000 6 3 and the requirements of European LVD standard IEC 60 730 1 It carries the CE mark Inputs and outputs In RCP Terminal blocks in RCP So called lift type for cable cross section 2 1 mm2 Setpoint settings via Regio Tool Basic heating setpoint 5 40 C Basic cooling setpoint 5 50 C Setpo...

Page 4: ...Wiring Terminal Designation Operation 10 33 No function 40 5 V 5 V supply voltage from RCP 41 N 0 V 0 V supply voltage from RCP 42 A RU Bus A 43 B RU Bus B Dimensions Product documentation Document Type Regio Maxi Manual Manual for the controllers from the Regio Maxi series Installation instruction Regio RU FO Installation instruction for RU FO All product documentation is available on www regin s...

Reviews: