Regin RCW-M Instruction Download Page 1

INSTRUCTION

i

Read this instruction before installation 

of the product

RCW-M

1

Number Description

Number Description

1

Communication/Test 

button

5

RS485 terminal

2

LED lights

6

Power terminal

3

DIP switch set 2

7

RS485 terminal resistor (jumper)

4

DIP switch set 1

8

Service connection

Commissioning

 

This product must be connected to a separate transformer to  

 

prevent damage to the communication port.

Connect the reciever to 24 V AC

 

supply voltage. LED 5 and 6 will light up 

when the receiver is powered on.

Connect to Modbus master controller

Connect the receiver to the master controller via the RS485 terminal. 

The receiver will be in 

Connected

 status as default when powered on, 

which means that it will forward signals received from sensors to the 
controller. LED 5 will turn on with a steady light.

Disconnect the Modbus receiver

To disconnect the receiver, press and hold the 

Test button

 for approx.  

3 seconds. Release the button when you hear 2 beeps. LED 5 will start 
flashing to indicate that the receiver is disconnected.

To connect the receiver again, press and hold the 

Test button

 for approx. 

1 second. There will be 1 beep and LED 5 will stop blinking and light up 
with a steady light to indicate that it is connected.

Configuration

The receiver has two sets of DIP-switches for configuration.

Set 1: RS-485 Parity and Baud rate setting

Function

Switch 1

Switch 2

Value

Parity

OFF

OFF

None*

ON

OFF

Even*

OFF

ON

None*

ON

ON

Odd*

* 1 or 2 stop bits

Wireless receiver with Modbus communication

The Modbus receiver can pair with up to 16 digital or analogue sen-
sors. It monitors the sensors and reports the information to the user 
via Modbus communication.

  

1

2

3

4

5

6

7

LED 1

LED 2
LED 3
LED 4
LED 5
LED 6

8

N -A +B

G

G0

RCW-M

12808F

 

MA

Y 17

EN

Function

Switch 3

Switch 4

Value

Baud rate

OFF

OFF

9600

ON

OFF

19200

OFF

ON

38400

ON

ON

38400

Set 2: For Modbus address setting

DIP-

switch

Bit

Position

1

Bit0

ON

2

Bit1

ON

3

Bit2

ON

4

Bit3

ON

5

Bit4

ON

6

Bit5

ON

7

Bit6

ON

8

Bit7

ON

If all DIP-switches are OFF, the address is 1.

 

Examples:

• 

If DIP-switch 1,3 and 5 is ON, the Modbus address will be  
00010101 = 21

• 

If DIP-switch 2 and 4 is ON, the Modbus address will be 
00001010 = 10

Programming mode on the receiver

To be able to pair sensors with the receiver, the receiver must be in 

Programming

 mode. 

To enter 

Programming

 mode: press and hold the 

Test button 

on the 

receiver until you hear 1 short beep (approx. 1 second). This indicates 

that the receiver has entered 

Programming 

mode. LED 6 will start 

flashing. 

To exit 

Programming 

mode

press and hold the 

Test button

 for approx. 

1 second. LED 6 will light up with a steady light.

The receiver will exit 

Programming 

mode automatically if it is idle for 

6 minutes.