AVDT25

Duct mounted air velocity transmitter

AVDT25 is a duct mounted air velocity transmitter for measuring air veloc-
ity in air handling systems.
The output can be set to 0...10 V or 4...20 mA.
Three different measuring ranges for full output signal can be set to give 
the best possible accuracy at different air velocities.

Ranges:

 0...10 m/s, 0...15 m/s and 0...20 m/s.

There is a choice of two different damping times for the output signal.

Installation

Note:

 It is important that the unit is mounted so that the direction of the 

sensor head opening corresponds to the direction of the air flow.

Ambient temperature:

 -10...+50°C.

Drill a Ø13 mm hole in the duct wall. Hold the flange against the hole 
and drill fastening holes using the flange as template. Fasten the flange. 
Mount the sensor stem through the hole in the flange and fix it at desired 

depth. It is also possible to mount the sensor using the screw-pockets in 
the sensor housing.
In both cases it is essential to position the sensor so that there can be an 

unobstructed, straight airflow past the sensor element.

Wiring

Connect supply voltage and output signal according to the diagram.

Supply voltage:

 24 V AC/DC ±20 %.

Output signals:

 0...10 V DC or 4...20 mA corresponding to the chosen 

range. Choose range by moving the jumper.

Measuring accuracy:

0...10 m/s: ± (0.3 m/s + 3 % of measured value)
0...15 m/s: ± (0.3 m/s + 3 % of measured value)
0...20 m/s: ± (0.3 m/s + 4 % of measured value)

External load impedance:

 > 10 kΩ for 0...10 V output signal.

 

 

 

< 500 Ω for 4...20 mA output signal.

Damping time:

 The damping time is normally set to 4 seconds. By re-

moving the jumper it is shortened to 0.7 seconds

Maintenance

Should the element become very dirty it can be blown clean using a soft 

air-jet or be rinsed in isopropyl alcohol.

 

EMC emissions & immunity standards

This product conforms to the requirements of the EMC Directive 
2004/108/EC through product standards EN 61326-1 and EN 61326-2-3.

RoHS

This product conforms to the Directive 2011/65/EU of the European  
Parliament and of the Council.

Contact

AB Regin, Box 116, 428 22 Kållered, Sweden

Tel: +46 31 720 02 00, Fax: +46 31 720 02 50

www.regin.se, [email protected]

3633J

 

AUG 15

EN

1     Supply voltage 24 V AC   
2     System neutral
3     0...10 V or 4...20 mA

The output signal, working range and  

response time are selected by the  

jumpers according to the picture

t90 HI MED LO I U

t90 HI MED LO I U

t90 HI MED LO I U

t90 HI MED LO I U

t90 HI MED LO I U

t90 HI MED LO I U

t90 HI MED LO I U

Output

Working range

Response time

No jumper

Jumper

Jumper

Jumper

Jumper

FAST 

approx. 0.7 s

Jumper

Current (I)

Jumper

Voltage (U)
= factory setting

= factory setting

= factory setting

0...10 m/s

0...15 m/s

0...20 m/s

SLOW  approx. 4 s