INSTRUCTION ALH230A

Room humidity controller

ALH230A is a room humidity controller that controls a 0...10 V  
output signal with a proportional algorithm in direct or reverse 
action. The output signal is applied to an air handling unit, e.g. a 
ventilator such as an EC fan or damper.

Technical data

Supply voltage 

 

110...240 V AC, 50/60 Hz

Power consumption 

Max. 0.46 W

Operating temperature 

0...50°C, 10...90 % RH

 

 (non-condensing)

Outputs 

 

1 analogue output 0...10 V (max. 1 mA)

Working range 

 

0...100 % RH

Manual activation   

Min. 600 cycles

Automatic activation 

> 100 000 cycles

Dimensions (WxHxD) 

85 x 100 x 30.5 mm

Installation 

 

*Wall mounting

Impulse voltage   

2,5 kV

Pollution degree   

2

Classification of unit 

Type 1

Protection class   

IP30

Insulation class   

Class II

*The unit must be installed exclusively in contact with a wall.  
Installation with a spacer that would allow access to the back of the 
unit is forbidden.

Installation

Place the device in a location that has a temperature representative 

for the room. A suitable location is approx. 1.6 m above floor level in 

a place with unobstructed air circulation. To remove the front cover, 

use a 3 mm flatblade screwdriver to depress the locking tongue in 

the lower part of the casing (

picture 1

). Press and twist the screw-

driver, and at the same time pull the bottom part of the front outwards 
(

pictures 2-4

). When the bottom end of the front cover is free from 

the bottom part of the casing, slide the cover towards the top of the 
casing to free the hooks holding the upper edge of the front cover 
(

picture 5

). Perform the connections according to electrical wiring 

diagram. Cables must be fixed using the 2 cable ties supplied as indi

-

cated in 

picture 6

. Screw the bottom part of the casing to the wall.

Disconnection

ALH230A should be connected to a switch or circuit breaker in the 
building installation. This switch should be in close proximity to the 
controller and within easy reach of the operator, and should be 
marked as the disconnecting device for the equipment.
Always use the circuit breaker to disconnect the controller from the 
mains supply during maintenance of the EC fan or damper.

Settings

The direction of the output signal is set using the JP1 jumper  
(

picture 8

):

SW1: Humidity setpoint (20...90 % RH)
SW2: Humidity proportional band (5...50 % RH)

JP1 closed 1-2: Humidification
JP1 closed 2-3: Dehumidification

R28: EC fan min. limit speed
R29: EC fan max. limit speed

The humidity setpoint is set using rotary switch 

SW1

:

SW1

0

1

2

3

4

5

6

7

Setpoint
(% RH)

20

25

30

35

40

45

50

55

SW1

8

9

A

B

C

D

E

F

Setpoint
(% RH)

60

65

70

75

80

85

90

90

The proportional band is set using rotary switch 

SW2

:

SW2

0

1

2

3

4

5

6

7

P-band
(% RH)

5

10

15

20

25

30

35

40

SW2

8

9

A

B

C

D

E

F

P-band
(% RH)

45

50

50

50

50

50

50

50

The range of the voltage applied to the ventilator is defined using 
the MIN and MAX knobs. MIN is used to define the minimum ap

-

plicable voltage to the ventilator (0...5 V), while MAX defines the 

maximum voltage (5...10 V). The PI controller will then operate 
between the relevant MIN and MAX values.

Example 1:

If the MIN value is set to the minimum position and MAX to the 
maximum position, the PI controller will work from 0...10 V.

Example 2:

If MIN is set to 2 V and MAX is set to 7 V, the PI controller works 
from 2 to 7 V.

Low Voltage Directive (LVD) standards

This product conforms to the requirements of the European Low  
Voltage Directive (LVD) 2006/95/EC through product standard 
EN 60730-1.

EMC emissions & immunity standards

This product conforms to the requirements of the EMC Directive 
2004/108/EC through product standards EN 61000-6-1, 
EN 61000-6-3, EN60730-1 and EN 60730-2-13.

RoHS

This product conforms to the Directive 2011/65/EU of the European 
Parliament and of the Council.

Contact

AB Regin, Box 116, 428 22 Kållered, Sweden 
Tel: +46 31 720 02 00, Fax: +46 31 720 02 50 
www.regincontrols.se, [email protected]

2

i

Read this instruction before installation and wiring of the 
product. Subject to change without notice.

Consult documentation in all cases where this symbol is 

used, in order to find out the nature of the potentional 

hazards and any actions to be taken. All installation, 

setting or maintenance of this unit must be performed with the 
supply voltage switched off and without any external loads on the 
unit! These operations should only be carried out by skilled 
workers. The manufacturer is not responsible for any damages 
caused by inadequate skills during installation and/or by any safety 
devices having been removed or tampered with.

EN