background image

12

F2400/S2400 Freestanding Woodfire

installation

Horizontal Installation

Standard Ceiling Installation

s  any  point  within  10  feet  (3m)  measured 

horizontally.  There must be at least 3 feet 

(.9m) of flue above the roof level.

Note:   Increasing the flue height above this 

minimum level will sometimes help 

your unit to “breathe” better by allow-

ing a greater draft to be created.  This 

greater draft can decrease problems 

such  as,  difficult  start-ups,  back-

smoking when door is open, and 

dirty glass.  It might be sufficient to 

initially try with the minimum required 

height, and then if problems do arise 

add additional height at a later date.

4) 

  Slide the roof flashing over your flue and 

seal  the  flashing  to  the  roof  with  roofing 

compound.    Secure  the  flashing  to  your 

roof with nails or screws.

5)

  Place  the  storm  collar  over  the  flashing, 

sealing the joints with a silicone caulking.

1)

  For easier assembly, tip the heater on its back 

(onto a soft surface to prevent scratching).

  

 

Hint:

 If you have chosen the Ash Drawer 

option, remove the ash dump cover plates 

before attaching the pedestal. See page 16 

"Ashdrawer Kit Installation".

2)

  Remove the blanking plate if 

 a)

    you are 

not

 installing outside combustion 

air or 

 b) 

outside air is to be brought in from the 

rear

 of the heater.

3)

  Unscrew the 4 bolts in the under-side of the 

heater. Align the holes in the corners of the 

pedestal top with the corresponding holes 

in the base of the heater. Fasten using a 

bolt and washer for each corner.

4)

  Push the Regency logo into the two holes in 

the front bottom left corner of the pedestal 

cover plate.

  

Note:  Any paint touch up should be done 

prior to placing logo on pedestal.

5) 

If not using ash drawer, then cover plate must 

be installed. If using ash drawer, then disregard 

cover plate.

STEP-BY-STEP 
FLUE AND CONNECTOR 
INSTALLATION:

Note:   These are a generic set of flue instal

-

lation instructions.  Always follow 

the manufacturers own instructions 

explicitly. Check Table 1 on page 13 

for the Minimum Recommended Flue 

Heights.

1) 

With your location already established, cut 

and frame the roof hole. It is recommended 

that no ceiling support member be cut for 

flue  and  support  box  installation.  If  it  is 

necessary to cut them, the members must 

be made structurally sound.

2)

  Install radiant shield and support from above.

3)

  Stack the insulated pipe onto your finish 

support to a minimum height of 3 feet (.9m) 

above the roof penetration, or 2 feet (.6m) 

above 

Leg and Bottom Shield Assembly

The instructions below apply to the steel leg, 

painted cast leg and the gold plated cast leg. It 

will be easier to attach the legs to the heater if 

the heater is tipped on its back (preferably on 

a soft surface to prevent scratching). Ensure 

to be extremely careful when tipping heater.

1)

  Remove the 4 bolts from underside of the 

base of the pedestal and discard.  Also 

remove cover plate and put to the side.

2)

  Line up the heat shield with the bottom of 

the unit.

3)

  Start threading the bolt and washer (supplied 

with the bottom shield) for about 1/4 of the 

way through the leg with the washers being 

underneath the legs.  Ensure that the legs 

are properly aligned with heat shield and 

tighten the bolts.

4)

  Level the heater by adjusting the levelling 

bolts in the bottom of each leg.

5)

  Reinstall cover plate.

6)

  Install logo plate onto heat shield by placing 

in 2 holes as shown in diagram.

If you are installing outside combustion air, bend 

the tabs out 90 degrees. Pipe fresh air into the 

bottom shield by using a minimum 4" duct pipe 

with a mesh grill at the outside termination. At-

tach the pipe to the 2 tabs with screws.

Summary of Contents for Vancouver

Page 1: ... flam mable vapours and liquids in the vicinity of this or any other appliance Installation and service must be performed by an authorised installer service agency or the gas supplier Freestanding Woodfire FOR YOUR SAFETY What to do if you smell gas Do not try to light any appli ance Do not touch any electri cal switch do not use any phone in your building Immediately call your gas supplierfromane...

Page 2: ...n about restrictions and installation inspection requirements in your area The authority having jurisdiction should be consulted before installation to determine the need to obtain a permit ONLY CLEAN APPLIANCE WITH A DAMP CLOTH NEVER WHEN UNIT IS HOT DO NOT USE ANY ABRASIVE CLEANERS DO NOT BURN WILL VOID WARRANTY Treated wood Tea Tree Oil Based woods Coal Garbage Cardboard Solvents Colored Paper ...

Page 3: ...F2400 S2400 Freestanding Woodfire 3 Modular Parts ...

Page 4: ...nty 26 SAFETY LABEL Copy of Data Badge 4 INSTALLATION Unit Dimensions 5 Residential Installation 6 Modular Installation Options 6 Minimum Clearance to Combustibles 7 Minimum Alcove Clearances 8 Floor Protection 8 Heater Assembly Prior to Installation 9 Airmate Assembly 9 Rear Heat Deflector Assembly 9 Pedestal Assembly 9 Flue Baffle and Secondary air tube installation 10 Leg and Bottom Shield Asse...

Page 5: ...belthataccompanieseach RegencyFreestandingWoodheater F2402M We have printed a copy of the contents here for your review NOTE Regency units are constantly being improved Check the label on the unit and if there is a difference the label on the unit is the correct one ...

Page 6: ...6 F2400 S2400 Freestanding Woodfire DIMENSIONS dimensions 24 610mm 30 3 8 772mm 29 1 8 740mm 27 3 8 695mm 24 7 8 632mm 6 5 8 168mm ...

Page 7: ...mically active areas Regency rec ommends that your unit is secured to the floor by using the bolt down holes inside 10 In seismically active areas Regency rec ommends that your unit is secured to the floor by using the bolt down holes inside the pedestal the same ones used in Mobile Home installations 11 Forresidentialinstallationsusing6 152mm C Vent single wall the flue connector must be at least...

Page 8: ...l length half perforated decromesh flue surround or 900mm long half round enamelled mild steel flue shield fitted Flue systems tested Acorn Special Insulated FLOMET Super Single Shamic 1A Floor Protector 6mm thick fibre cement sheet with thermal conductivity 0 41 W m degree K underneath heater extending 300mm in front and 200 mm from the sides of the firebox opening Use only the instructions and c...

Page 9: ... pipe and extend 2 51mm beyond each side Minimum Overall Width X of Floor Protector for all installations Heater F2402M 36 914 mm NOTE InCanada floorprotectionmustextend18 450mm tothe front and 8 200mm to each side and back of the heater From From Flue Min Min Hearth Unit Unit Center line Width to Rear Wall G H I J K L Medium F2402M with Airmate 15 381 mm 5 5 139 mm 27 685 mm 12 304 mm 54 1371 mm ...

Page 10: ...ld See diagrams 2 3 Rear Heat Deflector Assembly The rear heat deflector is supplied with the stove andmustbeinstalledunlesstheoptionalairmate has been selected It stops the heat radiated from the flue collar from overheating the rear wall The rear heat deflector is installed on top of the rear heat shield as shown in diagram 4 Pedestal Assembly 1 Foreasierassembly tipthestoveonitsback onto a soft...

Page 11: ...as far as possible and then bring it back into the hole on the right hand side until it locks into position If the tube will not slide in easily simply use a pair of vise grips or pliers and tap it into place with a hammer A tighter fit will ensure the tube will not move when the unit is burning 2 Slide the left baffle over the air tubes from the front and then push it to the back see Diagram 1 3 ...

Page 12: ...r plate must be installed If using ash drawer then disregard cover plate STEP BY STEP FLUE AND CONNECTOR INSTALLATION Note These are a generic set of flue instal lation instructions Always follow the manufacturers own instructions explicitly Check Table 1 on page 13 fortheMinimumRecommendedFlue Heights 1 With your location already established cut and frame the roof hole It is recommended that no c...

Page 13: ...itable for use in Mobile Homes must be used 5 If the flue exits the Mobile Home at a location other than through the roof and exits at a point 7ft 2130mm or less above the ground level on which the Mobile Home is positioned a guard or method of enclosing the flue shall be fitted at the point of exit for a height up to 7ft 2130mm 6 The flue shall be attached directly to the room heater and shall ex...

Page 14: ...ns for safety and proper draft operation MASONRY FLUE Ensure that a masonry flue meets the minimum standards of the National Fire Protection As sociation NFPA by having it inspected by a professional Make sure there are no cracks loose mortar or other signs of deterioration and blockage Have the flue cleaned before the heater is installed and operated When con necting the heater through a combusti...

Page 15: ... to combustibles Masonry chimney Chimney Flue Minimum chimney clearance to brick and combustibles 2 in 50 8mm Minimum clearance 12 in 304 8mm of brick Chimney connector Fire clay liner Starting with a minimum 24 gage 024 61 mm 6 152 4 mm metal flueconnector andaminimum24gageventilatedwallthimblewhichhas two air channels of 1 25 4 mm each construct a wall pass through There shall be a minimum 6 152...

Page 16: ... 5 5m 21 6 4m 1000 305m 18 72 5 7m 21 84 6 7m 2000 610m 19 44 5 9m 22 68 6 9m 5000 1524m 21 60 6 6m 25 20 7 7m 8000 2438m 23 76 7 2m 27 72 8 5m MINIMUM RECOMMENDED FLUE HEIGHTS IN FEET Measured from the top of the unit ELEVATION FT ABOVE SEA LEVEL OF ELBOWS 0 2 x 15o 4 x 15o 2 x 30o 4 x 30o 2 x 45o 4 x 45o 0 1000 12 0 13 0 14 0 15 0 18 0 16 0 20 0 1000 2000 12 5 13 5 14 5 15 5 19 0 16 5 21 0 2000 ...

Page 17: ...to your unit Cutaminimum4inchdiameterholethrough your floor protector and the floor directly under your pedestal base to the outside Use 4 duct pipe with a mesh grill to pipe fresh air into the pedestal area Block off the hole in the back of the pedestal with the square plate and the two 1 2 13mm screws provided Place your unit in position and secure it to the floor using two lag bolts 3 8 x 3 1 2...

Page 18: ... the ash dump cover plates one inside the firebox and one on the underside of the firebox by removing the two nuts and boltsholdingthe2platestogetherfrominside the firebox 4 Push the ash plug into the hole inside the firebox and replace all the bricks except for the brick over the ash plug See brick diagram 5 Place the ash drawer lid inside the pedestal and the ash plug tool beside the lid then sl...

Page 19: ...ack Black High Black Low Red Black Fan Thermodisc normally open 120V AC 60 Hz Blower Fan Wiring Diagram Wire98gr eps updated Jan 27 00 updated Aug 09 05 capitalized the word Nut Lockwasher Ground wire from power cord Ground wire from fan 8 Groun Lug d Star washer Nut Nut Star washer Grounding Lug Detail CAUTION Labelallwirespriortodisconnection whenservicingcontrols Wiringerrorscancause improper a...

Page 20: ...mbus tion rate at a moderate level and avoid a large fire Only after 5 or 6 such fires can you operate the heater at its maximum setting and only after the metal has been warmed 7 For the first few days the heater will give off an odour from the paint This is to be expected as the high temperature paint becomesseasoned Windowsand ordoors should be left open to provide adequate ventilation while th...

Page 21: ...removalofash see Modular Options on page 6 Safety Precautions 1 Do not allow ashes to build up to the loading doors Only remove ashes when the fire has died down Even then expect to find a few hot embers 2 Please take care to prevent the build up of ash around the start up air housing located inside the heater box under the loading door lip 3 Never start a fire if the ash plug and ash drawer are n...

Page 22: ...y during the season as creosote deposits may build up rapidly Moving parts of your heater require no lubrication 4 A small hot fire is preferable to a large smouldering one that can deposit creosote within the system 5 The flue and flue connector should be inspected at least once every two months during the heating season to determine is a creosote buildup has occurred 6 Have flue system and unit ...

Page 23: ... Nut 1 4 20 Hex 16 846 570 7 8 Door Gasket Repair Kit 17 846 918 Hinge Cap Gold 2 set 19 948 101 Spring Handle Large 20 948 102 Spring Handle Small HEATER MAIN ASSEMBLY Part Description Part Description 846 513 Complete Fan Blower Assy 240 V 25 910 684 Power Cord 120 V 27 910 142 Thermodisc Fan Auto ON OFF 28 910 138 Manual Auto Switch 2 way 29 910 140 Fan Speed Switch HI OFF LOW 3 way 30 910 155 ...

Page 24: ...sh Plug 59 820 249 Ash Plug Tool Handle 56 020 911 Bottom Shield Medium 57 Blanking Plate Btm Shield 850 101 Ashdrawer Kit Btm Shield 55 Ashdrawer Bottom Shield 58 942 110 Ash Plug 59 820 249 Ash Plug Tool Handle 140 850 126 Legs Cast Black 850 127 Legs Cast Gold 850 128 Legs Cast Brush Nickel 142 850 125 Legs Steel Black 948 216 Logo Regency Not available as a replacement part PEDESTAL BOTTOM SHI...

Page 25: ...ire 25 PARTS LIST parts list 020 960 Brick Set Complete 70 Brick Regular Full Size 1 1 4 x 4 1 2 x 9 74 Brick Partial 1 1 4 x 4 1 2 x 3 1 2 75 Brick Partial 1 1 4 x 4 1 2 x 2 76 Brick Partial 1 1 4 x 2 x 9 Part Description FIREBRICK ...

Page 26: ...awer Heatshields Pedestal 1 All Baffles Steel Ceramic Vermiculite 1 All castings firebox surrounds doors panels etc 1 All Electrical Fans wiring switches etc Fan only 1 Glass Crazing 1 Catalyst Assembly see below for specific details 6 Years Prorated 3 Flue components 1 Firebricks Nil Nil After the original warranty coverage for any of the parts above have expired any repair and or replacement par...

Page 27: ...r results or costs of workmanship of unauthorised FPI dealers or agents in the negligence of their service work Additional service fees may apply if you are seeking warranty service from a dealer other than the dealer from whom you originally purchased the product At all times FPI reserves the right to inspect reported complaints on location in the field claimed to be defective and determine wheth...

Page 28: ... appliances Any unit showing signs of neglect or misuse will not be covered under the terms of this warranty policy and may void this warranty This includes units with rusted or corroded fireboxes which have not been reported as rusted or corroded within three 3 months of installation purchase Any alteration to the unit which causes sooting or carboning that results in damage to the exterior fasci...

Page 29: ... to at the option of the supplier one or more of the following i replacement of the goods or the supply of equivalent goods ii the repair of the goods iii the payment of the cost of replacing the goods or of acquiring equivalent goods or iv equivalent goods or v the payment of the cost of having the goods repaired b To the extent that services supplied by the supplier are services other than servi...

Page 30: ...ace Products Australia Pty Ltd does not provide installation services Fireplace Products Australia Pty Ltd 1 3 Conquest Way Hallam VIC Australia 3803 Phone 61 3 9799 7277 Fax 61 3 9799 7822 To obtain warranty service in Western Australia and or New Zealand please contact one of our authorised distributors in those areas Western Australia Air Group Australia 28 30 Division St Welshpool WA Australia...

Page 31: ...ow in order for us to serve you better Warranty Registration Form or Register online immediately at the above Web Site Warranty Details Serial Number required Purchase Date required mm dd yyyy Product Details Product Model required Dealer Details Dealer Name required Dealer Address Dealer Phone Installer Date Installed mm dd yyyy Your Contact Details required Name Address Phone Email For purchases...

Page 32: ...32 F2400 S2400 Freestanding Woodfire ...

Page 33: ...F2400 S2400 Freestanding Woodfire 33 NOTES notes ...

Page 34: ...34 F2400 S2400 Freestanding Woodfire NOTES notes ...

Page 35: ...F2400 S2400 Freestanding Woodfire 35 ...

Page 36: ..._________________________ ___________________________________________________________________ Installer ____________________________________________________________ Phone ____________________________________________________________ Date Installed _______________________________________________________ Serial No ___________________________________________________________ ...

Reviews: