background image

32

Regency

®

 P33-4 Zero Clearance Direct Vent Gas Fireplace

INSTALLATION

GAS LINE 

INSTALLATION

The gas line is brought through the right side 
of the appliance. The gas valve is situated on 
the right hand side of the unit and the gas inlet 
is on the right hand side of the valve.

The gas line connection may be made of 
rigid pipe, copper pipe or an approved fl ex 
connector. (If you are using rigid pipe, ensure 
that the valve can be removed for servicing.) 
Since some municipalities have additional 
local codes it is always best to consult with 
your local authorities and the CAN/CGA B149 
installation code.

For USA installations follow local codes 
and/or the current National Fuel Gas Code, 
ANSI Z223.1.

When using copper or fl ex connectors use only 
approved fi ttings. Always provide a union so 
that gas lines can be easily disconnected for 
servicing. Flare nuts for copper lines and fl ex 
connectors are usually considered to meet 
this requirement.

Important: Always check for gas leaks 
with a soap and water solution or gas leak 
detector. Do not use open fl ame for leak 
testing.

Diagram 4

Diagram 3: The upper half of the fl ashing is 

installed under the roofi ng material and not 

nailed down until the chimney is installed. 

This allows for small adjustments.

Diagram 2

UNIT INSTALLATION 

WITH VERTICAL 

TERMINATION

1)

  Maintain the 1-1/2" clearances (air spaces) to 

combustibles when passing through ceilings, 
walls, roofs, enclosures, attic rafter, or other 
nearby combustible surfaces. Do not pack 
air spaces with insulation. Check "Venting" 
Sections for the maximum 
vertical rise of the venting 
system and the maximum 
horizontal offset limitations.

2)

  Set the gas appliance in its 

desired location. Drop a plumb 
bob down from the ceiling to 
the position of the appliance 
fl ue exit, and mark the location 
where the vent will penetrate 
the ceiling. Drill a small 
hole at this point. Next, 
drop a plumb bob from the 
roof to the hole previously 
drilled in the ceiling, and 
mark the spot where the 
vent will penetrate the roof. 

3)

  A Firestop spacer must be installed in the 

fl oor or ceiling of every level. To install the 
Firestop spacer in a fl at ceiling or wall, 
cut a 10 inch square hole. Frame the hole 
as shown in Diagram 2 and install the 
fi restop.

Diagram 4

NOTE:

   

For best results and optimum 

performance with each approved venting 
system, it is highly recommended to apply 
“Mill-Pac” sealant (supplied) to every in-
ner pipe connection. Failure to do so may 
result in drafting or performance issues not 
covered under warranty. Silicone (red RTV) 
is optional.

8)

  Slide the appliance and vent assembly 

towards the wall carefully inserting the 
vent pipe into the vent cap assembly. It is 
important that the vent pipe extends into the 
vent cap suffi cient distance so as to result 
in a minimum pipe overlap of 1-1/4 inches. 
Secure the connection between the vent 
pipe and the vent cap 3 sheet metal screws. 

9)

  Install wall thimble in the center of the 

10" square and attach with wood screws 
(Diagram 4).

4)

  Assemble the desired lengths of pipe and  

elbows. Ensure that all pipes and elbow 
connections are in the fully twist-locked 
position and sealed.

5)

  Cut a hole in the roof centered on the small 

drilled hole placed in the roof in Step 2. The 
hole should be of suffi cient size to meet 
the minimum requirements for clearance 
to combustibles of 1-1/2". Slip the fl ashing 
under the shingles (shingles should overlap 
half the fl ashing) as per Diagram 3.

6)

  Continue to assemble pipe lengths.

Note:  If an offset is necessary in the attic to 

avoid obstructions, it is important to 
support the vent pipe every 3 feet, to 
avoid excessive stress on the elbows, 
and possible separation.  Wall straps 
are available for this purpose.

 
 

Galvanized pipe is desirable above the roofl ine 
due to its higher corrosion resistance. Continue 
to add pipe sections through the fl ashing until 
the height of the vent cap meets the minimum 
height requirements specifi ed in Dia. 4 or local 
codes.  Note that for steep roof pitches, the 
vertical height must be increased.  A poor 
draft, or down drafting can result from high 
wind conditions near big trees or adjoining 
roof lines, in these cases, increasing the 
vent height may solve the problem.

7)

  Ensure vent is vertical and secure the base 

of the fl ashing to the roof with roofi ng rails, 
slide storm collar over the pipe section and 
seal with a mastic.

8)

  Install the vertical termination cap by twist-

locking it.

Note:  Any closets or storage spaces, which 

the vent passes through must be 
enclosed. 

Diagram 1

    Roof Pitch                   Minimum Vent Height

                                           Feet         Meters

fl at to 7/12 

      0.61

over 7/12 to 8/12 

0.61

over 8/12 to 9/12 

0.61

over 9/12 to 10/12 

2.5 

0.76

over 10/12 to 11/12 

3.25 

0.99

over 11/12 to 12/12 

1.22

over 12/12 to 14/12 

1.52

over 14/12 to 16/12 

1.83

over 16/12 to 18/12 

2.13

over 18/12 to 20/12 

7.5 

2.29

over 20/12 to 21/12 

2.44

Summary of Contents for P33-4

Page 1: ...st be performed by a qualified installer service agency or the gas supplier FOR YOUR SAFETY What to do if you smell gas Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Tested by I...

Page 2: ... provide you with all the warmth and charm of a wood fireplace at the flick of a switch The P33 4 has been approved by Warnock Hersey Intertek for both safety and efficiency As it also bears our own mark it promises to provide you with economy comfort and security for many trouble free years to follow Please take a moment now to acquaint yourself with these instructions and the many features of yo...

Page 3: ...follow the current National Fuel Gas Code ANSI Z223 1 and the current National Electrical Code ANSI NFPA 70 in the U S A and the cur rent CAN CGA B149 Gas Installation Code and the current Canadian Electrical Code CSA C22 1 in Canada The appliance when installed must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA...

Page 4: ...Safety Information 7 Requirements 7 INSTALLATION Installation Checklist 8 Locating your fireplace 8 Duct System Option 8 Unit Dimensions 9 Unit Dimensions with contemporary faceplate 9 Clearances for bay or flush front 10 Clearances with contemporary faceplate 10 Combustible Mantels 11 Mantel Leg Clearances with Flush or bay glass 12 Mantel Leg Clearances with contemporary Faceplate 12 Framing and...

Page 5: ...the unit and if there is a difference the label on the unit is the correct one For the State of Massachusetts installation and repair must be done by a plumber or gasfitter licensed in the Commonwealth of Massachusetts For the State of Massachusetts flexible connectors shall not exceed 36 inches in length For the State of Massachusetts the appli ances individual manual shut off must be a t handle ...

Page 6: ...ade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon...

Page 7: ...have to be removed for servicing should be replaced prior to operating this appliance 12 Installation and any repairs to this appliance should be done by a qualified service person Aprofessional service person should be called to inspect this appliance annually Make it a practice to have all of your gas appliances checked annually 13 Do not slam shut or strike the glass door 14 Under no circumstan...

Page 8: ...that the appliance is firing correctly and operation fully explained to customer This includes 1 Clockingtheappliancetoensurethecorrect firing rate rate noted on label after burning appliance for 15 minutes 2 Ifrequired adjustingtheprimaryairtoensure that the flame does not carbon First allow the unit to burn for 15 20 min to stabilize CAUTION Any alteration to the product that causes sooting or c...

Page 9: ...egency P33 4 Zero Clearance Direct Vent Gas Fireplace 9 INSTALLATION UNIT DIMENSIONS WITH CONTEMPORARY FACEPLATE 33 838mm 33 838mm 23 584mm 12 3 4 324mm 29 737mm 28 1 2 724mm 31 1 2 800mm UNIT DIMENSIONS ...

Page 10: ...C Close to Ceiling Flue Clearances to Combustibles Horizontal Top 2 1 2 Horizontal Side 1 1 2 Horizontal Bottom 1 1 2 Vertical Flex Vent 1 1 2 Vertical Rigid 1 1 4 Note All measurements are from the top side of the unit not optional front Clearances for Bay or Flush Front The clearances listed below are Minimum distances unless otherwise stated A major cause of chimney related fires is failure to ...

Page 11: ...non combustible board This drawing is to scale at 1 6 one inch 6 inches Mantel can be installed anywhere in shaded area or higher using the above scale Note Ensure the paint that is used on the mantel and the facing is heat resistant or the paint may discolour Combustible mantel leg clearances as per diagrams below Drywall Mantel Clearances with Flush Full Screens or Bay Glass 2 0 12 6 4 8 10 2 0 ...

Page 12: ...NTEL LEG CLEARANCES WITH CONTEMPORARY FACEPLATE Combustible mantel leg clearances from side of unit as per diagram MANTEL LEG CLEARANCES WITH FLUSH OR BAY GLASS Combustible mantel leg clearances from side of unit as per diagram Maximum 1 1 2 projection at 2 minimum clearance ...

Page 13: ...rame in the enclosure for the unit with framing material FRAMING AND FINISHING 16 1 2 419mm Minimum 4 102mm 3 76mm 1 1 2 38mm 30 762mm 10 254mm dia Hole through wall for Dura Vent 1 2 13mm Drywall Top Header Opening for gas connection 12 3 4 324mm Minimum 4 102mm 3 76mm 1 1 2 38mm 26 660mm 10 254mm dia Hole through wall for Flex 1 2 13mm Drywall Top Header Opening for gas connection Rigid Vent Min...

Page 14: ...tical Rise 16 1 2 419mm Rigid 12 3 4 324mm Flex K Corner Wall Length 37 1 2 953mm L Corner Facing Wall Width 53 1 4 1353mm M Framed Chase Ceiling 36 914mm Rigid 32 812mm Flex N Vent Centerline Height 30 762mm Rigid 26 660mm Flex O Gas Connection Height 1 1 2 38mm P Gas Connection Inset 4 102mm Q Gas Connection Width 3 76mm FRAMING DIMENSIONS WITH CONTEMPORARY FACEPLATE NOTE If this is an outside c...

Page 15: ...rtbeforeunitisslippedintoposition See Unit Assembly Prior to Installation Section 4 Combustible material may be brought up to the top and sides of the unit and be covered with wood drywall ceramic tiles bricks rock or other suitable combustible finishing materials Note The unit does not have to be completely enclosed in a chase The clearance on top of the unit is 0 to the standoffs so combustible ...

Page 16: ...ing Strip using the 3 supplied screws into the three pre punched screw holes at the front sides of the unit Adjust support to desired facing material thickness UNIT ASSEMBLY PRIOR TO INSTALLATION Top Facing Support Side Nailing Strips folded out VENTING INTRODUCTION The P33 4 uses the balanced flue technology Co Axial system The inner liner vents products of combustion to the outside while the out...

Page 17: ...ne extended above meter regulator assembly 36 90cm a J Clearance to service regulator vent outlet 36 90cm K Clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance 12 30cm 9 23cm L Clearance to a mechanical air supply inlet 3 91cm above if within 10 3m horizontally 72 1 8m 36 90cm b M Clearance above paved sidewalk or a paved driveway located on ...

Page 18: ... a continuous vent length of more than 2 ft 6m to a maximum of 10 ft 3 0m use Kit 946 515 4 ft or 946 516 10 ft or see Rigid Pipe Venting Systems Section for alternate venting arrangements 1 6 7 8 dia flexible liner 2 ft length 2 4 dia flexible liner 2 ft length 3 spring spacers 3 4 thimble 2 5 AstroCap termination cap 1 6 screws 12 7 tube of Mill Pac 1 8 plated screws 8 9 screws 8 x 1 1 2 drill p...

Page 19: ...3 Assemble the vent assembly by applying Mill Pac to the 4 100mm inner collar of the terminationand slippingthe4 100mm liner over it at least 1 3 8 35mm Fasten with the3screws drillingpilotholeswillmakethis easier Apply Mill Pac or high temperature silicone to the 6 7 8 175mm flex pipe and slip it over the 6 7 8 outer collar of the vent terminal at least 1 3 8 35mm and fasten with the 3 screws 4 S...

Page 20: ...ernate Horizontal Termination Caps This product has been evaluated by Intertek for using a Rigid Pipe Adaptor in conjunction withDuraventDirect Vent SelkirkDirect Temp Ameri Vent Direct venting and Security Secure Vent systems Use of these systems with the Rigid Pipe adaptor is deemed acceptable and does not affect the Warnok Hersey Intertek listing of components WARNING Do not combine venting com...

Page 21: ...ength 3 10 Black N A N A N A 4DALB N A TC 4DLTB Adjustable Length 7 Galvanized N A N A 4D7A N A N A N A Adjustable Length 7 Black N A N A 4D7AB N A N A N A Extension Pipe 8 1 2 Galvanized 46DVA 08A N A N A N A N A N A Extension Pipe 8 1 2 Black 46DVA 08AB N A N A N A N A N A Adjustable Length 12 Galvanized N A N A 4D12A N A SV4LA12 N A Adjustable Length 12 Black N A N A 4D12A N A SV4LBA12 N A Exte...

Page 22: ...rmination 36 N A N A N A N A N A TM 4ST36 Basic Horizontal Termination Kit A Disc 4DT HKA 4DHTK2 4DHTKA SV SHK N A Horizontal Termination Kit B 46DVA KHA Changed Components 4DT HKB 4DHTK1 4DHTKB SV HK N A Vertical Termination Kit Disc 4DT VKC 4DHTK 4DHTK SV FK N A FPI 946 506 P Vent Guard Optional for AstroCap 946 205 Vinyl Siding Shield for Riser Vent Terminal 510 994 Rigid Pipe Adaptor Must use ...

Page 23: ...bles When using Contemporary Faceplate unit must be raised 1 Note Must use optional rigid pipe adapter when using rigid vent systems Part 510 994 RIGID PIPE VENTING ARRANGEMENTS Vertical Terminations Propane Natural Gas The shaded area in the diagram shows all allowable combinations of straight vertical and offset to vertical terminations using one 90o elbow with rigid pipe vent systems for Propan...

Page 24: ...dedareainthediagramshowsallallowablecombinationsofstraight vertical and offset to vertical terminations with rigid pipe vent systems for Propane and Natural Gas Maximum two 45o elbows allowed Vent must be supported at offsets Firestops are required at each floor level and whenever passing through a wall Maintain clearances to combustibles When using Contemporary Faceplate unit must be raised 1 ...

Page 25: ...pe adaptor Part 510 994 when using rigid pipe vent systems Refer Rigid Pipe Venting Systems Section Maintain clearances to combustibles Horizontal vent must be supported every 3 feet Firestops are required at each floor level and whenever passing through a wall When using Contemporary Faceplate unit must be raised 1 A vent guard should be used whenever the terminationislowerthanthespecifiedminimum...

Page 26: ...w Two 45o elbows Option H V H H1 H2 With these options maximum total pipe length is 30 feet with minimum of 11 feet total vertical and maximum 9 feet total horizontal P l e a s e n o t e minimum 1 foot between90o elbows is required A 1 Max 1 Min 3 Max B 2 Max 3 Min 5 Max C 3 Max 5 Min 6 Max D 4 Max 7 Min 7 Max E 5 Max 9 Min 8 Max F 6 Max 11 Min 9 Max One 90o elbow Two 45o elbows Option H V H H1 Wi...

Page 27: ...x B 3 Min 2 Max 4 Min 5 Max C 4 Min 3 Max 6 Min 6 Max D 5 Min 4 Max 8 Min 7 Max E 6 Min 5 Max 10 Min 8 Max F 7 Min 6 Max 12 Min 9 Max One 90o elbow Two 45o elbows Option V H V V1 With these options maximum total pipe length is 30 feet with minimum of 6 feet total vertical and maximum 8 feet total horizontal Please note minimum 1 foot between 90o elbows is required A 1 Min 4 Max 2 Min B 2 Min 5 Max...

Page 28: ...45o elbows One 90o elbow Two 45o elbows With these options max total pipe length is 30 feet with min of 11 feet total vertical and max 7 feet total horizontal Please note min 1 foot between 90o elbows is required Option V H H1 V V1 A 2 Min 3 Max 4 Min B 3 Min 4 Max 6 Min C 4 Min 5 Max 7 Min D 5 Min 6 Max 8 Min E 6 Min 7 Max 9 Min F 7 Min 8 Max 10 Min With these options max total pipe length is 30 ...

Page 29: ...cal Terminations Section for minimum and maximum heights Required Parts Part Description 946 529 Co linear DV Vertical Termination Cap 948 305 3 Flex 35 ft 946 563 Co Axial to Co Linear Adapter Kit whichcontainsthefollowing Co linear Flex Adapter Outer Pipe Inner Pipe Adapter 510 994 Rigid Pipe Adaptor 46DVA E45 45o Elbow Alternate Approved Caps 46dva VC Vertical Termination Cap 46dva VCH High Win...

Page 30: ...S with Co linear Flex System for both Residential Manufactured Homes into Masonry Fireplaces The shaded area in the diagrams show the allowable vertical terminations 8 2 4m Min 30 762mm 30 9 1m Max 30 Horizontal Distance Feet Vertical Height feet 2 51mm max When using Contemporary Faceplate unit must be raised 1 ...

Page 31: ...nents 1 Set the unit in its desired location Check to determine if wall studs or roof rafters are in the way when the venting system is attached If this is the case you may want to adjust the location of the unit Rough in the gas preferably on the right side of the unit and the electrical junction block is on the left side on the left 2 Direct Vent pipe and fittings are designed with special twist...

Page 32: ...venting system it is highly recommended to apply Mill Pac sealant supplied to every in ner pipe connection Failure to do so may result in drafting or performance issues not covered under warranty Silicone red RTV is optional 8 Slide the appliance and vent assembly towards the wall carefully inserting the vent pipe into the vent cap assembly It is important that the vent pipe extends into the vent ...

Page 33: ...LEVATION This unit is approved in Canada for altitude to 4500 ft CAN CGA 2 17 M91 For Natural Gas installations above 4500 ft follow current CAN CGA B149 1 S I T VALVE DESCRIPTION 1 Gas on off knob 2 Manual high low adjustment 3 Pilot Adjustment 4 Thermocouple Connection option 5 Outlet Pressure Tap 6 Inlet Pressure Tap 7 Pilot Outlet 8 Main Gas Outlet 9 Alternative TC Connection Point PILOT ADJUS...

Page 34: ... Assembly to the left and lift out Installation of the LPG Conversion Kit 1 Shut off the gas supply 2 a Remove the louvers bay door or faceplate if installed b Open the flush door and remove the door c Remove the logs embers and brick panels if used Pilot assembly is now accessible for steps 4 to 9 d Remove the 2 screws holding the Burner Assembly to the firebox base Push the Burner Assembly to th...

Page 35: ...e screw clockwise until snug do not overtighten 13 Verify that if the conversion is from NG to LPG the screw must be re assembled with the red o ring visible Fig 5 14 Re assemble the black protection cap Fig 6 WARNING Also check that the pilot and main burner injectors are appropriate for the gas type Fig 1 Fig 2 Fig 3 Fig 4 LPG Configuration Red o ring visible Fig 5 Fig 6 15 See Page 35 for DC Sp...

Page 36: ...cation which is not too hot and is easy to reach for changing the battery Note It should be kept away from the chain 14 Tie up the loose wire with the wire clip Ground wire from kit Chain 1 Locate the Piezo Ignitor situated at the side of valve 2 Remove the Piezo Ignitor by unscrewing the nut at the back of the mounting bracket 3 Disconnect the ignitor wire from the Piezo Ignitor and connect it to...

Page 37: ...ach log Readtheinstructionsbelowcarefully and refer to the diagrams If logs are broken do not use the unit until they are replaced Broken logs can interfere with the pilot operation Log Kit 431 930 contains the following pieces A 250 Rear Log B 254 Middle Cross Log C 253 Front Left Cross Log D 251 Rear Left Log E 252 Front Right Cross Log F Embers 902 156 G Vermiculite 902 179 H Rock Wool 902 153 ...

Page 38: ...ember size pieces of rock wool and gently place them on the front of the burner tray in the places shown in the photo below Do not compress the rock wool leave it loose Separate platinum embers and place them on the front of the burner on and around the rock wool Place rock wool in these 2 locations on the burner tray 251 2 5 2 250 254 2 5 3 250 254 2 5 3 251 2 5 3 250 254 2 5 3 254 252 Cutout 9 T...

Page 39: ...1 Secure with 1 screw Diagram 2 Note Top and bottom louvers are different 3 Open the bottom louver Pull the Burner ON OFF control box from inside the bottom of the fireplace and position the slots in the bracket over the 2 screws on the left side of the bottom louver Push down to lock into place Tighten the screws Screws on louver bracket Burner ON OFF control box attached to bottom flush louver B...

Page 40: ...t Shield 3 Install top louver by sliding the two bracket clips into the brackets located on top of the bay door See below The fitted louver leaves a small gap between faceplate bottom and louver top Bay Louver Top Heat Shield 4 Install bottom louver by sliding the two bracket clips into the brackets located underneath the bay door Secure with 1 screw into each Bottom Louver Mounting Bracket as per...

Page 41: ...crews located on the inside top of the outer frame of the appliance Also remove the center screw b Slide the cut outs in the Top and Bottom Flange of the Full Screen Door Frame under the screw heads which were loosened in step 4a Once the Frame is in place tighten the screws to secure Also re secure the top center screw through the oblong hole 3 Before attaching the Full Screen Door Frame remove t...

Page 42: ...he 2 x 8 Self Tapping Phillips screws provided Bottom Grill Hinge Location 7 Mount the Burner ON OFF Control Box to the left side of the Bottom Grill using 2 x 8 1 4 Philips Head Screws Burner ON OFF Control Box Left Side of Bottom Grill 5 Install the Hinges to the Hinge Brackets on the left and right side of the Bottom Faceplate Bracket seen in step 2 secure using 2 x 8 Self Tapping Philips screw...

Page 43: ...ews holding the Burner Assembly to the firebox base Push the Burner Assembly to the left and lift out Burner Orifice 3 Remove burner orifice with a 1 2 wrench and discard Use another wrench to hold on to the elbow behind the orifice 4 Reinstall new burner orifice and tighten NG 47 LP 56 LP Conversion Must also use Kit 434 969 with P33 units and Kit 425 972 with P33E units 5 Reverse Steps 1 and 2 N...

Page 44: ...n the fan base Ensure that the fan blades do not rub against the valve tubing Diagram 1 3 Connect fan ground cable to ground lug Refer to wiring diagram 5 Slide the thermodisc cover assembly into the bracket clip on the un derside of the firebox Check that no wire will touch the hot surfaces Diagram 2 Diagram 1 Diagram 2 TO REMOVE THE FAN 1 Shut the power off 2 Reverse the above instructions Note ...

Page 45: ... has a flange that hooks over the top of the flush door 2 Install the heat deflector on the fire box as shown in Diagrams 2 3 Loosen 3 Phillips head screws already in firebox slide heat deflector on to screws and retighten Diagram 1 Diagram 2 Top of Unit Heat Deflector Diagram 3 Diagram 4 Diagram 5 Bend Diagram 6 Flange Mounting Frame Heat Deflector Control Shield Faceplate Support Faceplate 434 0...

Page 46: ...iagram 8 Diagram 9 Image of P33 4 with Faceplate Image of P33S with Faceplate Faceplate Faceplate Support 6 Hook the flange on the faceplate over the top of the flush door and gently lower the faceplate into place until it rests against the faceplate supports as shown in Diagrams 7 8 ...

Page 47: ...he Regency Remote Control Kit approved for this unit Use of other systems may void your warranty The remote control kit comes with a hand held transmitter a receiver and a wall mounting plate 1 Choose a convenient location on the wall to install the receiver and the receptacle box protectionfromextremeheatisveryimportant Run wires from the fireplace to that location Use Thermostat Wire Table 2 Con...

Page 48: ...control thermostat will continue to operate However a 120V A C power supply is needed for the fan blower operation Do not cut the ground terminal off under any circumstances NOTE Even if the fan is not purchased with the unit it is still a good idea to bring power to the receptacle box provided with the unit in case the fan is installed at a later date For NATURAL GAS Units and Units NOT Equipped ...

Page 49: ... hot surfaces and are away from sharp edges CAUTION Labelallwires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation For PROPANE Units and Units Equipped with DC Spark Boxes For installation of the DC Spark Box refer to the LP Conversion instructions in this manual ...

Page 50: ...ol box assembly on the 12 Secure the fan wires and power cord by attaching one of the adhesive backed wire holder clips Part 910 199 onto Secure left side with 2 screws Secure right side with one screw Secure the 2 boxes together with one screw Hold control box assembly in place and mark the position of the right side slot Diagram 1 Diagram 2 Diagram 3 Use the clip hook on the side of the control ...

Page 51: ...Regency P33 4 Zero Clearance Direct Vent Gas Fireplace 51 51 OPERATING INSTRUCTIONS COPY OF THE LIGHTING PLATE INSTRUCTIONS OFF a ...

Page 52: ...ect and enclosed to prevent possible shock 3 Check to ensure there are no gas leaks 4 Makesuretheglassinthedoorframeisproperly positioned Neveroperatetheappliancewiththe glass removed 5 Verifythattheventingandcapareunobstructed 6 Ensure that the brick panels are installed 7 Verify log placement If the pilot cannot be seen when lighting the unit the logs have been incorrectly positioned 8 The unit ...

Page 53: ...sened Alsocheckmechanicalsupportssuch as Wall Straps or plumbers tape for rigidity GOLD PLATED LOUVERS TRIM The 24 carat gold plated finish on the louvers and trim requires little maintenance and need only be cleaned with a damp cloth DO NOT use abrasive materials or chemical cleaners as they may harm the finish and void the warranty Clean any finger prints off before turning the unit on LOG REPLA...

Page 54: ... Do not use abrasive materials Do not clean the glass when hot In the event that you break your glass by impact purchase your replacement from an authorized Regency dealer only and follow our step by step instructions for replacement WARNING Do not operate the ap Remove the flush door front Remove the 4 glass clipsfromeachcorner Slideinthenewreplacement glass Push the 4 glass clips back onto the f...

Page 55: ...t with a 9mm wrench 6 Reconnectthepilottubenutwitha7 16 wrench 7 Scrape off the old gasket from the floor of the firebox and from the valve tray assembly 8 Install a new gasket and reinstall the valve tray assembly Note Failuretoinstallanewgasketmayseverely affect the appliance performance 9 Reinstall the 10 hold down screws 10 Hook up the 2 TP and 2 TH wires to the appropriate connections on the ...

Page 56: ...6 Brick Panel Top 37 430 056 Brick Clip Top 38 430 057 Brick Clip Bottom 432 917 Fan Assembly 120 Volts Optional 42 910 331 P Fan Motor 120 Volts 432 966 Fan Switch Assy 120 Volts 43 910 813 Power Cord 120 Volts 46 910 330 Fan Speed Control 47 904 586 Knob Speed Control 49 910 142 Thermodisc Fan Auto ON OFF 50 904 713 U Clip at Louver 432 967 Burner On Off Switch Assy 63 910 241 Switch Burner On O...

Page 57: ...T 10 DOORS LOUVERS PLEASE REFER SEPARATE SECTION BRICK PANEL SET 34 37 38 FAN SWITCH ASSEMBLY 42 50 46 26 22 102 94 95 97 98 99 100 90 96 91 92 93 HEAT WAVE DUCT KIT 93 89 9 7 1 23 20 2 23 31 28 30 27 13 14 30 19 104 8 36 33 35 47 43 49 ASSEMBLY ON OFF SWITCH 63 16 17 ...

Page 58: ... Propane 57 910 478 S I T Valve NG LP 58 Valve Bracket 59 Firebox Base 60 Valve Tray 66 910 038 Pilot Assy 3 way flame S I T NG 910 039 Pilot Assy 3 way flame S I T LP 904 568 Orifice 44 Natural Gas 904 163 Orifice 54 Propane 936 170 Orifice Gasket 67 Pilot Holder 68 W840470 Pilot Assembly Gasket 79 433 525 Burner Assy NG LP 82 433 024 Burner Grate Assembly NG LP 83 Rear Log Support Bracket NG LP ...

Page 59: ...uver Assy Bottom 433 538 Flush Door Assembly Complete 135 940 088 P Glass Flush 137 904 691 U Clip 139 936 155 Glass Gasket Tadpole 140 948 042 Spring Hinge Black 430 940 Finishing Trim Set Black Option 157 Finishing Trim Left 159 Finishing Trim Right 158 Finishing Trim Top 431 943 Double Screen Door Complete Option 171 Door Frame Left Assembly 172 Door Frame Right Assembly 173 904 712 U Clip for ...

Page 60: ...bly Painted Red 434 517 Faceplate Assembly Stainless Steel 2 434 033 Mounting Plate 3 434 514 Faceplate Support Bracket Assembly 909 924 Bumper Rubber W Machine Screw 8 32 x 3 8 904 925 Cap Assy Brushed Stainless 3 4 diameter 4 434 032 Control Shield 5 434 018F Heat Deflector 6 904 434 Burner Orifice 47 Natural Gas 904 434 Burner Orifice 56 Propane Gas CONTEMPORARY FACEPLATE 1 2 4 5 3 6 ...

Page 61: ...Regency P33 4 Zero Clearance Direct Vent Gas Fireplace 61 NOTES ...

Page 62: ...62 Regency P33 4 Zero Clearance Direct Vent Gas Fireplace NOTES ...

Page 63: ...is included with these parts parts of this unit which in our judgement show evidence of such defects will be repaired or replaced at FPI s option through an accredited distributor or ag ective part be returned to the distributor or agent Transportation Prepaid if requested namel Absolute perfectionisneither guaranteednor commercially possible Any chips must be reported and inspected by an authoriz...

Page 64: ..._________________________ Date Installed ______________________________________________________ Serial No __________________________________________________________ Register your Regency warranty online www regency fire com Reasons to register your product online today View and modify a list of all your registered products Request automatic email notification of new product updates Stay informed a...

Reviews: