26
Regency GF900C-2 Gas Fireplace
installation
Notes:
1. Liner sections should be continuous without any joints
or seams.
2. Only Flex pipe purchased from Regency® may be used
for Flex installations
3. Horizontal flue must be supported every 0.9m.
4. Regency® Direct Vent System (Flex) is only approved
for horizontal terminations.
5. Flex system can only be used up to a maximum continu-
ous vent length of up to 3m. If longer runs are required,
rigid pipe must be used.
NOTE:
Maximum horizontal run: 3M
FPI Kit #
Length
Contains:
#946-515
1.2 m
1) 175mm flexible outer liner (Kit length)
2) 102mm flexible inner liner (Kit length)
3) spring spacers
4) thimble
5)
AstroCap
termination cap
6) screws
7) tube of Mill Pac
8) plated screws
9) S.S. screws #8 x 1-1/2” drill point
#946-516
3 m
FLUEING ARRANGEMENTS
HORIZONTAL TERMINATION (FLEX)
Regency
®
Direct Vent System
These flueing systems, in combination with GF900C, have been tested and listed as a Direct Vent system by AGA. The location of the termination cap must
conform to the requirements in the Flue Terminal Locations diagram from the "Exterior Flue Termination Locations" section.
Regency
®
Direct Vent (Flex) System Termination Kits includes all the parts needed to install the GF900C using a flexible vent.
Flue Guard - if required*
(Part #946-506/P)
102mm