Regency GF1500L Gas Fireplace
15
installation
COMBUSTIBLE REQUIREMENTS
FRAMING & FINISHING
Note:
Depending on the material used for finishing, the nailing
strips must be set accordingly so that the finished material
is always at the 38mm edge of the flange.
MINIMUM THICKNESS OF THE FINISH MATERIAL: 12MM
NOTE:
The appliance must be installed
on a flat, solid continuous surface,
For example., a wood, metal or
concrete floor or in a raised (on
the wall) application. The appli-
ance must be installed on a metal
or wood base extending the full
width and depth of the appliance.
Note:
A minimum thickness of 12mm non-
combustible facing is required.
(11
19
m
m)
(83mm)
(617 mm)
(502mm)
(1432 mm)
Non-combustible
Material
Non-combustible
Non-combustible
Non-combustible
Header
on edge
Timber Stud
Timber Stud
(159 mm)
(459 mm)
Combustible material
Note:
The siding nailing strips are factory set at 12mm. The top
nailing strip is fixed during transit to the rear of the appliance.
NOTE:
If raising the unit, then the minimum
height measurement (A) on page
11 of the framing dimensions must
be adhered to. For example., Unit
raised 300mm then A+ 300mm =
1395mm.
Finished
Material
Nailing Strip
Position
12mm
25mm
25mm
12mm
38mm
0mm (flush)
Unit
Nailing Strip
Flush w/unit
Factory Set
Unit
Nailing Strip
12mm Forward
Unit
Nailing Strip
25mm Forward