background image

203

June 2007 Regency Product Specifi cations Book

Wood Stoves

W
ood Sto

v

es

Residential Close Clearance 

(To be installed with required pipe components)

When the stove is installed as a close clearance residential unit, a listed double wall connector is required 
from the stove collar to the ceiling level.

Unit

From Unit

From Corner

From Vent 

centerline

F2400 

    A               B

C               D

E               F

with Airmate

  15”              5.5”                  

  4”              27”             

12”          15.5”

with Rear Defl ector

  15”              6.5”  

 6”              27” 

13”          17.5”

Mobile Home Close Clearance 

(To be installed with required pipe components)

“C” Vent single wall pipe is not approved for Mobile Home installations. (Refer to mobile home instructions.)

Unit

From Unit

From Corner

From Vent 

centerline

F2400

    A               B

C               D

E               F

with Airmate

   15”             5.5”                  

  4”              27”             

12”          15.5”

with Rear Defl ector

   15”             6.5”  

  6”              27” 

13”          17.5”

Unit

From Unit

From Vent 

centerline

Min. 

Width

Min. Hearth 

to Rear Wall

F2400

    G               H

I               J

K

L

with Airmate

   15”            5.5”                  

27”          12”             

54”

48”

with Rear Defl ector

   15”            6.5”  

27”          13” 

54”

49”

Minimum Alcove Clearance To
Combustible Materials

Regency Freestanding models have been alcove approved and must be 
installed with a listed double wall connector to the ceiling level. 

Note:  Minimum alcove ceiling height - 84"
 

 

Maximum depth of alcove - 36"

*The rear clearance to combustibles is less than 6" (152mm), for corner 
installations the rear corners may be angled to take advantage of the
closer clearances.

NOTE: In Canada, fl oor protection must extend 18" to the front 

and 8" to each side of the stove.

Floor Protection

A combustible fl oor must be protected by a non-combustible material 
(like tile, concrete board, or certifi ed to UL-1618 or as defi ned by local 
codes) extending beneath the heater and a minimum of 6" from each 
side and minimum 16" from the front face of the stove and minimum 6" 
(or the rear clearance to combustibles whichever is smaller) from the 
rear of the stove. 

    Minimum Overall Width (X) of Floor 
       Protector

 

for all installations: 

Medium Stove 

F2400 

36"

Minimum Overall Depth (Y) of Floor Protector

Unit

Residential

“C” Vent

Residential 

Close 

Clearance

Mobile 

Home Close 

Clearance

Alcove

F2400

    Y               Z

Y               Z

Y               Z

Y               Z

with Airmate

   46”             6”                  

  45”*           5”             

45”           5”    

45”*           5”

with Rear Defl ector

   46”             6”  

  45”            5”    

45”           5”    

45”            5”    

F2400 Wood Stove

Reviews: