background image

Regency CLASSIC C34-2 Direct Vent Freestanding Gas Heater

23

INSTALLATION

7) The connection between the appliance and

the Retro Connector may be completed with
sections of black direct vent pipe, together
with an adjustable length.

Converting a Masonry Chimney

Important: The existing  masonry flue
opening needs to have an area of at least
a 36 sq. in. to insure proper intake/ex-
haust flow.

1) Before cutting any holes, assemble the

desired sections of black direct vent pipe to
determine the center of the masonry pene-
tration.

Diagram 6

2) Once the center point of the penetration has

been determined, cut a 6" (152mm) dia. hole
in the masonry. Be careful, if the hole is too
large, the Retro Connector might not mount
properly, and if the hole is too small, then the
appliance might starve for intake air. If there
is a frame wall in front of the masonry wall,
cut and frame a 10" (254mm) clear square
opening in the wall (centered around the 6"
(152mm) masonry opening). If there is sheet
rock only (no studs) in front of the masonry,
the 10" (254mm) clear opening is still need-
ed, but does not need to be framed. This
allows the Retro Connector to mount direct-
ly on the masonry and provide clearance to
the combustibles. Diagram 11.

3) Secure the Flashing (Part # 705C) to the top

of the masonry chimney using a bead of
non-hardening sealant-adhesive. IF the

Flashing is larger than the top of the chim-
ney, then cut and fold flashing as needed
to fit chimney. Diagram 7.

Diagram 7

4) To determine the length of flex required,

measure from 3" (76mm) above the top of
the Flashing down to the level of the open-
ing. Add to this measurement the distance
from the center of the chimney to out through
the wall. Cut a piece of 4" flex to this length
(the flex should already be extended to its
nominal length).

5) Connect the 4" flex liner to the Top Adaptor

(Part # 985K) using 3 sheet metal screws.
Diagram 2.

6) Feed the 4" flex liner through the Flashing

into the chimney. Continue to feed the liner
out through the opening in the masonry wall.

7) Secure the Top Adaptor to the Flashing. Use

3 sheet metal screws through the side of the
adaptor into the flange on the Flashing
(diagram 8). Twist lock the Termination Cap
(Part # 980 or 991) on to the Top Adaptor.

and the mounting holes line up with the
masonry wall.

Diagram 8

Diagram 9

9) Slide the Wall Thimble Cover (Part # 940)

over the Retro Connector and secure with
masonry bolts. Diagram 10. If you have a
framed wall in front of the masonry, use
wood screws to mount the Wall Thimble
Cover to the framed wall, over the Retro
Connector and the 10" (254mm) square
framed opening. Diagram 11. If needed, add
a section of direct vent pipe to the Retro
Connector in order to extend through the
opening in the Wall Thimble Cover.

Diagram 10

8) Attach the flex to the Retro Connector. Use

3 sheet metal screws to attach the flex liner
to the Connector. Diagram 9. Mount the
Retro Connector to the masonry wall using
masonry bolts. Re-drill larger holes on con-
nector as needed. Be careful to insure that
the connector is centered in the opening

10) The connection between the appliance and

the Retro Connector may be completed
with a section of black direct vent pipe,
together with an adjustable length pipe
section.

Diagram 11

Summary of Contents for C34-LP2

Page 1: ... switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department FPI FIREPLACE PRODUCTS INTERNATIONAL LTD 6988 Venture St Delta BC Canada V4G 1H4 908 584a MODELS C34 NG2 Natural Gas C34 LP2 Propane C34 Classic Direct Vent Freestanding Gas Stove Classic C34 ...

Page 2: ... ANSI NFPA 501A and with CAN CSA Z240 MH Mobile Home Standard in Canada This appliance installation must comply with the manufacturer s installation instructions and local codes if any In the absence of local codes follow the current National Fuel Gas Code ANSI Z223 1 and the current National Electrical Code ANSI NFPA 70 in the U S A and the current CAN CGA B149 Gas Installation Code and the curre...

Page 3: ...nformation 5 Installation Checklist 6 Locating Your Classic Gas Stove 6 Manufactured Mobile Home Requirements 6 Combustion and Ventilation Air 6 Clearances to Combustibles 6 Optional Fan Installation 7 Pedestal Assembly 8 Leg and Bottom Shield Assembly 8 Venting 9 Installation Precautions 9 Safety Precautions for the Installer 9 Vent Restrictor Position 9 Exterior Vent Terminal Locations 10 Rigid ...

Page 4: ...s are constantly being improved Check the label on the unit and if there is a difference the label on the unit is the correct one SAFETY LABEL FortheStateofMassachusetts installation and repair must be done by a plumber or gasfitter licensed in the Commonwealth of Massachusetts For the State of Massachusetts flexible connectors shall not exceed 36 inches in length For the State of Massachusetts th...

Page 5: ...Have a qualified building inspector review your plans before installation GENERAL SAFETY INFORMATION 1 The appliance installation must conform with local codes or in the absence of local codes with the current Canadian or Na tional Electrical Codes CAN1 B149orANSI Z223 1 Installation Codes 2 The appliance when installed must be electrically grounded in accordance with local codes or in the absence...

Page 6: ... venting either with the DV Stove Horizontal Vent Kit page 15 or the Dura VentTerminationkits page17 CheckVent Restrictor setting page 9 If converting a Class A Metal Chimney or Masonry Chim ney to a Direct Vent system see instruc tions on pages 22 and 23 5 Make gas and electrical connections page 24 Test the pilot Must be as per diagram pages 28 6 Test gas pressure page 24 7 Install log set see p...

Page 7: ...estal door and remove door cov er plate by removing 4 screws See dia gram 1 IMPORTANT Disconnect power supply before servicing For leg unit remove 7 screws remove bottom access panel and install fan assembly follow steps 4 to 17 INSTALLATION For pedestal unit To install the fan in an installed stove access from front throughthepedestalbyfollowingthe directions below If the stove is not installed a...

Page 8: ...m 4 17 Reverse steps 3 1 to complete installation Fan Removal 1 Disconnect the power to the fan 2 Allowthestovetocooltoroomtemperature 3 Open the pedestal door and remove the screws on the door cover plate Leg units remove the bottom access panel 4 Loosen the screws of the nutserts 5 Removethefanassemblyfromthekeyslots at the fan base and pull fan out through the rectangular opening Diagram 3 6 Tu...

Page 9: ... and the Simpson Dura Vent Direct Vent System Model DV GS venting systems in combination with theClassicDirectVentFreestandingGasStove C34B NG C34G NG and C34B LP C34G LP have been tested and listed as direct vent heater systems by Warnock Hersey If converting a Class A Metal Chimney or Ma sonry Chimney to a Direct Vent system see instructions on pages 22 and 23 The C34 uses the balanced flue tech...

Page 10: ...ffit located above the terminal within a horizontal distance of 24 60 cm from the centre line of the terminal 18 46 cm min E Clearance to unventilated soffit 12 30 cm min F Clearance to outside corner with AstroCap Termination Cap min 6 15cm with Dura Vent Termination Cap 12 30cm G Clearance to inside corner with AstroCap Termination Cap min 6 15cm with Dura Vent Termination Cap 12 30cm H Not to b...

Page 11: ... Length 7 Black N A N A 4D7AB Adjustable Length 12 Galvinized N A N A 4D12A Adjustable Length 12 Black N A N A 4D12AB 45O Elbow Galvinized 945 4DT EL45 4D45L 45O Elbow Black 945B 4DT EL45B 4D45LB 45O Elbow Swivel Galvinized 945G N A N A 45O Elbow Swivel Black 945BG N A N A 90O Elbow Galvinized 990 4DT EL90S 4D90LS 90O Elbow Black 990B 4DT EL90SB 4D90LBS 90O Elbow Swivel Galvinized 990G N A N A 90O...

Page 12: ...e Products International Ltd Dura Vent and Direct Vent GS are registered and or proprietary trademarks of Simpson Dura Vent Co Inc ThisproducthasbeenevaluatedbyIntertekfor using a Dura Vent Flue Adaptor in conjunction with Selkirk Direct Temp and Ameri Vent Direct venting systems Use of these systems with the Direct Vent GS starting collar is deemed acceptableanddoesnotaffecttheIntertekWHI listing...

Page 13: ...h the factory set vent restrictor position of C Example B Offset to Vertical Vent A 15 ft vertical run with 4 ft horizontal offset distance falls within the shaded area and is an allowable installation with Vent Restrictor Position R Right VENTING ARRANGEMENTS HORIZONTAL TERMINATIONS FOR ALL VENTING SYSTEMS The shaded areas in the diagram below show all allowable combinations of vertical runs with...

Page 14: ...his30feetwithmin of6feettotalverticalandmax 8 feet total horizontal Please note min 1 foot between 90o elbows is re quired With these options maximum total pipelengthis30feetwithminimum of6feettotalverticalandmaximum 8 feet total horizontal Please note minimum 1 foot between 90o elbowsisrequired INSTALLATION One 90o elbow Two 45o elbows One 90o elbow Two 45o elbows Vent restrictor position C fully...

Page 15: ...bstituted for any other manufacturer s products Reviewthefollowingsequenceofinstructions which are typical of most installations The sequence may vary depending on wall thick ness Refertopages6 to10forventlocationand clearance dimensions 1 Set the unit in its desired location Check to determine if wall studs will be in the way of the venting system adjust location until all clearances are met and ...

Page 16: ...rdeningmasticshouldbe run around both the termination and vinyl siding standoff to prevent water from en tering and to make a tight seal between the cap and the standoff 7 Stretchthe4 dia flexlineroutfullyandget a trial fit of the liner onto the 4 dia starter collar 8 Cut the 4 dia flex liner to the desired size Hint leaveanextra12 to16 oflength this willmakethefinalassemblyeasiertowork with 9 Sec...

Page 17: ...ation DURA VENT VENTING COMPONENTS The Simpson Dura Vent Direct Vent System offers a complete line of component parts for installation of both horizontal and vertical installation Many items are offered in decorative black as well as galvanized finish The galvanized pipe and fittings are used for concealed locations such as attics or where corrosion is a factor such as above the roof line Decorati...

Page 18: ... Vent Basic Horizontal Kit 970 1 90o Elbow 1 Wall Thimble Cover 1 Horiz Sq Term Cap Alternate Horizontal Termination Caps Alternate Horizontal Riser Vent Terminal Part 640 530 P Minimum components for a Horizontal Installation using Dura Vent Compo nents A Dura Vent Horizontal Termination Kit 971 B Wall Thimble 942 required for combusti ble walls Canada Only Minimum components for a Vertical Termi...

Page 19: ... ends diagram 1 Push the pipe sections completely together then twist lock one section clockwise ap proximately one quarter turn until the two sections are fully locked The female locking lugs will not be visible from the outside on the Black Pipeorfittings Theymaybelocatedby examiningtheinsideofthefemaleends Apply sealant Mill Pac to inner pipe and high temperature silicone sealant to outer pipe ...

Page 20: ... cap by attaching the two sheet metal strips extending from the vent capassemblyintotheouterwallofthevent pipe Use the two sheet metal screws provided to connect the strips to the pipe section Bend any remaining portion of the sheet metal strip back towards the vent cap so it will be concealed by the decora tive wall thimble cover See diagram 6 7 Install Wall Thimble in the center of the 10 square...

Page 21: ...ure flashing totheroof withroofingnails Slidethestorm collar over the pipe section and seal with a mastic 6 Twist lock the vent cap on to the last section Offset Chart Diagram 12 Diagram 13 Roof Pitch Minimum Vent Height Feet Meters flat to 7 12 2 0 61 over 7 12 to 8 12 2 0 61 over 8 12 to 9 12 2 0 61 over 9 12 to 10 12 2 5 0 76 over 10 12 to 11 12 3 25 0 99 over 11 12 to 12 12 4 1 22 over 12 12 t...

Page 22: ...tified chim ney sweep or home inspection service The direct vent system must not be connected to a damaged factory built or masonry chimney For factory built zero clearance and masonry chimneys cleanout doors and caps or plugs for cleanout tee fittings and ash dumps shall be secured in place andsealedbeforeinstallingaDirectVent system within the chimney If the appliance shuts off during opera tion...

Page 23: ... 3 76mm above the top of the Flashing down to the level of the open ing Add to this measurement the distance fromthecenterofthechimneytooutthrough the wall Cut a piece of 4 flex to this length the flex should already be extended to its nominal length 5 Connect the 4 flex liner to the Top Adaptor Part 985K using 3 sheet metal screws Diagram 2 6 Feed the 4 flex liner through the Flashing into the ch...

Page 24: ...from the piping system by closing its individual manual shut off valve during the testing Valve Description 1 Gas cock knob 2 Manual high low adjustment 3 Pilot Adjustment 4 Thermocouple Connection 5 Main Operator 6 Outlet Pressure Tap 7 Inlet Pressure Tap 8 Pilot Outlet 9 Main Gas Outlet 10 Flange Securing Screw Holes 11 Alternative TC Connection Point 12 Thermoelectric Unit 13 Additional Valve M...

Page 25: ...ved locations Read the instructions below carefully and refer to the diagrams If logs are broken do not use the unit until they are replaced Broken logs can interfere with the pilot and burner operation The gas log kit contains the following a Front Log Part 902 180 b Rear Log Part 902 186 c SmallCrossLogs 2 Part 902 182 d Bag of embers Part 902 151 e Bag of rockwool Part 902 153 Part 490 932 for ...

Page 26: ...operation OPTION 2 REMOTE WALL SWITCH 1 Run the wire through the opening in the rear of the unit Be careful not to damage any wires Note We recommend a maximum of 15 of wire but if you wish to go with a longer run use the Thermostat Wire Table 2 Connect the wire to the wall switch and install into receptacle box CAUTION Do not wire millivolt wall switch for gas appliance to the 120V AC wires OPTIO...

Page 27: ...wer operation CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation CAUTION Ensure that the wires do not touch a hot surface and are away from sharp edges WARNING Electrical Grounding Instructions This appliance is equipped with a three pronged grounding plug for your protection against shock hazard and should be plugged dir...

Page 28: ...uburn your fireplace for at least four 4 hours the first time you use it with the fan on When first operated the unit will release an odour caused by the curing of the paint the burning off of any oils remaining from manufacturing Smoke de tectorsinthehousemaygooffatthistime Open a few windows to ventilate the room for a couple of hours The glass panel may require cleaning after the unit has coole...

Page 29: ...ed by the installer and is primarily used in installations at high elevations Pushinforayellowflame orpullout forabluerflame Theburneraerationisfactory set but may need adjusting due to either the local gas supply or altitude Caution Carbon will be produced if air shutter is closed too much Note Aeration Adjustment should only be performed by an authorized Regency Installer at the time of installa...

Page 30: ...Stove Brite Paint Metallic Black 6309 3 The glass should be cleaned with a gas fireplaceglasscleanerwhenitstartstoturn milky 4 Make a periodic check of burner for proper position and condition Visually check the flameoftheburnerperiodically makingsure the flames are steady not lifting or floating If there is a problem call a qualified service person 5 The appliance and venting system must be inspe...

Page 31: ...of 90o elbow 16 Removetwo 2 phillipsheadM5screwson each side of the valve 17 Remove valve and remove gas out 90o brass fitting Note orientation of fitting See diagram on page 7 for more detail INSTALLING VALVE ASSEMBLY 1 To install a new valve assembly reverse instructions for removing valve See assembly steps 1 10 2 Checkforleaksandmanifoldpressure See Gas Pressure Test instructions 3 To reinstal...

Page 32: ... 20 490 917 Complete Fan Assembly Optional 910 157 P Blower Motor 120V 21 910 142 Fan Auto on off Thermodisc 22 910 794 Power Cord 120V 24 Gasket Air Passage 25 Flex Pipe 3 ID 26 Stainless Steel Hose Clamp 27 936 197 Gasket Flue Collar Starter Collar 28 936 194 Gasket Starter Collar Air Passage 29 Airmate Heat Shield 30 W260260 Relief Frame Gasket 31 942 117 Top Relief Plate Frame 32 W260280 Top R...

Page 33: ... Assy 3 Flame S I T NG 910 035 Pilot Assy 3 Flame S I T LP 67 904 604 36 Orifice NG 904 390 52 Orifice LP 936 170 Orifice Gasket 68 936 175 Gasket Top Plate 69 948 280 Burner c w Air Cap NG LP Complete Burner Tray Assy NG LP 71 Clamp for Burner 72 490 023 Front Log Deflector NG LP 78 490 067 Deflector Top Rear Log NG 79 490 068 Deflector Top Rear Log LP 490 932 Complete Log Set 80 902 180 Front Lo...

Page 34: ...er Cord 121 490 005 Access Panel 140 850 127 Cast Legs Gold 4 set 850 126 Cast Legs Black 4 set 850 128 Cast Legs Brush Nickel 4 set 142 850 125 Steel Legs 4 set 490 926 Complete Pedestal 100 948 216 Regency Logo 102 904 257 Magnetic Catch Large 103 11 Pedestal Hinge 108 910 246 Burner ON OFF Switch 109 910 140 Fan HIGH OFF LOW Switch 110 910 327 Strain Relief for Power Cord 123 490 070 Pedestal B...

Page 35: ...redit once the replaced component has been returned to FPI and evaluated for manufacturer defect The authorized selling dealer is responsible for all in field service work carried out on your Regency product FPI will not be liable for results or costs of workmanship from unauthorized service persons or dealers At all times FPI reserves the right to inspect product in the field which is claimed to ...

Page 36: ..._______________________________________ Printed in Canada Regency fireplace products are designed with reliability and simplicity in mind In addition our internal Quality Assurance Team carefully inspects each unit thor oughly before it leaves our door Fireplace Products International Ltd is pleased to extend this Limited Lifetime Warranty to the orig inal purchaser of a Regency Product See the in...

Reviews: