background image

Bellavista

®

 B36XTCE-10 Gas Fireplace

  |     

41

 

 

|

 

41

installation

918-774

09/02/08

1

B36X/XT

BRICK PANEL INSTALLATION

Dangerous operating conditions may occur if the panels are broken.

Handle with care. DO NOT FORCE INTO POSITION.

1) 

Unwrap the Brick Panels from the protective wrapping.

2) Ensure that the logs are not in the unit.

3)

  Remove the heat defl ector (if installed) by removing the 2 screws  

     securing the heat defl ector from the top of the fi rebox.

4)

  Install the back brick panel fi rst - use caution when clearing the            

     burner assembly and rear log tray so the panel is not damaged.

Note:

  Ensure that an equal space (gap) is maintained on both 

           the right and left side - when installing the back panel. 

5)

 Remove the hex head screw on the upper left side of the fi rebox   

   wall.  

  Position left brick panel in place and secure with the brick panel clip    

  and screw.

6) 

 Slide top brick panel under left and back brick panel, use care not  

     to damage panel.

7)

  Right brick panel is installed last, follow the same procedure as for   

     left panel (see step 5).  

Left Panel

Right Panel

Back Panel

Top Panel

Back Panel Installed

Final Brick Panel  Installation

Heat defl ector

8)

  Reinstall top heat defl ector (reverse Step 3).

BRICK PANEL INSTALLATION

Summary of Contents for bellavista B36XTCE

Page 1: ...or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Leave the building immediately Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach you gas supplier call the fire...

Page 2: ... warmth and charm of a wood fireplace at the flick of a switch The Bellavista B36XTCE has been approved by Warnock Hersey Intertek for both safety and efficiency As it also bears our own mark it promises to provide you with economy comfort and security for many trouble free years to follow Please take a moment now to acquaint yourself with these instructions and the many features of your Regency F...

Page 3: ...cal codes if any In the absence of local codes follow the current National Fuel Gas Code ANSI Z223 1 and the current National Electrical Code ANSI NFPA 70 in the U S A and the current CAN CGA B149 Gas Installation Code and the current Canadian Electrical Code CSA C22 1 in Canada This appliance comes equipped with a dedicated 8 Ground Lug for attachment of the ground wire to the steel chassis as ap...

Page 4: ...hree 3 90o Elbows Rigid Pipe 4 x 6 5 8 31 Venting Arrangements for Vertical Terminations Rigid Pipe 4 x 6 5 8 32 Vertical Terminations Three 3 90o Elbows Rigid Pipe 4 x 6 5 8 33 Venting Arrangements with Co Linear Flex System 34 Co Linear Flex System Into Masonry Fireplaces 35 Unit Installation with Horizontal Termination 4 x 6 5 8 or 5 x 8 Venting Rigid Pipe 36 Unit Installation with Horizontal T...

Page 5: ...ct one COPY OF SAFETY DECAL For the State of Massachusetts installation and repair must be done by a plumber or gas fitter licensed in the Commonwealth of Massachusetts For the State of Massachusetts flexible connectors shall not exceed 36 inches in length For the State of Massachusetts the appli ances individual manual shut off must be a t handle type valve The State of Massachusetts requires the...

Page 6: ...tly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon inspecti...

Page 7: ...UNIT DIMENSIONS 33 23 5 8 14 3 4 8 5 8 29 3 4 41 5 16 35 5 16 33 1 8 7 7 16 3 1 4 1 1 2 1 1 4 40 5 8 38 1 16 29 7 8 4 1 8 25 5 8 32 7 8 21 13 16 838mm 599mm 3 375mm 1032mm 529mm 759mm 759mm 105mm 650mm 79mm 188mm 32mm 38mm 840mm 895mm 756mm 1049mm 219mm ...

Page 8: ...on sense however we are required by the Canadian Safety Standards and ANSI Standards to make you aware of the following GENERAL SAFETY INFORMATION 1 The appliance installation must conform with localcodesor intheabsenceoflocalcodes with the current Canadian or National Gas Codes CAN1 B149orANSIZ223 1InstallationCodes 2 The appliance when installed must be electrically grounded in accordance with l...

Page 9: ...irements Refer to Framing Finishing section e VentingRequirements Referto Venting section 2 Assemble Top Standoffs and Top Facing Support and Side Nailing Strips Refer to Unit AssemblyPriortoInstallation Section NOTE Must be done before installing unit into place 3 Install vent Refer to Venting sections 4 Make gas connections Test the pilot Must beasperDiagram Referto PilotAdjustment section Conve...

Page 10: ...aintain required clearances air space to combustible materials It is of the greatest importance that this fireplace and vent system be installed only in accordance with these instructions B36XTCE Clearance Requirements Minimum Vent Clearances to Combustibles Clearance Dimension Measured From A Mantel Height min 21 1 4 540mm Top of Fireplace Opening B Sidewall 12 304mm one side only Side of Firepla...

Page 11: ...this fireplace emits the mantel clearances are critical Combustible mantel clearances from top of front facing are shown in the Diagram on the right Note A non combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non combustible board Mantel Clearances B36XTCE A B C D From Top of Fireplace Opening 29 11 16 754mm 29 1 4 743mm 25 3 4 641mm 21 1 4...

Page 12: ... NOTE The 9 1 4 x 40 5 8 non combustible material supplied with this unit can be replaced if trying to achieve a clean finish A large piece of non combustible material ie 4 x 8 x 1 2 can be used to eliminate taped seams on or near unit 6 5 3 5 Mantel leg Mantel leg Allowable mantel leg projection 3 1 1 2 Top View 12 Side opening of fireplace ...

Page 13: ... Rear Vent Framed Chase Ceiling Rear 47 3 4 1213mm R Top Vent Framed Chase Ceiling Top 50 1 2 1283mm S Rear Vent Vent Centerline Height Rear 26 1 2 673mm S Top Vent 5 x 8 Vent Centerline Height Top 42 1 8 1070mm Flex 44 1 4 1123mm Rigid S Top Vent 4 x 6 5 8 Vent Centerline Height Top 49 1245mm Rigid T Gas Connection Height 1 1 2 38mm U Gas Connection Inset 7 3 8 187mm V Gas Connection Width 3 1 4 ...

Page 14: ...t to combustible materials See Clearances section Combustible materials can be laid against the side and back standoffs and the stove base 4 Tile Finish Option 1 Drywall may be installed onto the unit as shown below to create a surface to apply finishing materials such as tile slate etc Drywall cannot extend beyond the metal surface of the unit 5 Tile Finish Option 2 If applying a non combustible ...

Page 15: ...d Minimum Clearances for Finishing Materials Trim materials Note All non combustible facingmaterialshouldbuttupcleanly to the flanges around the firebox opening Rough edges may be visible from an angle To maintain a clean finished edge facing material edges may be finished with a J style trim or metal cornerbead both materials available at your local building or hardware store IMPORTANT Materials ...

Page 16: ...y are marked B36XT B36XTE B36XTCE STANDOFF SLOT LOCATION B36XT B36XTE B36XTCE TopView B36X B36X Nailing strip for Tile Finish set back 1 2 Nailing strip for Clean Finish set flush with unit 1 There are 8 eight side nailing strips and one top nailing strip available on the unit One set of four 4 are for a clean finish installation the other set are for a tile finish installation as they are set bac...

Page 17: ...y Gasket spare 1 Insulation Plate Cover 1 Insulation Filling Exhaust Assembly w gasket Intake Cover Plate w gasket Insulation cover plate Insulation filling Intake Collar Assembly w gasket 2 From inside the firebox remove the top heat deflector by removing 2 screws Heat Deflector Diagram 2 1 Remove the door assembly by releasing the adjustable latches and lifting up off the door frame assembly Adj...

Page 18: ...ws Diagram 9 Ensure all screws are tight but do not over tighten All 8 screws must be used Diagram 8 Diagram 9 10 From the outside rear of the firebox install the intake cover plate with 4 1 4 x 1 2 screws Ensure all screws are tight but do not over tighten All 4 screws must be used 11 Set vent restrictor accordingly see next page 12 From inside the firebox re install the baffle plate and heat def...

Page 19: ... TO OPTIONAL PANEL INSTALLATION Note If installing brick optional panels see brick optional panel instructions before proceeding to next step Diagram 2 Vent restrictor installed on top exhaust assembly 6 From inside the firebox install the baffle plate with 4 1 4 x 1 2 screws Ensure all screws are tight but do not over tighten Baffle Plate Diagram 3 7 From inside the firebox install the top heat d...

Page 20: ...xtended above meter regulator assembly 36 90cm a J Clearance to service regulator vent outlet 36 90cm K Clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance 12 30cm 9 23cm L Clearance to a mechanical air supply inlet 3 91cm above if within 10 3m horizontally 72 1 8m 36 90cm b M Clearance above paved sidewalk or a paved driveway located on publ...

Page 21: ...le Length 7 Black N A N A 4D7AB N A N A N A Extension Pipe 8 1 2 Galvanized 46DVA 08A N A N A N A N A N A Extension Pipe 8 1 2 Black 46DVA 08AB N A N A N A N A N A Adjustable Length 12 Galvanized N A N A 4D12A N A SV4LA12 TC 4dLSI Adjustable Length 12 Black N A N A 4D12A N A SV4LBA12 TC 4dLSIB Extension Pipe 16 Galvanized 46DVA 16A N A N A N A N A N A Extension Pipe 16 Black 46DVA 16AB N A N A N A...

Page 22: ...nation Kit A Disc 4DT HKA 4DHTK2 4DHTKA SV SHK TM4 HTK Horizontal Termination Kit B 46DVA KHA Changed Components 4DT HKB 4DHTK1 4DHTKB SV HK TM4 HTK Vertical Termination Kit Disc 4DT VKC 4DHTK 4DHTK SV FK N A FPI 946 506 P Vent Guard Optional for AstroCap 946 205 Vinyl Siding Shield for Riser Vent Terminal 510 994 Rigid Pipe Adaptor Must use with all rigid piping 946 208 P Vent Guard Optional for ...

Page 23: ...t 58DVA DC N A from FPI N A N A N A Firestop Spacer 58DVA FS 5DT FS 5DFS TM 5LS Trim Plate Black 58DAV WFS 5DT TP 5DCP TM 5TP 5 X 8 RIGID PIPE CROSS REFERENCE CHART Components from different Manufacturers may not be mixed Not all rigid pipe components are available directly from Regency Note The listed manufacturers may have other lengths not shown on this chart which would also be approved Descri...

Page 24: ... AstroCap XL Horizontal Cap 770 994 Rigid Pipe Adaptor Must use with all rigid piping 946 506 P Vent Guard Optional 946 606 Starter collar reducer 5 x 8 to 4 x 6 5 8 946 625 Vinyl Siding Standoff AstroCap XL Note When using Metal Fab Sure Seal Rigid Piping please note that the Adaptor 4DDA must be used in conjunction with FPI Rigid Pipe Adaptor 510 994 Offset Pipe Selection Use this table to deter...

Page 25: ...ions with a maximum continuous vent maximum horizontal length of 3ft 0 9m Note Must use optional rigid pipe adaptor Part 770 994 when using Rigid Pipe vent systems Maintain clearance to combustibles Horizontal vent must be supported every 3 feet Firestops are required at each floor level and whenever passing through a wall 2 0 12 6 4 8 10 2 0 6 4 8 Vertical Height Feet Rigid 44 1 4 1 1m Horizontal...

Page 26: ...42 1 3 to center line No other application is approved 1 8 dia flexible liner 4 ft length 2 5 dia flexible liner 4 ft length 3 spring spacers 4 4 thimble 5 AstroCapXL termination cap 1 6 screws 12 7 tube of Mill Pac 1 8 plated screws 8 9 screws 8 x 1 1 2 Drill Point Stainless Steel 4 10 vinyl siding standoff Notes 1 Liner sections should be continuous without any joints or seams 2 Only Flex pipe p...

Page 27: ... Vent No Vertical Rise When venting with a 90 elbow directly off the unit must use 5 X 8 AstroCapXL Flex vent or approved Rigid Vent System Max 3 ft horizontal run B Rear Vent w Horizontal Termination Can only use 5 x 8 venting Max 3ft horizontal run B A HORIZONTAL TERMINATIONS RIGID PIPE 5 X 8 Rigid Pipe Adaptor Pipe Length Horizontal Termination Cap Wall Thimble Vinyl Siding Standoff Optional ...

Page 28: ...inimum vent configuration when using a rear vent application with a horizontal termination in a corner installation Kit 946 612 Includes 1 AstroCap XL 946 623 P 1 Rigid Pipe Adaptor 770 994 1 Vinyl Siding Standoff Optional 946 625 1 Wall Thimble 58DVA WT 1 6 galvanized rigid pipe 58DVA 06 1 8 1 2 galvanized pipe extension 58DVA 08A 1 45º galvanized elbow 58DVA E45 1 90 ml MillPac 948 128 26 1 2 673...

Page 29: ...R PART 946 606 770 994 RIGID PIPE ADAPTOR The diagram shows all allowable combinations of vertical runs with horizontal terminations using one 90o two 45o elbows equal one 90o elbow Maintainclearancestocombustiblesaslistedin Clearances section Horizontal vent must be supported every 3 feet Firestops are required at each floor level and whenever passing through a wall A wall thimble is mandatory fo...

Page 30: ...ired it must be used with vinyl siding measure to outside surface of wall without siding and add 2 inches Note The 4 x 6 5 8 Regency Flex Kits 946 515 946 516 are not approved for use with this fireplace Only rigid pipe may be used when 4 x 6 5 8 is used The FPI AstroCapTM and FPI Riser Vent terminal are certified for installations using FPI venting systems as well as Simpson Dura Vent Direct Vent...

Page 31: ...ust use reducer 946 606 and rigid pipe adaptor 770 994 No Vent Restrictor Installed HORIZONTAL TERMINATIONS THREE 3 90O ELBOWS RIGID PIPE 4 X 6 5 8 Lengths do not include elbow indicated Must use reducer 946 606 and rigid pipe adaptor 770 994 Option V H V V1 H H1 A 0 Min 1 Max 1 Min 2 Max B 1 Min 2 Max 3 Min 3 Max C 2 Min 2 Max 5 Min 4 Max D 3 Min 2 Max 7 Min 5 Max E 4 Min 3 Max 9 Min 6 Max F 5 Mi...

Page 32: ...each floor level and whenever passing through a wall Maintain clearances to combustibles as listed in the Clearances section Refer to the Vent Restrictor Position section for details on how to change the vent restrictor from the factory setting to 2 14 opening 1 5 8 opening and to 1 1 16 opening Note Must use optional flue adapter when using Rigid Pipe Part 770 994 Maximum 35 5 ft 10 m 8 Minimum 8...

Page 33: ... Max 6 Min E 4 Min 5 Max 7 Min F 5 Min 6 Max 8 Min G 6 Min 7 Max 9 Min H 7 Min 8 Max 10 Min With these options max total pipe length is 30 feet with min of 10 feet total vertical and max 8 feet total horizontal Please note min 1 foot between 90o elbows is required One 90o elbow Two 45o elbows Lengths do not include elbow indicated Must use reducer 946 606 and rigid pipe adaptor 770 994 No Vent Res...

Page 34: ...ed Parts Part Description 946 529 Co linear DV Vertical Termination Cap 948 305 3 Flex 35 ft 946 563 Co Axial to Co Linear Adapter Kit whichcontainsthefollowing Co linear Flex Adapter Outer Pipe Inner Pipe Adapter 770 994 Rigid Pipe Adaptor 946 606 Vent Reducer Alternate Approved Caps 46dva VC Vertical Termination Cap 46dva VCH High Wind Cap 46dva GK 3 Co linear Adapter with flashing Flex Liner Ex...

Page 35: ...E 10 Gas Fireplace 35 35 installation VERTICAL TERMINATIONS CO LINEAR FLEX SYSTEM INTO MASONRY FIREPLACES FOR BOTH RESIDENTIAL MANUFACTURED HOMES The shaded area in the Diagrams show the allowable vertical terminations ...

Page 36: ...using nails or screws through the top and side nailing strips Diagram 1 Note For best results and optimum performance with each approved venting system it is highly recommended to apply Mill Pac sealant supplied to every inner pipe connection Failuretodosomayresult in drafting or performance issues not covered under warranty Diagram 2 Horizontal runs of vent must be supported every 3 feet 0 9meter...

Page 37: ...ith the tabs to the outside wall making sure that the tabs are on top and bottom Fasten the other thimble half to the inside wall The thimble halves slip inside each other and can be adjusted for 2 x 4 or 2 x 6 walls 5 Slip the assembled liner and termination assembly through the thimble making sure the termination cap faces up there are markings on the cap that show which wayis up This will posit...

Page 38: ...level To install the Firestop spacer in a flat ceiling or wall cut a 10 inch square hole Frame the hole as shown in Diagram 2 and install the firestop 4 Assemble the desired lengths of pipe and elbows Ensurethatallpipesandelbowcon NOTE For best results and optimum perfor mance with each approved venting system it is highly recommended to apply Mill Pac sealant supplied to every inner pipe connecti...

Page 39: ...river Note Screw should be snug but do not over tighten HIGH ELEVATION This unit is approved in Canada for altitude to 4500ft CAN CGA 2 17 M91 ForNaturalGas installations above 4500 ft follow current CAN CGA B149 1 B36XTCE NG10 System Data For 0 to 4500 feet altitude Burner Inlet Orifice Sizes 35 Max Input Rating 31 000 Btu h Min Input Rating 21 500 Btu h Supply Pressure min 5 0 w c Manifold Press...

Page 40: ...pper Motor 1 919 437 Instruction Sheet Installation of LP Conversion Kit 9 Re install pilot cap wire clip and pilot shield 10 Remove burner orifice with a 1 2 wrench Use another wrench to hold on to the elbow behind the orifice Discard orifice 11 Reinstall new burner orifice LPG stamped 51 and tighten 6 Remove the wire clip below the pilot cap 8 Unscrew the pilot orifice with the allen key then re...

Page 41: ...ring the burner assembly and rear log tray so the panel is not damaged Note Ensure that an equal space gap is maintained on both the right and left side when installing the back panel 5 Remove the hex head screw on the upper left side of the firebox wall Position left brick panel in place and secure with the brick panel clip and screw 6 Slide top brick panel under left and back brick panel use car...

Page 42: ...heat to the unit Failure to do this will result in burn stains on panels which you will be unable to remove Not protected by product warranty 5 Repeat step 4 for left side panel 6 Reverse step 1 Final Installation 4 Remove 1 screw see inset A position right side panel in firebox position panel clip in place and secure with 1 screw see inset B Tighten the screw A B 1 Remove the heat deflector by re...

Page 43: ...C Top Middle Log D Top Right Log E Rear Log 902 156 Lava Rocks 902 179 Vermiculite 946 669 Platinum Embers supplied w packaged manual 1 Carefully remove the logs from the packaging and unwrap them The logs are fragile handle with care do not force into position 2 Spread vermiculite along the base of the firebox Vermiculite D E A C B 4 Place Log B on the front left side of the burner Position the n...

Page 44: ... the front right side of the burner Position the notch on the bottom right side of the log into the right side of the grate Slide Log A back towards Log E until the flat surface on Log A rests up against the tabs on the burner and grate this maintains a necessary gap between Logs A E Note Use the notch on the bottom of Log A as a guide see below Tabs on burner grate Back of Log A A 7 The notch on ...

Page 45: ...ound the lava rocks Avoid stacking platinum embers Platinum embers may be placed over burner ports 9 Position Log C with the flat side toward Log E Fit Log C onto left peg on Log E the notch on the bottom of Log C rests against the 3rd from the left grate post 10 Test fire to ensure proper light off make sure flame flows smoothly from one end of the burner to the other If there is any flame hesita...

Page 46: ... dangerous operation Caution Ensure that the wires do not touch any hot surfaces and are away from sharp edges Proflame System Configuration 886 GTMF Wire Diagram SureFire Switch 885 1 of 10 AC Adaptor WIRING DIAGRAM This heater does not require a 120V A C supply for operation but it is highly recommended to install the supplied AC adaptor to eliminate the need for batteries In case of a power fai...

Page 47: ...ff 2 Remove the mesh barrier and standard flush door Diagram 2 Diagram 3 Diagram 4 Push Fan down on mounting pins Electrical Receptacle Ground Lug Plug fan power cord into receptacle rear Mounting Pins 5 Slide the thermodisc cover assembly into the bracket clip on the underside of the firebox Check that no wire will touch the hot surfaces Diagram 3 and 4 6 Install the Fan Control Module FCM on to ...

Page 48: ...WIRING DIAGRAM WITH OPTIONAL FAN SureFire Switch CAUTION Labelallwirespriortodisconnection whenservicingcontrols Wiringerrorscancause improper and dangerous operation Caution Ensure that the wires do not touch any hot surfaces and are away from sharp edges ...

Page 49: ...es will be located near the gas valve Disconnect greenTH wire Green Wires White Connector 3 Connect one thermostat lead to female connector using male spade con nector see picture below CAUTION Do not wire Thermostat wires to 120V wire 4 Connect the other thermostat lead to male connector disconnected from Step1using a female spade connector see picture below When complete turn remote receiver to ...

Page 50: ...te to the firebox base Discard cover plate keep the 2 screws 6 From inside the firebox feed the wires from the bottom of the light assembly through the opening exposed after the removal of the cover plate 7 When light assembly has been fully seated secure in place with 2 screws that were removed from the cover plate 8 From underneath the firebox slide back the protective sheath on the plug wiring ...

Page 51: ...ng to the base of the unit Ensure wiring does not come into contact with the fan blades or any sharp metal edges Wire Clip Gasket Ground Lug 15 Install a gasket over top of the bulb Installed diffuser shown below with 2 options a With amber glass plate for use with units without panels or with brick panels Left and right side tabs to be bent down 90 degrees as shown below Image A b Amber glass pla...

Page 52: ...ocated on the bottom left side of the unit 20 Turn on electrical supply test lights 1 Follow steps 1 4 from previous page 2 Remove 2 screws to remove light diffuser plus gasket 3 Replace thebulb donottouchbulbwithbarehands useglovesorbulb packaging to protect bulb 4 Reinstall the gasket and light diffuser 5 Reverse steps 4 1 Ground Wire Receptacle BULB REPLACEMENT ...

Page 53: ...e by AC adaptor Break Tab on Black hot side Ground Ground Copper Black Hot White Neutral Do not break Tab on White neutral side Clamp Connector Receptacle located inside the unit Supplied with the appliance NOTE ON OFF switch all wires supplied by others Scheme 2 Only Use if Optional Fan is purchased Green Optional Accent Light Receptacle located inside the unit Extension Cord NOTE Lights can be t...

Page 54: ...barrier on both sides from the bot tom Lift up and out slightly to release from bottom magnets and to release hooks on mesh frame from brackets inside unit see below Hooks on mesh barrier frame 2 When hooks are clear of the bracket tilt mesh frame out slightly from the bottom and manoeuvre mesh out 3 To reinstall reverse steps ...

Page 55: ...ith tabs in firebox Hook slots on to tabs and lower door slowly See Diagram 1 2 Lower the flush door then hook the 2 adjustable tension latches close the latches to secure the flush door See Diagram 2 Diagram 1 Tabs in Firebox Diagram 2 Adjustable Tension Latch location Note To remove Flush Glass door reverse Steps 1 and 2 ...

Page 56: ...tion and fog the glass This condensation is normal and will disappear in a few minutes as the glass heats up DO NOT ATTEMPT TO CLEAN THE GLASS WHILE IT IS STILL HOT DO NOT BURN THE UNIT WITHOUT THE GLASS DOOR IN PLACE FIRST FIRE NORMAL OPERATING SOUNDS OF GAS APPLIANCES It is possible that you will hear some sounds from yourgasappliance Thisisperfectlynormaldueto the fact that there are various ga...

Page 57: ...here is no flame ignition rectification the board will stop sparking for approximately 35 seconds After wait time the board will start second try for ignition by sparking for approximately 60 seconds If there is still no positive ignition the board will go into lock out The system will need to be reset as follows a Turn the system off using ON OFF switch or press ON OFF button if using optional re...

Page 58: ...service agency or gas supplier AVERTISSEMENT Quiconque ne respecte pas à la lettre les instructions dans la présente notice risquede déclencher un incendie ou une explosion entraînant des dommages des blessures ou la mort Une installation d ajustement de modification de service ou d entretien peut provoquer des blessures ou des dommages matériels Reportez vous au manuel du propriétaire de l inform...

Page 59: ...the gas valve before cleaning Forrelighting refertolightinginstructions Keep the burner and control compartment clean by brushing and vacuuming at least once a year When cleaning the logs use a soft clean paint brush as the logs are fragile and easily damaged 2 Clean appliance and door with a damp cloth neverwhenunitishot Neveruseanabrasive cleaner The glass should be cleaned with a gas fireplace ...

Page 60: ... and ground wires from the valve as shown below Diagram 3 Diagram 5 Diagram 8 Diagram 6 INSTALLING VALVE 1 Place new valve tray into position 2 Reinstall the 8 hold down screws 3 Hook up the 2 TP and 2 TH wires to the ap propriate connections on the valve 4 Reinstall the rear log tray 5 Install burner grate assembly 6 Hook up the gas line and check for gas leaks with a soap and water solution or a...

Page 61: ...crew 1 4 20 x 3 5 NC Gr5 14 940 382 P Ceramic Glass 15 556 012 Door Frame 16 Outerbox Assembly 17 Firebox Assembly Part Description 18 578 917 Fan Assembly 19 910 215 P Fan Motor 120 Volts 911 030 Fan Control Module 20 911 159 Power Cord 120 Volts 23 910 142 Thermodisc Fan Auto ON OFF 24 946 000 Round Duct Adaptor 25 910 367 Box Plastic Switch Receptacle 26 910 412 Fan Speed Controller 27 910 417 ...

Page 62: ...62 Bellavista B36XTCE 10 Gas Fireplace 62 parts list 1 2 3 4 5 6 7 8 13 16 17 36 15 14 9 18 11 10 12 MAIN ASSEMBLY ...

Page 63: ...ifice 51 LP 6 911 084 Valve NG 911 085 Valve LP Part Description 9 576 574E P Valve Assembly NG 576 576E P Valve Assembly LP 10 911 006 Pilot Assembly NG 911 007 Pilot Assembly LP 911 012 Ignition Board DBC 911 013 Wiring Harness Switch 911 018 Battery Holder 911 037 Flame Sensor 911 038 Flame Electrode 911 039 Pilot Hood 910 432 Pilot Tube 911 032 Remote Wiring Harness 578 930 Log Set Complete No...

Page 64: ...64 Bellavista B36XTCE 10 Gas Fireplace 64 notes ...

Page 65: ...Bellavista B36XTCE 10 Gas Fireplace 65 65 notes ...

Page 66: ...66 Bellavista B36XTCE 10 Gas Fireplace 66 notes ...

Page 67: ...ent parts and issue credit once the replaced component has been returned to Regency and evalu ated for manufacturer defect The authorized selling dealer is responsible for all in field service work carried out on your Regency product Regency will not be liable for results or costs of workmanship from unauthorized service persons or dealers At all times Regency reserves the right to inspect product...

Page 68: ...__________________________________________________________ Phone ____________________________________________________________ Date Installed _______________________________________________________ Serial No ___________________________________________________________ Register your Regency warranty online www regency fire com Reasons to register your product online today View and modify a list of al...

Reviews: