12
If the motor does not shut off at the end of
the cycle, check the delay times and wait for
the delays to time out. Also, make sure that
there is no call for “Continuous fan” on the “G”
terminal. This motor may take a while to come
to a complete stop with selected delays and the
normal ramp down.
If the 2.0 / 2.3 / Eon
®
/ 3.0 motor
has proper high
voltage and ground at the 5-pin connector, go
to the “Troubleshooting with the TECINspect
®
Service Tool” section on page 16. If the 2.5
motor has proper high voltage and ground at the
5-pin connector, the equipment manufacturer’s
checks, located in their service manuals, must be
referenced. This guide cannot troubleshoot the
communication to the 2.5 motor. The TECINspect
Service Tool is not designed for use on the 2.5
motor.
Checking the high voltage on the 5-pin
connector is outlined in step 1 on page 13.
3.
4.